140 likes | 445 Views
Ductless Heat Pumps Sizing Example. Gary Nordeen Bill Kingrey, P.E. 11/5/08 AFE Webinar. www.nwBuildings.org/dhp.aspx info@nwBuildings.org. Introduction. This presentation is intended to show how a ductless heat pump is sized for a particular space.
E N D
Ductless Heat PumpsSizing Example Gary NordeenBill Kingrey, P.E.11/5/08 AFE Webinar www.nwBuildings.org/dhp.aspx info@nwBuildings.org
Introduction This presentation is intended to show how a ductless heat pump is sized for a particular space. The example is a maternity room inside a health facility, that needs supplemental cooling.
Heat Loss Calculations Calculate the heat loss through walls, glass, ceiling/roof, floor and any other building components in the zone to be served, using ASHRAE procedures (chapter 26, Fundamentals)
Heat Gain Calculations • Survey each zone and estimate heat gains from lights, equipment (computers, copiers, etc), people, building envelope and ventilation • Calculate both sensible and latent (water vapor) loads • Use ASHRAE Handbook of Fundamentals Chapter 26
Heat Gain Calculation Example Assume we are going to provide cooling to a maternity room that is currently heated and ventilated by a central system with heating and ventilation air. We surveyed the room and found the following existing conditions.
Maternity Room Example • 2 fluorescent lights at 32 watts each - ballast heat included • 2 People @ 275 BTUH sensible, 105 BTUH latent (water vapor) • Equipment = 1 computer = 65W • Vent. Air = 40 CFM outdoor air at ambient temp in summer, 70 in winter • Envelope (windows, walls and roof) calculated gain = 4,800 BTU
Maternity Room Example Sensible Cooling Loads • Lights + Equipment + People = 2x32 + 65 + 2 x 275 = 679 watts 679w X 3.412 BTU / watt = 2317 BTUH Sensible • 40 CFM Ventilation Air at 92dB, 74wB = 40CFM x 1.08 BTUH / CFM x ºF x (92ºF – 75ºF) =734 BTUH • Total Sensible Cooling Load = 4,800 BTUH (envelope) + 2,317BTUH + 734 BTUH = 7,850 BTUH Sensible
Maternity Room ExampleCalculate Latent Loads To calculate latent loads, use a Psychometric Chart or software that will determine enthalpy and density of water/air mixtures
Psychometric Calculations • Or you can use this free online program that will calculate enthalphy, density, relative humidity, etc. http://www.gorhamschaffler.com/psy.htm
Latent Cooling Loads Assumptions: • Ventilation air is cooled and dehumidified to 75°FDb (dry bulb) at 30%RH (relative humidity) • Cooling design conditions at the site were 86Db and 68 Wb (wet bulb)
Latent Cooling Loads • People = 2 x 105 BTUH = 210 BTUH latent • Ventilation Air = 40ft³/min at 86Db/68Wb • 13.55 ft³ of air at that temp = 1 lb of air • In one hour we will cool 40ft³/min x 60 min/hr/13.55 ft³/lb = 177lbs/hr of air • Air at 86dB/68wB contains 32.21 BTU/lb (of air) • Air at 75dB/30% RH = 24.05 BTU/lb • It will require 32.21- 24.05 = 8.16 BTU for each pound of air cooled • Total Ventilation Load = 177 lbs/hr x 8.16 BTU/lb = 1,440 BTU/hr • Latent Load = People + Ventilation Air = 210 + 1440 =1,650 BTU/hr (about 1.5 pints of water per hour)
Selecting Ductless Heat Pump • Pick a unit that has a capacity greater than or equal to the total cooling load • Mini-splits express heating and cooling capacity in kW. To convert to BTUH multiply the kW rating by 3412
More Information Northwest Building Efficiency Center 866-929-6232 Info@nwBuildings.org www.nwBuildings.org