ESPECIFICACIONES DE MEDICION PARA ACOMETIDAS MONOFASICAS

ESPECIFICACIONES DE MEDICION PARA ACOMETIDAS MONOFASICAS. CFE EM-BT1. CFE EM-BT101 ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, AREA URBANA, RED AEREA, CON BARDA FRONTAL

ocean
Download Presentation

ESPECIFICACIONES DE MEDICION PARA ACOMETIDAS MONOFASICAS

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. ESPECIFICACIONES DE MEDICION PARA ACOMETIDAS MONOFASICAS CFE EM-BT1 • CFE EM-BT101 ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, AREA URBANA, RED AEREA, CON BARDA FRONTAL • CFE EM-BT102 ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, AREA URBANA, RED AEREA, CONSTRUCCION AL FONDO DE LA PROPIEDAD • CFE EM-BT103 ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, AREA URBANA, RED AEREA, CON BARDA LATERAL • CFE EM-BT104 ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, AREA URBANA, RED SUBTERRANEA, CON BARDA FRONTAL • CFE EM-BT105 ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, RED SUBTERRANEA, CONSTRUCCION AL FONDO DE LA PROPIEDAD • CFE EM-BT106 ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, RED AEREA, EN ZONAS DE ARQUITECTURA COLONIAL • CFE EM-BT107 ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, RED SUBTERRANEA, EN ZONAS DE ARQUITECTURA COLONIAL • CFE EM-BT108 ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, AREA SUBURBANA, RED AEREA, CON BARDA FRONTAL • CFE EM-BT109 ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, AREA SUBURBANA, RED AEREA CONSTRUCCION AL FONDO DE LA PROPIEDAD • CFE EM-BT110 ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, AREA RURAL, RED AEREA, CONSTRUCCION AL LIMITE DE LA PROPIEDAD • CFE EM-BT111 ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, AREA RURAL, RED AEREA CONSTRUCCION AL FONDO DE LA PROPIEDAD

  2. ACOTACIONES EN mm SIN ESCALA ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, AREA URBANA, RED AEREA, CON BARDA FRONTAL CFE EM-BT101 HOJA 1 DE 2 VISTA DE CONJUNTO 1 F F N N 500 mm DE LONGITUD 2 3 12 # 250 4800 4 11 C F E 13 6 5 1800 7 A INSTALACION INTERIOR 8 9 10 VISTA LATERAL VISTA FRONTAL

  3. ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, AREA URBANA, RED AEREA, CON BARDA FRONTAL CFE EM-BT101 HOJA 2 DE 2 F N DE LAACOMETIDA ESPECIFICACIONES DE MATERIALES Y EQUIPO DE LA BASE ENCHUFE F N 2 A CARGO DEL USUARIO NEUTRO 1 MUFA INTEMPERIE DE 32 mm (1 1/4") DE DIAMETROTUBO CONDUIT DE FIERRO GALVANIZADO PARED GRUESA DE 32 mm (1 1/4") DE DIAMETRO Y CON 3000 mm DE LONGITUDCABLE DE COBRE THW CALIBRE 8.367 mm2 (8 AWG) DESDE LA MUFA HASTA EL INTERRUPTOR, EL FORRO DEL CONDUCTOR NEUTRO DE COLOR BLANCO Y EL DE LA FASE DIFERENTE AL BLANCOBASE ENCHUFE DE 4 TERMINALES, 100 AMPERESINTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 2 POLOS, 1 TIRO, 250 VOLTS, 30 AMPERES, A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIEREDUCCION DE 32 mm (1 1/4") A 12,7 mm (1/2")TUBO CONDUIT PARED DELGADA DE 12,7 mm (1/2") DE DIAMETROALAMBRE O CABLE DE COBRE CALIBRE 8.367 mm2 (8 AWG) MINIMOCONECTOR PARA VARILLA DE TIERRAVARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS FASE 5 2 12 3 4 5 4 6 7 7 6 8 A INSTALACIONINTERIOR 9 10 8 A LA VARILLADE TIERRA DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR INSTALADO POR C.F.E. 11 MEDIDOR TIPO ENCHUFE DE 15 AMPERES, 1 FASE, 2 HILOS, 120 VOLTS (F121) ARO PARA BASE ENCHUFE DE ACERO INOXIDABLE 12 SELLO DE PLASTICO 13 AL EMPOTRAR LA BASE ENCHUFE, ESTA DEBE SALIR COMO MINIMO 5 mm DEL MURO PARA COLOCAR EL MEDIDOR Y EL ARO NOTAS : A LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBEESTAR COMO MAXIMO A 35 METROS DEL POSTE DESDE EL CUAL SE DARA EL SERVICIOEL CONDUCTOR DEL NEUTRO DEBE CONECTARSE DIRECTO A LA CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION ( FUSIBLE O TERMOMAGNETICO ) LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL LIMITE DE PROPIEDAD, EMPOTRADA O SOBREPUESTA EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO OCONSTRUCCIONLA ALTURA DE LA MUFA PARA RECIBIR LA ACOMETIDA ES DE 4800mm EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm DEL MEDIDOR MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE BASE ENCHUFE B ARO C D MURO E F G DETALLE DE EMPOTRADO DE LA BASE PROPIEDADDEL USUARIO VIAPUBLICA MEDIDOR VISTA DE PLANTA SIN ESCALA

  4. N F ACOTACIONES EN mm SIN ESCALA ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, AREA URBANA, RED AEREA, CONSTRUCCION AL FONDO DE LA PROPIEDAD CFE EM-BT102 HOJA 1 DE 2 VISTA DE CONJUNTO 1 3 F N 500 mm DELONGITUD 2 220 MINIMO 220 MINIMO MURETEDECONCRETO 13 4800 11 4 12 C F E ARMADO DE CONCRETO Y VARILLA 2800 MINIMO 14 5 6 1800 7 A INSTALACIONINTERIOR 9 8 A INSTALACIONINTERIOR CIMIENTO DE PIEDRA CON CEMENTO Y ARENA 10 VISTA LATERAL VISTA FRONTAL

  5. ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, AREA URBANA, RED AEREA, CONSTRUCCION AL FONDO DE LA PROPIEDAD CFE EM-BT102 HOJA 2 DE 2 F N DE LAACOMETIDA ESPECIFICACIONES DE MATERIALES Y EQUIPO DE LA BASE ENCHUFE F N 2 A CARGO DEL USUARIO 1 MUFA INTEMPERIE DE 32 mm (1 1/4") DE DIAMETROTUBO CONDUIT DE FIERRO GALVANIZADO PARED GRUESA DE 32 mm (1 1/4") DE DIAMETRO Y CON 3000 mm DE LONGITUDCABLE DE COBRE THW CALIBRE 8.367 mm2 (8 AWG) DESDE LA MUFA HASTA EL INTERRUPTOR, EL FORRO DEL CONDUCTOR NEUTRO DE COLOR BLANCO Y EL DE LA FASE DIFERENTE AL BLANCOBASE ENCHUFE DE 4 TERMINALES, 100 AMPERESINTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 2 POLOS, 1 TIRO, 250 VOLTS, 30 AMPERES, A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIEREDUCCION DE 32 mm (1 1/4") A 12,7 mm (1/2")TUBO CONDUIT PARED DELGADA DE 12,7 mm (1/2") DE DIAMETROALAMBRE O CABLE DE COBRE CALIBRE 8.367 mm2 (8 AWG) MINIMOCONECTOR PARA VARILLA DE TIERRAVARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS MURETE DE ACUERDO A LO INDICADO NEUTRO FASE 2 5 13 3 4 5 4 6 7 7 8 6 9 A INSTALACIONINTERIOR 10 11 8 A LA VARILLADE TIERRA DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR INSTALADO POR C.F.E. 12 MEDIDOR TIPO ENCHUFE DE 15 AMPERES, 1 FASE, 2 HILOS, 120 VOLTS (F121) ARO PARA BASE ENCHUFE DE ACERO INOXIDABLE 13 14 SELLO DE PLASTICO AL EMPOTRAR LA BASE ENCHUFE, ESTA DEBE SALIR COMO MINIMO 5 mm DEL MURO PARA COLOCAR EL MEDIDOR Y EL ARO NOTAS : A LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBEESTAR COMO MAXIMO A 35 METROS DEL POSTE DESDE EL CUAL SE DARA EL SERVICIOEL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A LA CARGA SIN MEDIO PASAR POR ALGUN MEDIO DE PROTECCION ( FUSIBLE O TERMOMAGNETICO ) LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL LIMITE DE PROPIEDAD, EMPOTRADA O SOBREPUESTA EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO OCONSTRUCCIONLA ALTURA DE LA MUFA PARA RECIBIR LA ACOMETIDA ES DE 4800mm EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm DEL MEDIDOR MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE BASE ENCHUFE B ARO C D MURO E F G DETALLE DE EMPOTRADO DE LA BASE PROPIEDADDEL USUARIO VIAPUBLICA MEDIDOR VISTA DE PLANTA SIN ESCALA

  6. # 568 6 ACOTACIONES EN mm SIN ESCALA ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, AREA URBANA, RED AEREA, CON BARDA LATERAL CFE EM-BT103 HOJA1 DE 2 VISTA DE CONJUNTO 1 F F N N 2 500 mm DELONGITUD 3 12 4 4800 11 C F E 5 13 2800 MINIMO 7 1800 8 A INSTALACION INTERIOR 9 10 VISTA LATERAL VISTA FRONTAL

  7. ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, AREA URBANA, RED AEREA, CON BARDA LATERAL CFE EM-BT103 HOJA 2 DE 2 F N DE LAACOMETIDA ESPECIFICACIONES DE MATERIALES Y EQUIPO DE LA BASE ENCHUFE F N 2 A CARGO DEL USUARIO NEUTRO 1 MUFA INTEMPERIE DE 32 mm (1 1/4") DE DIAMETROTUBO CONDUIT DE FIERRO GALVANIZADO PARED GRUESA DE 32 mm (1 1/4") DE DIAMETRO Y CON 3000 mm DE LONGITUDCABLE DE COBRE THW CALIBRE 8.367 mm2 (8 AWG) DESDE LA MUFA HASTA EL INTERRUPTOR, EL FORRO DEL CONDUCTOR NEUTRO DE COLOR BLANCO Y EL DE LA FASE DIFERENTE AL BLANCOBASE ENCHUFE DE 4 TERMINALES, 100 AMPERESINTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 2 POLOS, 1 TIRO, 250 VOLTS, 30 AMPERES, A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIEREDUCCION DE 32 mm (1 1/4") A 12,7 mm (1/2")TUBO CONDUIT PARED DELGADA DE 12,7 mm (1/2") DE DIAMETROALAMBRE O CABLE DE COBRE CALIBRE 8.367 mm2 (8 AWG) MINIMOCONECTOR PARA VARILLA DE TIERRAVARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS FASE 5 2 12 3 4 5 4 6 7 7 6 8 A INSTALACIONINTERIOR 9 10 8 A LA VARILLADE TIERRA DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR INSTALADO POR C.F.E. 11 MEDIDOR TIPO ENCHUFE DE 15 AMPERES, 1 FASE, 2 HILOS, 120 VOLTS (F121) ARO PARA BASE ENCHUFE DE ACERO INOXIDABLE 12 SELLO DE PLASTICO 13 AL EMPOTRAR LA BASE ENCHUFE, ESTA DEBE SALIR COMO MINIMO 5 mm DEL MURO PARA COLOCAR EL MEDIDOR Y EL ARO NOTAS : A LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBEESTAR COMO MAXIMO A 35 METROS DEL POSTE DESDE EL CUAL SE DARA EL SERVICIOEL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A LA CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION ( FUSIBLE O TERMOMAGNETICO ) LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL LIMITE DE PROPIEDAD, EMPOTRADA O SOBREPUESTA EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO OCONSTRUCCIONLA ALTURA DE LA MUFA PARA RECIBIR LA ACOMETIDA ES DE 4800mm EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm DEL MEDIDOR MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE BASE ENCHUFE B ARO C D MURO E F G DETALLE DE EMPOTRADO DE LA BASE PROPIEDADDEL USUARIO VIAPUBLICA MEDIDOR VISTA DE PLANTA SIN ESCALA

  8. ACOTACIONES EN mm SIN ESCALA ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, AREA URBANA, RED SUBTERRANEA, CON BARDA FRONTAL CFE EM-BT104 HOJA 1 DE 2 #411 C F E DUCTO RED B.T. DUCTO RED B.T. REGISTRO DE ACOMETIDAEN B.T. VISTA DE CONJUNTO 12 4 11 C F E 5 13 6 1800 1800 7 2 14 VER DETALLE "A" 8 1 9 10 SECUNDARIO DE LA RED VISTA FRONTAL VISTA LATERAL

  9. ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, AREA URBANA, RED SUBTERRANEA, CON BARDA FRONTAL CFE EM-BT104 HOJA 2 DE 2 3 F T N ESPECIFICACIONES DE MATERIALES Y EQUIPO 12 4 A CARGO DEL USUARIO 5 1 CODO DE PVC 32 mm (1 1/4") DE DIAMETRO2 TUBO RIGIDO DE PVC 32 mm (1 1/4") DE DIAMETRO3 CABLE DE COBRE THW CALIBRE 8.367 mm2 ( 8 AWG) MINIMO . DESDE LA BASE HASTA EL INTERRUPTOR, CON FORRO DEL . CONDUCTOR NEUTRO DE COLOR BLANCO Y EL DE LA FASE . DIFERENTE AL BLANCO 4 BASE ENCHUFE DE 4 TERMINALES, 100 AMPERES5 INTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE 2 POLOS, 1 TIRO, 250 VOLTS, 30 AMPERES, A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIE6 REDUCCION DE PVC DE 32 mm (1 1/4") A 12,7 mm (1/2")7 TUBO RIGIDO DE PVC DE 12,7 mm (1/2") DE DIAMETRO8 ALAMBRE O CABLE DE COBRE CALIBRE 8.367 mm2 ( 8 AWG) MINIMO9 CONECTOR PARA VARILLA DE TIERRA10 VARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS NEUTRO FASE AINSTALACIONINTERIOR 8 2 A LA VARILLADE TIERRA 7 DE LA RED DEBAJA TENSION F N DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR INSTALADO POR C.F.E. AL EMPOTRAR LA BASE ENCHUFE, ESTA DEBE SALIR COMO MINIMO 5 mm DEL MURO PARA COLOCAR EL MEDIDOR Y EL ARO 11 MEDIDOR TIPO ENCHUFE DE 15 AMPERES, 1 FASE, 2 HILOS, 120 VOLTS (F121)12 ARO PARA BASE ENCHUFE DE ACERO INOXIDABLE 13 SELLO DE PLASTICO 14 CABLE MONOPOLAR XLP 15 CONECTOR EMPALME A COMPRESION, TENSION MINIMA, TIPO ZAPATA16 MANGA TERMOCONTRACTIL O REMOVIBLE BASE ENCHUFE ARO NOTAS : MURO DECONCRETO A LA PREPARACION DEBE ESTAR MAXIMO A 35 Mts. DEL REGISTRO B EL CONDUCTOR DEL NEUTRO DEBE CONECTARSE DIRECTO A LA . CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION ( FUSIBLE . O TERMOMAGNETICOC LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL . LIMITE DE LA PROPIEDAD EMPOTRADA D EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm . DEL MEDIDOR E MARCAR EL NUMERO OFICIAL DEL DOMICILO EN FORMA . PERMANENTE DETALLE DE EMPOTRADO DE LA BASE DISPONIBLES 16 15 ACOMETIDA SECUNDARIODE LA RED DETALLE "A" PROPIEDADDEL USUARIO VIAPUBLICA MEDIDOR VISTA DE PLANTA SIN ESCALA

  10. ACOTACIONES EN mm SIN ESCALA ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, RED SUBTERRANEA, CONSTRUCCION AL FONDO DE LA PROPIEDAD CFE EM-BT105 HOJA 1 DE 2 DUCTO RED DE BAJA TENSION VISTA DE CONJUNTO 220 220 11 5 14 2 2000 1800 15 8 VISTA FRONTAL VISTA LATERAL

  11. ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, RED SUBTERRANEA, CONSTRUCCION AL FONDO DE LA PROPIEDAD CFE EM-BT105 HOJA 2 DE 2 3 DE LA BASE ENCHUFE 13 ESPECIFICACIONES DE MATERIALES Y EQUIPO 4 NEUTRO A CARGO DEL USUARIO 5 FASE 1 CODO DE PVC 32 mm ( 1 1/4” ) DE DIAMETROTUBO RIGIDO DE PVC 32 mm ( 1 1/4” ) DE DIAMETROCABLE DE COBRE THW CALIBRE 8.367 mm2 (8 AWG) DESDE LA BASE HASTA EL INTERRUPTOR, EL FORRO DEL CONDUCTOR NEUTRO DE COLOR BLANCO Y EL DE LA FASE DIFERENTE AL BLANCOBASE ENCHUFE DE 4 TERMINALES, 100 AMPERES INTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 2 POLOS, 1 TIRO, 250 VOLTS, 30 AMPERES, A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIEREDUCCION DE PVC 32 mm (1 1/4") A 12,7 mm (1/2")TUBO RIGIDO PVC DE 12.7 mm ( 1/2” ) DE DIAMETROALAMBRE O CABLE DE COBRE CALIBRE 8.367 mm2 (8 AWG) MINIMOCONECTOR PARA VARILLA DE TIERRAVARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS MURETE DE ACUERDO A LO INDICADO 2 3 6 4 5 7 2 6 7 DE LA RED DEBAJA TENSION 8 F N A INSTALACION INTERIOR 9 10 11 DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR INSTALADO POR C.F.E. AL EMPOTRAR LA BASE ENCHUFE, ESTA DEBERA SALIR COMO MINIMO 5 mm DEL MURO PARA COLOCAR EL MEDIDOR Y EL ARO 12 MEDIDOR TIPO ENCHUFE DE 15 AMPERES, 1 FASE,2 HILOS, 120 VOLTS (F121) ARO PARA BASE ENCHUFE DE ACERO INOXIDABLE 13 SELLO DE PLASTICO 14 15 CABLE DE ALUMINIO XLP 16 CONECTOR EMPALME A COMPRESION, TENSION MINIMA, TIPO ZAPATA17 MANGA TERMOCONTRACTIL O REMOVIBLE BASE ENCHUFE ARO NOTAS : MURO DECONCRETO A LA PREPARACION DEBE ESTAR MAXIMO A 35 Mts. DEL REGISTRO B EL CONDUCTOR DEL NEUTRO DEBE CONECTARSE DIRECTO A LA . CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION ( FUSIBLE . O TERMOMAGNETICOC LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL . LIMITE DE LA PROPIEDAD EMPOTRADA D EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm . DEL MEDIDOR E MARCAR EL NUMERO OFICIAL DEL DOMICILO EN FORMA . PERMANENTE DETALLE DE EMPOTRADO DE LA BASE DISPONIBLES 17 16 ACOMETIDA SECUNDARIODE LA RED PROPIEDADDEL USUARIO VIAPUBLICA MEDIDOR VISTA DE PLANTA SIN ESCALA

  12. 6 ACOTACIONES EN mm SIN ESCALA ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, RED AEREA, EN ZONAS DE ARQUITECTURA COLONIAL CFE EM-BT106 HOJA 1 DE 2 72 74 76 VISTA DE CONJUNTO 3 1 F F 2 N 500 mm DELONGITUD N 11 4 4800 C F E 12 5 1800 13 MURODEADOBE 7 8 INTERIOR BANQUETA 9 10 VISTA FRONTAL VISTA LATERAL

  13. ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, RED AEREA, EN ZONAS DE ARQUITECTURA COLONIAL CFE EM-BT106 HOJA 2 DE 2 F N DE LA BASEENCHUFE DE LAACOMETIDA ESPECIFICACIONES DE MATERIALES Y EQUIPO N F T 2 A CARGO DEL USUARIO NEUTRO 1 MUFA INTEMPERIE DE 32 mm (1 1/4") DE DIAMETROTUBO CONDUIT DE FIERRO GALVANIZADO PARED GRUESA DE 32 mm (1 1/4") DE DIAMETRO Y CON 3000 mm DE LONGITUDCABLE DE COBRE THW CALIBRE 8.367 mm2 (8 AWG) DESDE LA MUFA HASTA EL INTERRUPTOR, EL FORRO DEL CONDUCTOR NEUTRO DE COLOR BLANCO Y EL DE LA FASE DIFERENTE AL BLANCOBASE ENCHUFE DE 4 TERMINALES, 100 AMPERESINTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 2 POLOS, 1 TIRO, 250 VOLTS, 30 AMPERES, A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIEREDUCCION DE 32 mm (1 1/4") A 12,7 mm (1/2")TUBO CONDUIT PARED DELGADA DE 12,7 mm (1/2") DE DIAMETROALAMBRE O CABLE DE COBRE CALIBRE 8.367 mm2 (8 AWG) MINIMOCONECTOR PARA VARILLA DE TIERRAVARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS FASE 5 2 12 3 A INSTALACIONINTERIOR 4 5 4 6 6 7 7 8 9 A LA VARILLADE TIERRA 10 A LA VARILLADE TIERRA DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR INSTALADO POR C.F.E. 11 MEDIDOR TIPO ENCHUFE DE 15 AMPERES, 1 FASE, 2 HILOS, 120 VOLTS (F121) ARO PARA BASE ENCHUFE DE ACERO INOXIDABLE 12 300 SELLO DE PLASTICO 13 NOTAS : 300 A. EL NICHO PARA MEDIDOR SERA DE CONCRETO ARMADO DE 300 X 300 X 300 mm B. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR COMO MAXIMO A 35 METROS DEL POSTE DESDE EL CUAL SE DARA EL SERVICIO. C. EL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A LA CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION ( FUSIBLE O TERMOMAGNETICO ) D. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL LIMITE DE LA PROPIEDAD EMPOTRADA E. EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO O CONSTRUCCIONF. LA ALTURA DE LA MUFA PARA RECIBIR LA ACOMETIDA SERA DE 4800 mm G. EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm DEL MEDIDOR H. MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE MALLAMETALICA PUERTA DEL NICHOCON APLANADO IDENTICOAL MATERIAL DE LA FACHADA DETALLE PUERTA DEL NICHO PROPIEDADDEL USUARIO MEDIDOR VIAPUBLICA VISTA DE PLANTA ACOTACIONES EN mm SIN ESCALA

  14. 6 ACOTACIONES EN mm SIN ESCALA ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, RED SUBTERRANEA, EN ZONAS DE ARQUITECTURA COLONIAL CFE EM-BT107 HOJA 1 DE 2 72 74 76 REGISTRO DE ACOMETIDA BAJA TENSION DUCTO RED BAJA TENSION DUCTO RED BAJA TENSION VISTA DE CONJUNTO 4 300 300 11 300 C F E 5 12 1800 13 MURODEADOBE 7 2 8 14 INTERIOR BANQUETA 1 9 10 VISTA FRONTAL VISTA LATERAL

  15. ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION RED SUBTERRANEA, EN ZONAS DE ARQUITECTURA COLONIAL CFE EM-BT107 HOJA 2 DE 2 3 DE LA BASE ENCHUFE 12 ESPECIFICACIONES DE MATERIALES Y EQUIPO 4 NEUTRO A CARGO DEL USUARIO 5 FASE 1 CODO DE PVC 32 mm (1 1/4") DE DIAMETRO2 TUBO RIGIDO DE PVC 32 mm (1 1/4") DE DIAMETRO3 CABLE DE COBRE THW CALIBRE 8.367 mm2 ( 8 AWG) MINIMO . DESDE LA BASE HASTA EL INTERRUPTOR, CON FORRO DEL . CONDUCTOR NEUTRO DE COLOR BLANCO Y EL DE LA FASE . DIFERENTE AL BLANCO 4 BASE ENCHUFE DE 4 TERMINALES, 100 AMPERES5 INTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) o DE CARTUCHO FUSIBLE 2 POLOS, 1 TIRO, 250 VOLTS, 30 AMPERES, A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIE6 REDUCCION DE PVC DE 32 mm (1 1/4") A 12,7 mm (1/2")7 TUBO RIGIDO DE PVC DE 12,7 mm (1/2") DE DIAMETRO8 ALAMBRE O CABLE DE COBRE CALIBRE 8.367 mm2 ( 8 AWG) MINIMO9 CONECTOR PARA VARILLA DE TIERRA10 VARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS 6 7 2 DE LA RED DEBAJA TENSION F N DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR INSTALADO POR C.F.E. 11 MEDIDOR TIPO ENCHUFE DE 15 AMPERES, 1 FASE, 2 HILOS, 120 VOLTS (F121)12 ARO PARA BASE ENCHUFE DE ACERO INOXIDABLE 13 SELLO DE PLASTICO 14 CABLE DE ALUMINIO XLP 15 CONECTOR EMPALME A COMPRESION, TENSION MINIMA, TIPO ZAPATA16 MANGA TERMOCONTRACTIL O REMOVIBLE PROPIEDADDEL USUARIO MEDIDOR NOTAS : VIAPUBLICA A. EL NICHO PARA MEDIDOR SERA DE CONCRETO ARMADO DE 300 X 300 X 300 mm B. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR COMO MAXIMO A 35 METROS DEL REGISTRO. C. EL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A LA CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION ( FUSIBLE O TERMOMAGNETICO ) D. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL LIMITE DE LA PROPIEDAD EMPOTRADA E. EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO o CONSTRUCCIONG. EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm DEL MEDIDOR H. MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE VISTA DE PLANTA 300 300 DISPONIBLES 16 15 PUERTA DEL NICHOCON APLANADO IDENTICOAL MATERIAL DE LA FACHADA MALLAMETALICA DETALLE PUERTA DEL NICHO SECUNDARIODE LA RED ACOMETIDA SIN ESCALA DETALLE "A”

  16. N F ACOTACIONES EN mm SIN ESCALA ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, AREA SUBURBANA, RED AEREA, CON BARDA FRONTAL CFE EM-BT108 HOJA 1 DE 2 VISTA DE CONJUNTO 1 3 F N 500 mm DELONGITUD 2 12 4800 4 11 2800 MINIMO C F E 13 5 6 1800 7 A INSTALACIONINTERIOR 9 8 A INSTALACIONINTERIOR 10 VISTA LATERAL VISTA FRONTAL

  17. ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, AREA SUBURBANA, RED AEREA, CON BARDA FRONTAL CFE EM-BT108 HOJA 2 DE 2 F N DE LAACOMETIDA ESPECIFICACIONES DE MATERIALES Y EQUIPO DE LA BASE ENCHUFE F N 2 A CARGO DEL USUARIO NEUTRO 1 MUFA INTEMPERIE DE 32 mm (1 1/4") DE DIAMETROTUBO CONDUIT DE FIERRO GALVANIZADO PARED GRUESA DE 32 mm (1 1/4") DE DIAMETRO Y CON 3000 mm DE LONGITUDCABLE DE COBRE THW CALIBRE 8.367 mm2 (8 AWG) DESDE LA MUFA HASTA EL INTERRUPTOR, EL FORRO DEL CONDUCTOR NEUTRO DE COLOR BLANCO Y EL DE LA FASE DIFERENTE AL BLANCOBASE ENCHUFE DE 4 TERMINALES, 100 AMPERESINTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 2 POLOS, 1 TIRO, 250 VOLTS, 30 AMPERES, A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIEREDUCCION DE 32 mm (1 1/4") A 12,7 mm (1/2")TUBO CONDUIT PARED DELGADA DE 12,7 mm (1/2") DE DIAMETROALAMBRE O CABLE DE COBRE CALIBRE 8.367 mm2 (8 AWG) MINIMOCONECTOR PARA VARILLA DE TIERRAVARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS FASE 5 2 12 3 4 5 4 6 7 7 8 6 A INSTALACIONINTERIOR 9 10 8 A LA VARILLADE TIERRA DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR INSTALADO POR C.F.E. 11 MEDIDOR TIPO ENCHUFE DE 15 AMPERES, 1 FASE, 2 HILOS, 120 VOLTS (F121) ARO PARA BASE ENCHUFE DE ACERO INOXIDABLE 12 13 SELLO DE PLASTICO AL EMPOTRAR LA BASE ENCHUFE, ESTA DEBE SALIR COMO MINIMO 5 mm DEL MURO PARA COLOCAR EL MEDIDOR Y EL ARO NOTAS : LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBEESTAR COMO MAXIMO A 50 METROS DEL POSTE DESDE EL CUAL SE DARA EL SERVICIOEL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A LA CARGA SIN MEDIO PASAR POR ALGUN MEDIO DE PROTECCION ( FUSIBLE O TERMOMAGNETICO ) LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL LIMITE DE PROPIEDAD, EMPOTRADA O SOBREPUESTA EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO OCONSTRUCCIONLA ALTURA DE LA MUFA PARA RECIBIR LA ACOMETIDA ES DE 4800mm EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm DEL MEDIDOR MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE A BASE ENCHUFE B ARO C D MURO E F G DETALLE DE EMPOTRADO DE LA BASE PROPIEDADDEL USUARIO VIAPUBLICA MEDIDOR VISTA DE PLANTA SIN ESCALA

  18. N F ACOTACIONES EN mm SIN ESCALA ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, AREA SUBURBANA, RED AEREA CONSTRUCCION AL FONDO DE LA PROPIEDAD CFE EM-BT109 HOJA 1 DE 2 VISTA DE CONJUNTO 1 3 F 220 N 500 mm DELONGITUD 2 220 13 4800 4 12 2800 MINIMO C F E 14 5 6 1800 7 A INSTALACIONINTERIOR 9 8 A INSTALACIONINTERIOR CIMIENTO DE PIEDRA CON CEMENTO Y ARENA 10 VISTA LATERAL VISTA FRONTAL

  19. ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, AREA SUBURBANA, RED AEREA CONSTRUCCION AL FONDO DE LA PROPIEDAD CFE EM-BT109 HOJA 2 DE 2 F N DE LAACOMETIDA ESPECIFICACIONES DE MATERIALES Y EQUIPO DE LA BASE ENCHUFE F N 2 A CARGO DEL USUARIO NEUTRO 1 MUFA INTEMPERIE DE 32 mm (1 1/4") DE DIAMETROTUBO CONDUIT DE FIERRO GALVANIZADO PARED GRUESA DE 32 mm (1 1/4") DE DIAMETRO Y CON 3000 mm DE LONGITUDCABLE DE COBRE THW CALIBRE 8.367 mm2 (8 AWG) DESDE LA MUFA HASTA EL INTERRUPTOR, EL FORRO DEL CONDUCTOR NEUTRO DE COLOR BLANCO Y EL DE LA FASE DIFERENTE AL BLANCOBASE ENCHUFE DE 4 TERMINALES, 100 AMPERESINTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 2 POLOS, 1 TIRO, 250 VOLTS, 30 AMPERES, A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIEREDUCCION DE 32 mm (1 1/4") A 12,7 mm (1/2")TUBO CONDUIT PARED DELGADA DE 12,7 mm (1/2") DE DIAMETROALAMBRE O CABLE DE COBRE CALIBRE 8.367 mm2 (8 AWG) MINIMOCONECTOR PARA VARILLA DE TIERRAVARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS MURETE DE ACUERDO A LO INDICADO FASE 5 2 13 3 4 5 4 6 7 7 8 6 A INSTALACIONINTERIOR 9 10 11 8 A LA VARILLADE TIERRA DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR INSTALADO POR C.F.E. 12 MEDIDOR TIPO ENCHUFE DE 15 AMPERES, 1 FASE, 2 HILOS, 120 VOLTS (F121) ARO PARA BASE ENCHUFE DE ACERO INOXIDABLE 13 14 SELLO DE PLASTICO AL EMPOTRAR LA BASE ENCHUFE, ESTA DEBE SALIR COMO MINIMO 5 mm DEL MURO PARA COLOCAR EL MEDIDOR Y EL ARO NOTAS : LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBEESTAR COMO MAXIMO A 50 METROS DEL POSTE DESDE EL CUAL SE DARA EL SERVICIOEL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A LA CARGA SIN MEDIO PASAR POR ALGUN MEDIO DE PROTECCION ( FUSIBLE O TERMOMAGNETICO ) LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL LIMITE DE PROPIEDAD, EMPOTRADA O SOBREPUESTA EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO OCONSTRUCCIONLA ALTURA DE LA MUFA PARA RECIBIR LA ACOMETIDA ES DE 4800mm EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm DEL MEDIDOR MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE A BASE ENCHUFE B ARO C D MURO E F G DETALLE DE EMPOTRADO DE LA BASE PROPIEDADDEL USUARIO VIAPUBLICA MEDIDOR VISTA DE PLANTA SIN ESCALA

  20. ACOTACIONES EN mm SIN ESCALA ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, AREA RURAL, RED AEREA, CONSTRUCCION AL LIMITE DE LA PROPIEDAD CFE EM-BT110 HOJA 1 DE 2 VISTA DE CONJUNTO A LA INSTALACIONDE LA CASA ACOMETIDA DE CFE A LA INSTALACIONDE LA CASA 10 #35 5 BARDA DEL USUARIO 8 3 4400 1 MEDIDORMONOFASICODE C.F.E. 6 C F E 30AMP 2 7 1800 LADO DE LA CALLE LADO DE LA PROPIEDAD 600 RELLENO DE PIEDRAOGRAVA CON CEMENTO ESTA ESPECIFICACION SE APLICA EN COMUNIDADES RURALES DE BAJOS RECURSOS ECONOMICOS Y CON POBLACION MAXIMA DE 1000 HABITANTES VISTA FRONTAL VISTA LATERAL

  21. ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, AREA RURAL, RED AEREA, CONSTRUCCION AL LIMITE DE LA PROPIEDAD CFE EM-BT110 HOJA 2 DE 2 ESPECIFICACIONES DE MATERIALES Y EQUIPO A CARGO DEL USUARIO BARROTE POLIN DE MADERA DE 150X 150 X 5000 mm TRATADO CON ACEITE QUEMADO O POSTE DE CONCRETO O MURETE DE CONCRETO O POSTE TUBULAR INTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 2 POLOS, 1 TIRO, 250 VOLTS, 30 AMPERES, A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIEBASE ENCHUFE DE 4 TERMINALES, 100 AMPERES PIJAS DE 38 mm (1 1/2”) PARA FIJAR LA BASE GRAPA AISLADA PARA FIJAR CONDUCTORES DEL INTERRUPTOR A LA INSTALACION DE LA CASA 1 2 A LA INSTALACIONDE LA CASA 3 1 4 5 5 10 INSTALADO POR C.F.E. 5 10 6789 MEDIDOR TIPO ENCHUFE DE 15 AMPERES, 1 FASE, 2 HILOS, 120 VOLTS (F121)SELLO DE PLASTICO TAPON ROSCADO DE PLASTICO ARO PARA BASE ENCHUFE DE ACERO INOXIDABLE GRAPA AISLADA PARA FIJAR CONDUCTORES DE ACOMETIDA HASTA LA BASE ENCHUFE 8 4 FASE NEUTRO 10 9 3 NOTAS : 5 10 A LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR COMO MAXIMO A 50 METROS EN LA LINEA RECTA DEL POSTE DESDE EL CUAL SE DARA EL SERVICIOLA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL LIMITE DE PROPIEDAD EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO O CONSTRUCCIONLA ALTURA DEL BARROTE POLIN DE MADERA PARA RECIBIR LA ACOMETIDA SERA DE 5000 mmEL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm DEL MEDIDORMARCAR NUMERO OFICIAL DE FORMA PERMANENTE B 30AMPERES C D 2 E F ESTA ESPECIFICACION SE APLICA EN COMUNIDADES RURALES DE BAJOS RECURSOS ECONOMICOS Y CON POBLACION MAXIMA DE 1000 HABITANTES DETALLE DE ALAMBRADO DE LA BASE SIN ESCALA

  22. ACOTACIONES EN mm SIN ESCALA ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, AREA RURAL, RED AEREA CONSTRUCCION AL FONDO DE LA PROPIEDAD CFE EM-BT111 HOJA 1 DE 2 VISTA DE CONJUNTO A LA INSTALACIONDE LA CASA ACOMETIDA DE CFE A LA INSTALACIONDE LA CASA 10 #35 5 BARDA DEL USUARIO 8 3 4400 1 6 MEDIDORMONOFASICODE C.F.E. C F E 30AMP 2 7 1800 LADO DE LA CALLE LADO DE LA PROPIEDAD 600 RELLENO DE PIEDRAOGRAVA CON CEMENTO ESTA ESPECIFICACION SE APLICA EN COMUNIDADES RURALES DE BAJOS RECURSOS ECONOMICOS Y CON POBLACION MAXIMA DE 1000 HABITANTES VISTA LATERAL VISTA FRONTAL

  23. ESPECIFICACION PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, AREA RURAL, RED AEREA CONSTRUCCION AL FONDO DE LA PROPIEDAD CFE EM-BT111 HOJA 2 DE 2 ESPECIFICACIONES DE MATERIALES Y EQUIPO A CARGO DEL USUARIO BARROTE POLIN DE MADERA DE 150X 150 X 5000 mm TRATADO CON ACEITE QUEMADO O POSTE DE CONCRETO O MURETE DE CONCRETO O POSTE TUBULAR INTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 2 POLOS, 1 TIRO, 250 VOLTS, 30 AMPERES, A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIEBASE ENCHUFE DE 4 TERMINALES, 100 AMPERES PIJAS DE 38 mm (1 1/2”) PARA FIJAR LA BASE GRAPA AISLADA PARA FIJAR CONDUCTORES DEL INTERRUPTOR A LA INSTALACION DE LA CASA 1 2 A LA INSTALACIONDE LA CASA 3 1 4 5 5 10 INSTALADO POR C.F.E. 5 10 6789 MEDIDOR TIPO ENCHUFE DE 15 AMPERES, 1 FASE, 2 HILOS, 120 VOLTS (F121)SELLO DE PLASTICO TAPON ROSCADO DE PLASTICO ARO PARA BASE ENCHUFE DE ACERO INOXIDABLE GRAPA AISLADA PARA FIJAR CONDUCTORES DE ACOMETIDA HASTA LA BASE ENCHUFE 8 4 FASE NEUTRO 10 9 3 NOTAS : 5 10 A LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR COMO MAXIMO A 50 METROS EN LA LINEA RECTA DEL POSTE DESDE EL CUAL SE DARA EL SERVICIOLA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL LIMITE DE PROPIEDAD EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO O CONSTRUCCIONLA ALTURA DEL BARROTE POLIN DE MADERA PARA RECIBIR LA ACOMETIDA SERA DE 5000 mmEL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm DEL MEDIDORMARCAR NUMERO OFICIAL DE FORMA PERMANENTE B 30AMPERES C D 2 E F ESTA ESPECIFICACION SE APLICA EN COMUNIDADES RURALES DE BAJOS RECURSOS ECONOMICOS Y CON POBLACION MAXIMA DE 1000 HABITANTES DETALLE DE ALAMBRADO DE LA BASE SIN ESCALA