PSRC Line Protection Subcommittee Working Group D4 Application of Overreaching Distance Relays

PSRC Line Protection Subcommittee Working Group D4 Application of Overreaching Distance Relays Presented to the: 64 th Annual Georgia Tech Protective Relaying Conference by Russell W. Patterson P atterson P ower E ngineers, LLC Atlanta, GA May 5-7, 2010.

sabin
Download Presentation

PSRC Line Protection Subcommittee Working Group D4 Application of Overreaching Distance Relays

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. PSRC Line Protection Subcommittee Working Group D4 Application of Overreaching Distance Relays Presented to the: 64th Annual Georgia Tech Protective Relaying Conference by Russell W. Patterson Patterson Power Engineers, LLC Atlanta, GA May 5-7, 2010

  2. Power System Relaying Committee • Scope: • Standards, technical papers and guide the industry relative to the protection system, including communication between, among and within relays and relay systems. • Maintenance of liaison and collaboration as required with other committees of the Power & Energy Society and associated Groups and Societies of the IEEE. • Web Site: http://www.pes-psrc.org/ • Upcoming Meetings: • May 10-14, 2010 Madison, WI • September 13-16, 2010 Berkeley, CA • January 10-14, 2011 Atlanta, GA 2 of 30

  3. Power System Relaying Committee New or Revised Standards: • Guide for Power System Protection Testing (C37.233) • Guide for the Protective Relay Applications to Power Systems Buses (C37.234) • Synchronous Generator Tutorial Revision (95-TP-201) Reports Published: • Understanding Microprocessor-Based Technology Applied to Relaying • Adjustable Speed Drive Motor Protection Applications and Issues • Ancillary Protective and Control Functions Common to Multiple Protective Relays   3 of 30

  4. PSRC Subcommittees B – Advisory Committee C – Systems Protection Subcommittee D – Line Protection Subcommittee H – Relay Communications Subcommittee I – Relaying Practices Subcommittee J – Rotating Machinery Subcommittee K – Substation Protection Subcommittee 4 of 30

  5. D4 Members Chair: Russell Patterson Vice-chair: Walter McCannon R. Beazer G. Benmouyal G. Brunello J. Burger S. Chano A. Darlington P. Elkin Walt Elmore D. Fontana R. Haas B. Kasztenny B. Kennedy C. Kim, Suwon Kyunggi-do G. Kobet R. Lavorin F. Lopez M. McDonald P. Mysore M. Nagpal C. Rogers S. Sambasivan M. Schroeder G. Sessler D. Tziouvaras E. Udren Q. Versosa T. Wiedman 5 of 30

  6. Outline • 1. Introduction • Why we are writing this document. • 2. Background • . Zone Descriptions • . Purpose of overreaching distance zones; step-distance and pilot • . Susceptibility of overreaching distance zones to undesirable operation • 3. Application Practice • . Application of high-speed distance functions (forward and reverse) in pilot schemes • . Permissive and blocking schemes • . Phase versus ground distance • . Stepped-distance and remote backup applications • . Remote backup by zone two or zone three • . Special considerations: • . Three-terminal applications • . Loadability limitations • . Power swing considerations (brief discussion of the existing practice, or the lack thereof) 6 of 30

  7. 4. Overreaching Distance Functions and Line Loadability: • . Definition of loadability and sample calculations • . Zone Characteristics Impacting Loadability: • . Variations in Zone Positioning • a. Mho characteristic angle adjustment - maintaining a given mho circle • b. Offsetting of mho characteristics • 2. Variations in Zone Shape • a. Lens characteristic • b. Rectangular (Quadrilateral) characteristic • 3. Supervision of Zone tripping • a. Use of blinders • b. Use of load encroachment characteristics • . Means to prevent tripping on load: • . Shaping the characteristics & load encroachment blocking • . Using ground directional overcurrent (67N) instead of Z2 in pilot schemes • . Maximum sensitivity angle (characteristic or torque angle) Considerations 7 of 30

  8. 5. Overreaching Distance Functions and Power Swings: • . Power Swings and Their Impact on The Power System • . Impedances Seen by Distance Relays During Power Swings • . Effect of Power Swings on Distance Relays • . Means to Prevent Tripping on Power Swings. • . Power-Swing Blocking and Tripping Functions • . Power-Swing Blocking and Tripping Functions • . Power-Swing Blocking and Tripping Principles • . Additional Considerations • . Distance Protection Requirements During OOS Conditions • . Power Swing Protection During Single Pole Open Conditions • . Three-Phase Faults Following Power Swings 8 of 30

  9. 6. Alternatives to Remote Backup Application of Overreaching Zones: • A. Local Breaker failure Protection Systems • B. Redundant Line Protection Systems • C. Communication Applications • D. Direct Transfer Tripping and other Teleprotection Applications • 7. References • 8. Bibliography • Appendix A. Zone 3 and Load Power • Appendix B. NERC Interim Requirements for Line Loadability • Appendix C. Effect of Fault Resistance in Loop System • Appendix D. Transmission Circuits Protection Schemes and Limitations 9 of 30

  10. “Why we are writing this document.” • Overreaching distance relays tripping under load have played a part • in many major blackouts. • August 14th, 2003 • November 9th, 1965 • November 4th, 2006 • In an effort to help protection engineers avoid repeating history this document is being written to describe some of the susceptibilities of distance relaying and methods to circumvent them while adequately providing the intended protection function these relays are in place to provide. 10 of 30

  11. 11 of 30

  12. 12 of 30

  13. 13 of 30

  14. 14 of 30

  15. 15 of 30

  16. http://pes-psrc.org 16 of 30

  17. 17 of 30

  18. 18 of 30

  19. 19 of 30

  20. 20 of 30

  21. 21 of 30

  22. 22 of 30

  23. 23 of 30

  24. 24 of 30

  25. 25 of 30

  26. 26 of 30

  27. 27 of 30

  28. 28 of 30

  29. 29 of 30