An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. GE Fanuc Automation GE Fanuc Automation 90-30 DeviceNet configuration Training Course Presented by GE Fanuc

  2. DeviceNet Master --- DNM200 P S Bus power, Module status and Network status indicators S C 1 A N 1 N E R 2 RS232, Firmware download port 2 DeviceNet bus connector 3 3 Resistors shall be on both ends of bus

  3. DNM200 Specification • Support all standard DeviceNet data rates (125K, 250K, 500K) • Up to 255 bytes input data and 255 bytes output data per slave • Up to 3972 bytes of input data and 3972 bytes of output per master • Support UCMM • Support explicit message and I/O connections: polling, strobe, Change of state, Cyclic I/O

  4. Add DNM200 Module Right click slot and Choose “Add Module” 1 2 Under “Bus Controller” Choose “IC693DNM200” 1 2

  5. Configure DNM200 Mac ID: station address, valid value 0-63 1 4 Slave status bits Array Addr: bit 1 for online status of station address 0, bit 2 for station address 1. Length is fixed to be 64 2 1 2 3 Network Status/Firmware ID: 3 words representing Server status, Can status and Firmware version, See next page for detail 3 Master to Master Data Area: configure DNM to operate as a slave 4

  6. Network Status/Firmware ID Server (slave) status: How DNM200 works as a slave Can network status Firmware ID of DNM200

  7. Configure Network Parameters Right click DNM200 module and choose “Network Settings” 1 Set up the Baud rate for fieldbus 2 Configure DNM200 as a slave 1 2

  8. Add Slave Right click DNM200 module and choose “Add slave” 1 Choose slave device from the list, for most of the cases, choose “Generic Slave Device” 2 1 2

  9. Add Slave … Slave station address (0-63) 1 1 For most slaves, choose “Polled” and specify the size of input/output data 2 Enable “Explicit Message” if the slave supports “Explicit Message”. Specify the buffer size for DNM200 to receive reply explicit message 3 2 3

  10. Assign I/O Address for Slave Modules Right click slave device Choose “Configure”

  11. Assign I/O Address for Slave Modules Define I/O reference address for this slave 1 3 1 2 Offset of input/output data of slave, which the I/O reference is assigned to 2 3 Don’t change the length which is automatically adjusted by ME