An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. ERT 210/4Process Control CHAPTER 9 Control System Instrumentation • Hairul Nazirah bt Abdul Halim • Email: hairulnazirah@unimap.edu.my • Office: 04-9798840

  2. Control System Instrumentation Transducers and Transmitters • transducer - typically consists of a sensing element combined with a driving element (transmitter). Figure 9.3 A typical process transducer.

  3. Transducers for process measurements convert the magnitude of a process variable (e.g., flow rate, pressure, temperature, level, or concentration) into a signal that can be sent directly to the controller. • The sensing element is required to convert the measured quantity, that is, the process variable, into some quantity more appropriate for mechanical or electrical processing within the transducer.

  4. Standard Instrumentation Signal Levels • Before 1960, instrumentation in the process industries utilized pneumatic (air pressure) signals to transmit measurement and control information almost exclusively. • These devices make use of mechanical force-balance elements to generate signals in the range of 3 to 15 psig, an industry standard. • Since about 1960, electronic instrumentation has come into widespread use. • Signal range: 1-5 mA, 4-20 mA, 10-50mA, 0-50V. • Most industrial analog instrumentation use 4-20 mA

  5. Sensors • Main categories of measurements used in process control: • Temperature • Pressure • Flow rate • Liquid level • Composition

  6. Temperature Sensor • On-line measurement by: • Thermocouples & resistance temperature detector (RTD) – up to 10000C • Pyrometer and filled – above 9000C • System thermometer.

  7. Differential Pressure On-line measurement by: - Liquid column - Elastic element: Bourdon tube - Optical fiber sensor: measure pressure in high- temperature environments (>11000C)

  8. Liquid or gas flow rate • Flow rate can be measured indirectly using pressure drop across orifice or venturi • Other measurements: • Rotameter • Turbine flowmeter • Ultrasonic • Magnetic

  9. Liquid level • Level can be measured using: • Float-activated • Head devices • Electrical (Conductivity) • Radiation • Radar

  10. Chemical Composition • On-line measurement by: • Gas-liquid chromatography (GLC) • Gas chromatography (GC) • Infrared (IR) spectroscopy • UV spectroscopy (UV spectrophotometer) • Magnetic resonance analysis (MRA) • Refractive index (RI) • Electrophoresis

  11. Transmitters • Converts the sensor output to a signal level appropriate for input to a controller, such as 4 to 20 mA. • Transmitters are generally designed to be direct acting. • Commercial transmitters have an adjustable input range (or span). • For example, a temperature transmitter might be adjusted so that the input range of a platinum resistance element (the sensor) is 50 to 150 °C.

  12. In this case, the following correspondence is obtained: • Lower limit or zero of 50 °C • Range or span of 100 °C • The relation between transducer output and input is

  13. For any linear instrument, the gain (Km): The gain of the measurement element Km is 0.16 mA/°C.

  14. Figure 9.4 A linear instrument calibration showing its zero and span.

  15. Final Control Elements • Final control element (actuator) is the device that enables a process variable to be manipulated. • There are many different ways to manipulate the flows of material and energy into and out of a process. • Final control elements (usually control valves) adjust the flow rates of materials, and indirectly, the rates of energy transfer to and from the process. • Variable speed air compressor – adjust air flow rates • Variable speed pump - adjust the flow rates of material

  16. Control Valves • Automatic control valve - Simple and widely used method to adjust flow rate of fluid. • The control valve components include the valve body, trim, seat, and actuator. • Control valves are either linear or rotary in design.

  17. Globe valve • Linear valve • Open and close by moving a plug vertically away from the orifice and seat

  18. Rotary valve • Closed by a 900 turn of the closing element • Used for both on-off and flow modulating control valve • Ball valve : • Plug valve:

  19. Figure 9.7 A pneumatic control valve (air-to-open).

  20. Air-to-Open vs. Air-to-Close Control Valves • Air-to-open: output signal , pressure on the diaphragm compresses the spring Pulling the stem out open the valve further • Air-to-close: output signal , pressure on the diaphragm compresses the spring Valve stem downward close the valve further

  21. Normally, the choice of A-O or A-C valve is based on safety considerations. • We choose the way the valve should operate (full flow or no flow) in case of a transmitter failure. • Hence, A-C and A-O valves often are referred to as fail-open and fail-closed, respectively.

  22. Example 9.1 Pneumatic control valves are to be specified for the applications listed below. State whether an A-O or A-C valve should be used for the following manipulated variables and give reason(s). • Steam pressure in a reactor heating coil. • Flow of effluent from a wastewater treatment holding tank into a river. • Flow of cooling water to a distillation condenser.

  23. Valve Positioners Pneumatic control valves can be equipped with a valve positioner, a type of mechanical or digital feedback controller that senses the actual stem position, compares it to the desired position, and adjusts the air pressure to the valve accordingly.

  24. Specifying and Sizing Control Valves A design equation used for sizing control valves : q = flow rate, = flow characteristic, = pressure drop across the valve, gs = specific gravity of the fluid.

  25. Specification of the valve size is dependent on the so-called valve characteristicf. • Three control valve characteristics are mainly used: • - linear • - quick opening • - equal percentage

  26. Figure 9.8 Control valve characteristics.

  27. For a fixed pressure drop across the valve, the flow characteristic is related to the lift , that is, the extent of valve opening, by one of the following relations: where R is a valve design parameter that is usually in the range of 20 to 50.

  28. Rangeability • The rangeability of a control valve is defined as the ratio of maximum to minimum input signal level. • For control valves, rangeability translates to the need to operate the valve within the range 0.05 ≤ f ≤ 0.95 or a rangeability of 0.95/0.05 = 19.