Comparing New Building Pre-Construction and Post Occupancy Energy Models with Actual Performance

Comparing New Building Pre-Construction and Post Occupancy Energy Models with Actual Performance. 2014 CA Higher Education Sustainability Conference – Session 47 June 18, 2014 Gerry Hamilton. How Energy Models are Staged. Utilize Building Energy Models Economic Model Final Design Model

quilla
Download Presentation

Comparing New Building Pre-Construction and Post Occupancy Energy Models with Actual Performance

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Comparing New Building Pre-Construction and Post Occupancy Energy Models with Actual Performance 2014 CA Higher Education Sustainability Conference – Session 47 June 18, 2014 Gerry Hamilton

  2. How Energy Models are Staged • Utilize Building Energy Models • Economic Model • Final Design Model • Evaluation Model Applied at different stages of the project. Turnover & Operation Permitting Programming DDs SDs CDs

  3. Recently Completed “High Performance” Buildings Lokey Stem Cell Research Building • Large Wet Lab Knight Management Center • Multi building office / classroom facility William H. Neukom Building • Simple office building

  4. Lokey Stem Cell Research Building • Medical School lab/research building • Opened in Fall 2010 • 258,000 square feet • 380 VAV fumehoods • Zone level heating and cooling • Heat recovery on main air handler units

  5. Lokey Stem Cell Research Building – Data

  6. LokeyStem Cell Research Building - Analysis • Zone level heating + cooling is very effective • Heat recovery system is more effective than modeled for this 100% outside air AHU system. • The plug load for lab space used in the original load calculation is over estimated by a factor of three.

  7. Lokey – Benchmark Comparisons

  8. Knight Management Center • Stanford Graduate School of Business • Completed in 2011 • 387,510 square feet (eight buildings) • Includes: offices, classrooms, conference rooms, library, auditoria, and dining pavilion • LEEDTM Platinum • Extensive submetering

  9. Knight Management Center – Data

  10. Knight Management Center – Analysis • Design operating hours were greatly exceeded • Could see high nighttime plug and lighting loads thanks to submetering • Utilized temporary occupancy sensors to verify • (Need an industry metric to account for space utilization) • Heating load under-estimated in model • Found a few RCx type measures through post occupancy energy modeling effort • Review of global heating setpoints • Schedule of several AHUs

  11. Knight Center – Benchmark Comparisons EIA - US Energy Information Admin

  12. William H. Neukom Building • Law School office building • Completed in 2011 • 65,000 square feet • VAV Reheat • Operable windows

  13. Neukom Building – Data

  14. Neukom Building – Data Analysis • Model underestimates heating loads • Model missed some electric loads • Some outdoor lighting • More emergency lighting than expected (runs 24/7) • Power converter and battery backup for emergency lighting parasitic load

  15. Neukom Building – Benchmark Comparisons EIA - US Energy Information Admin