Nexans' Superconducting Fault Current Limiters for medium voltage applications

Nexans' Superconducting Fault Current Limiters for medium voltage applications - status and prospects - Achim Hobl, Joachim Bock, Simon Krämer, Markus Bludau, Judith Schramm, Christian Jänke, Steffen Elschner Nexans SuperConductors. Contents. Function of SFCL´s

polly
Download Presentation

Nexans' Superconducting Fault Current Limiters for medium voltage applications

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Nexans' Superconducting Fault Current Limiters for medium voltage applications - status and prospects - Achim Hobl, Joachim Bock, Simon Krämer, Markus Bludau,Judith Schramm, Christian Jänke, Steffen Elschner Nexans SuperConductors

  2. Contents • Function of SFCL´s • Possible installation sites • SFCL Systems • Perspectives for future grids

  3. operating area HTS FCL normal operation limitation Operating area of HTS devices Transition fasterdue to temperature rise

  4. Resistive Limitation FCL Breaker Load + compact + intrinsically safe + strong limitation + independent of short circuit level – current leads to low temperature

  5. Inductive Limitation FCL Load + no quench of the superconductor + can be without interruption – large volume and weight – low level of limitation – relatively high impedance

  6. Function • ultrafast • reacts in 1-2 ms • automatic • no external trigger, • self-recovering • wear-free • service only for • cooling normal operation limiting operation

  7. High voltage Transformer feeder Medium voltage Busbar coupler Installation sites • Bus bar coupling • In line (secondary side of transformer) • House load protection in power plants(auxiliary power) FCL FCL

  8. Advantages of the FCL system • Passive limiting characteristics of the superconductor • Inherently safe and free from wear and maintenance • The power flow is not interrupted completely • Less mechanical and thermal stress Customer benefits • Higher network reliability • Considerable cost savings • Low impedance networks • Voltage stability and reduction of harmonics • Load levelling of busbars / transformers

  9. 12-400 (ASL 2) second system for UK (bifilar)Delivered to UK April 2011 FCL Systems 12-100 (ASL 1) first commercial systemField tested for ~8 months 12-800 (Vattenfall) first system in a power stationField tested Nov. 2009 - Dec. 2010 XX-YYY XX: Voltage [kV] YYY: Current [A]

  10. 12-100 ASL, Newcastle ENW, Bamber Bridge Live on grid10-2009 to 06-2010

  11. Test at IPH 12-400 Customer has ordered second system!

  12. 12-800

  13. 12-800 Power Plant Boxberg, Germany Supply for crushers and conveyor belts

  14. Perspectives for future grids • Low impedance networks WITH low short circuit power • Supports integration of distributed generation • Load / generation growth without substation upgrading • Improvements in availability and stability

  15. generator transformer FCL 10 kV G 5...50 MVA Integration of distributed generation 110 kV 10 kV grid

  16. powersafetyat its best thank you for your attention