FIRE SAFETY DESIGN OF STEEL STRUCTURES THERMAL & MECHANICAL ACTIONS

International conference Sept. 25-26, 2008, B ă ile Felix. FIRE SAFETY DESIGN OF STEEL STRUCTURES THERMAL & MECHANICAL ACTIONS. Prof. K ároly Jármai University of Miskolc, Hungary. Resistance to Fire - Chain of Events. Loads. . Steel columns. time. R. time. 1: Ignition.

pennie
Download Presentation

FIRE SAFETY DESIGN OF STEEL STRUCTURES THERMAL & MECHANICAL ACTIONS

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. International conference Sept. 25-26, 2008, Băile Felix FIRE SAFETY DESIGN OF STEEL STRUCTURES THERMAL & MECHANICAL ACTIONS Prof. Károly Jármai University of Miskolc, Hungary Part 1: Thermal & Mechanical Actions

  2. Resistance to Fire - Chain of Events Loads  Steel columns time R time 1: Ignition 2: Thermal action 3: Mechanical actions 4: Thermal response 5: Mechanical response 6: Possible collapse Part 1: Thermal & Mechanical Actions

  3. Thermal action on structure Composite Slab 1 side exposed Column 4 sides exposed Part 1: Thermal & Mechanical Actions

  4. Heat transfer at surface of building elements Net Radiative Heat Flux Net Convective Heat Flux Total net Heat Flux + = & & & h h h net net,c net , r • Exposed side • Non-exposed side Part 1: Thermal & Mechanical Actions

  5. Structural Fire Safety Engineering vs. Classification Prescriptive Performance based Part 1: Thermal & Mechanical Actions

  6. Actions on Structures Exposed to FireEN 1991-1-2 - Prescriptive Rules Design Procedures Prescriptive Rules Performance-Based Code (Thermal Actions given by Nominal Fire) (Physically based Thermal Actions) Part 1: Thermal & Mechanical Actions

  7. Nominal Temperature-Time Curve *) Nominal temperature-time curve Standard temperature-, External fire - & Hydrocarbon fire curve No data needed *) Simplified Fire Models Localised Fire Fully Engulfed Compartment - HESKESTADT Rate of heat release Fire surface Boundary properties Opening area Ceiling height - Parametric Fire - HASEMI q (t) uniform in the compartment q (x, y, z, t) + Exact geometry *) Advanced Fire Models - One-Zone Model - Two-Zone Model - Combined Two-Zones and One-Zone fire - CFD Part 1: Thermal & Mechanical Actions

  8. Prescriptive Fire Regulations Defining ISO Curve Requirements ISO ISO Time [min] ISO ISO ISO ISO ISO ISO ISO-834 Curve (EN1364 -1) T = 20 + 345 log (8 t + 1) q [°C] 1200 1110 1049 1006 The ISO curve * Has to be considered in the WHOLE compartment, even if the compartment is huge 1000 945 842 800 600 400 * Never goes DOWN * does not consider the PRE-FLASHOVER PHASE * Does not depend on FIRE LOAD and VENTILATION CONDITIONS 200 0 90 120 0 30 60 180 Part 1: Thermal & Mechanical Actions

  9. Stages of a Natural Fire and the Standard Fire Curve Post- Flashover 1000-1200°C Pre- Flashover Flashover Temperature Natural fire curve ISO834 standard fire curve Time Heating Ignition - Smouldering Cooling …. Part 1: Thermal & Mechanical Actions

  10. Sprayed Protection Part 1: Thermal & Mechanical Actions

  11. Partially Encased Beams & Columns Part 1: Thermal & Mechanical Actions

  12. Actions on Structures Exposed to FireEN 1991-1-2 - Performance Based Code Design Procedures Prescriptive Rules Performance-Based Code (Physically based Thermal Actions) (Thermal Actions given by Nominal Fire) Part 1: Thermal & Mechanical Actions

  13. Natural Fire Safety Concept ISO curve q [°C] 1200 1000 800 600 400 200 0 30 60 90 120 180 0 Time [min] • Implemented in: • EN 1991-1-2 • Some National Fire Regulations • include now alternative requirements • based on Natural Fire Part 1: Thermal & Mechanical Actions

  14. NFSC Valorisation Project Part 1: Thermal & Mechanical Actions

  15. Natural Fire Model *) Nominal temperature-time curve Standard temperature-, External fire - & Hydrocarbon fire curve No data needed *) Simplified Fire Models Localised Fire Fully Engulfed Compartment - HESKESTADT Rate of heat release Fire surface Boundary properties Opening area Ceiling height - Parametric Fire - HASEMI q (t) uniform in the compartment q (x, y, z, t) + Exact geometry *) Advanced Fire Models - One-Zone Model - Two-Zone Model - Combined Two-Zones and One-Zone fire - CFD Part 1: Thermal & Mechanical Actions

  16. List of needed Physical Parameters for Natural Fire Model • Boundary properties • Ceiling height • Opening Area • Fire surface • Rate of heat release Geometry Fire Part 1: Thermal & Mechanical Actions

  17. Characteristics of the Fire Compartment Fire resistant enclosures defining the fire compartment according to the national regulations Material properties of enclosures: c, r, l Definition of Openings Part 1: Thermal & Mechanical Actions

  18. Characteristic of the Fire for Different Buildings RHR Fire Load q Fire Growth f f,k Occupancy Rate 80% fractile [kW/m²] [MJ/m²] Dwelling Medium 250 948 (room) Hospital Medium 250 280 (room) Hotel Medium 250 377 Library Fast 500 1824 Office Medium 250 511 School Medium 250 347 Shopping Centre Fast 250 730 (movie/cinema) Theatre Fast 500 365 (public space) Transport Slow 250 122 Part 1: Thermal & Mechanical Actions

  19. Fire Load Density 25 1,10 1,50 Examples Danger of Danger of Compartment Fire Activation Fire Activation of floor area Af [m²] q2 q1 Occupancies Art gallery, museum, 0,78 swimming pool 1,00 250 Residence, hotel, office Manufactory for machinery 1,22 2500 1,90 & engines Chemical laboratory, 1,44 5000 2,00 Painting workshop Manufactory of fireworks 2,13 1,66 10000 or paints ni Function of Active Fire Safety Measures Automatic Fire Suppression Automatic Fire Detection Manual Fire Suppression Automatic fire Automatic Automatic Independent Work Safe Fire Smoke Off Site Alarm Detection Water Water Fire Fire Access Fighting Exhaust Transmission & Alarm Supplies Extinguishing Brigade Brigade Routes Devices System to by by System Fire Brigade 0 1 2 Heat Smoke           n1 n5 n6 n7 n8 n9 n10 n2 n3 n4 0,9 or 1 1,0 1,0 0,61 or 0,78 0,61 0,87 or 0,73 0,87 1,0 0,87 0,7 1,5 1,5 1,5 Part 1: Thermal & Mechanical Actions

  20. Growing phase Rate of Heat Release CurveStationary State and Decay Phase 10 Ultra- Fast (FGR) Fast (FGR) 9 8 Medium (FGR) 7 10 Steady state 6 RHR [MW] 9 Fire Growth Rate = FGR A x RHR f f 5 8 COMPARTMENT FIRE 4 Slow (FGR) 7 3 6 2 300'' 75'' 150'' 600'' 5 RHR [MW] 1 t [min] 4 A x RHR f f 0 0 5 10 15 20 3 Ventilation Controlled Fire 2 Decay phase 1 Decay Phase t [min] 0 70% (qf,d • Afi) 0 5 10 15 20 25 30 tdecay RHR [MW] 0 Time [min] Part 1: Thermal & Mechanical Actions

  21. Natural Simplified Fire Model *) Nominal temperature-time curve Standard temperature-, External fire - & Hydrocarbon fire curve No data needed *) Simplified Fire Models Localised Fire Fully Engulfed Compartment - HESKESTADT Rate of heat release Fire surface Boundary properties Opening area Ceiling height - Parametric Fire - HASEMI q (t) uniform in the compartment q (x, y, z, t) + Exact geometry *) Advanced Fire Models - One-Zone Model - Two-Zone Model - Combined Two-Zones and One-Zone fire - CFD Part 1: Thermal & Mechanical Actions

  22. Simplified Fire ModelsLocalised Fire FULLY ENGULFED COMPARTMENT LOCALISED FIRE q (t) uniform in the compartment q (x, y, z, t) Part 1: Thermal & Mechanical Actions

  23. Real Localised Fire Test Part 1: Thermal & Mechanical Actions

  24. Localised Fire: HESKESTAD Method • Annex C of EN 1991-1-2: • Flame is not impacting the ceiling of a compartment (Lf < H) • Fires in open air Q(z) = 20 + 0,25 (0,8 Qc)2/3 (z-z0)-5/3 900°C Flame axis The flame length Lf of a localised fire is given by : Lf = -1,02 D + 0,0148 Q2/5 H L f z D Part 1: Thermal & Mechanical Actions

  25. Localised Fire: HASEMI Method • Annex C of EN 1991-1-2: • Flame is impacting the ceiling (Lf> H) concrete slab beam q g Y = Height of the free zone q = Air Temperature Calculated by CaPaFi at Beam Level x Part 1: Thermal & Mechanical Actions

  26. Simplified Fire ModelsFully Engulfed Compartment FULLY ENGULFED COMPARTMENT LOCALISED FIRE q (t) uniform in the compartment q (x, y, z, t) Part 1: Thermal & Mechanical Actions

  27. Real Fire Test Simulating an Office Building Fully engulfed fire Part 1: Thermal & Mechanical Actions

  28. Fully Engulfed Compartment Parametric Fire Temperature [°C] Annex A of EN 1991-1-2 For a given b, qfd, At & Af Part 1: Thermal & Mechanical Actions

  29. Natural Advanced Fire Model *) Nominal temperature-time curve Standard temperature-, External fire - & Hydrocarbon fire curve No data needed *) Simplified Fire Models Localised Fire Fully Engulfed Compartment - HESKESTADT Rate of heat release Fire surface Boundary properties Opening area Ceiling height - Parametric Fire - HASEMI q (t) uniform in the compartment q (x, y, z, t) + Exact geometry *) Advanced Fire Models - One-Zone Model - Two-Zone Model - Combined Two-Zones and One-Zone fire - CFD Part 1: Thermal & Mechanical Actions

  30. Advanced fire Models LOCALISED FIRE The Fire switch to a fully engulfed fire The Fire stays localised LOCALISED FIRE FULLY ENGULFED COMPARTMENT Part 1: Thermal & Mechanical Actions

  31. Large Compartment Test Fire Load Part 1: Thermal & Mechanical Actions

  32. Large Compartment Test External Flaming During the Test Part 1: Thermal & Mechanical Actions

  33. Large Compartment Test After the Test Part 1: Thermal & Mechanical Actions

  34. Two Zone Calculation Software “OZone V2.2” Part 1: Thermal & Mechanical Actions

  35. OZone results: Input and Computed RHR Part 1: Thermal & Mechanical Actions

  36. OZone results: Gas Temperatures θHot θCold Part 1: Thermal & Mechanical Actions

  37. OZone results: Smoke Layer Thickness Part 1: Thermal & Mechanical Actions

  38. Calibration of Software OZone: Gas Temp 1400 1200 1000 800 600 400 200 0 0 200 400 600 800 1000 1200 MAXIMUM AIR T EMPERATURE OZone OZone [°C] MAXIMUM AIR T EMPERATURE IN THE COMPARTMENT 1400 TEST [°C] Part 1: Thermal & Mechanical Actions

  39. Calibration of Software OZone: Steel Temp 1400 UNPROTECTED STEEL TEMPERATURE 1200 1000 800 OZone [°C] 600 400 200 0 0 200 400 600 800 1000 1200 1400 TEST [°C] Part 1: Thermal & Mechanical Actions

  40. OZone: Case Study Influence of the Actives Fire Safety Measures 1000 Office : A = 291,2 m² f O.F. = 0,04 m½ ; Fire Load q = 511 MJ/m² 900 f,k No Fire Active Measures 800 Off Site Fire Brigade 700 Automatic Fire Detection & Alarm by Smoke 600 Automatic Alarm Transmission to Fire Brigade 500 Automatic Water Extinguishing System Gas temperature [°C] 400 Design Fire Load q [ MJ/m² ] 625 356 310 189 f,d 300 200 Õ d d d m q = q 100 f , d ni f , k q1 q2 i 0 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 Time [min] Part 1: Thermal & Mechanical Actions

  41. Computer Fluid Dynamics: Software Sofie Grid definition Part 1: Thermal & Mechanical Actions

  42. Sofie Results: Gas Temperatures Part 1: Thermal & Mechanical Actions

  43. Resistance to Fire - Chain of Events Loads  Steel columns time R time 1: Ignition 2: Thermal action 3: Mechanical actions 4: Thermal response 5: Mechanical response 6: Possible collapse Part 1: Thermal & Mechanical Actions

  44. Basis of Design and Actions on Structures S Actions for temperature analysis W Thermal Action G A FIRE C T I Actions for structural analysis Q O Mechanical Action N Dead Load G S Imposed Load Q Snow S Wind W Fire Part 1: Thermal & Mechanical Actions

  45. Combination Rules for Mechanical ActionsEN 1990: Basis of Structural Design Room temperature  +  + y  E G å Q Q = d G Q,1 1 0,i Q,i i i >1 f.i. : Offices area with the imposed load Q, the leading variable action = 1,35 G + 1,5 Q + 0,6 • 1,5 W + 0,5 • 1,5 S E d Part 1: Thermal & Mechanical Actions

  46. Combination Rules for Mechanical ActionsEN 1990: Basis of Structural Design E = G + 0,5 Q fi,d E = G + 0,2 W + 0,3 Q fi,d Fire conditions  Accidental situation = + y + y å E G Q Q i 1 fi,d 1or2,i 1or2,1 i >1 f.i. : Offices area with the imposed load Q, the leading variable action Offices area with the wind W, the leading variable action Part 1: Thermal & Mechanical Actions

  47. Values of  factors for buildings y y y Action 1 2 0 Imposed loads in buildings, category (see EN 1991-1.1) Category A : domestic, residential areas 0,7 0,5 0,3 0,3 Category B : office areas 0,7 0,5 Category C : congregation areas 0,7 0,7 0,6 0,6 Category D : shopping areas 0,7 0,7 Category E : storage areas 1,0 0,9 0,8 Category F : traffic area vehicle weight £ 30kN 0,7 0,7 0,6 Category G : traffic area, 0,3 30 kN < vehicle weight £ 160kN 0,7 0,5 0 Category H : roofs 0 0 Snow loads on buildings (see EN1991-1.3) Finland, Iceland, Norway, Sweden 0,70 0,50 0,20 Remainder of CEN Member States, for sites located at altitude 0,70 0,50 0,20 H > 1000 m a.s.l. Remainder of CEN Member States, for sites located at altitude 0,50 0,20 0 £ H 1000 m a.s.l. Wind loads on buildings (see EN1991-1.4) 0,6 0,2 0 Temperature (non-fire) in buildings (see EN1991-1.5) 0,6 0,5 0 ( Reference : EN1990 - February 2002) Part 1: Thermal & Mechanical Actions

  48. Load Factor Maximal Load level after R30 Part 1: Thermal & Mechanical Actions

  49. Part 1: Thermal & Mechanical Actions