ELEC130 - Electrical Engineering 1

ELEC130 - Electrical Engineering 1. Week 8 Module 4 Applications in Power Systems. This Lecture. Module 4 - Applications in Power Systems Revise power triangle Examples using the power triangle & calculating Power Factor Correction Module 5 - Transients in a.c. Circuits

Download Presentation

ELEC130 - Electrical Engineering 1

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. ELEC130 - Electrical Engineering 1 Week 8 Module 4 Applications in Power Systems

  2. This Lecture • Module 4 - Applications in Power Systems • Revise power triangle • Examples using the power triangle & calculating Power Factor Correction • Module 5 - Transients in a.c. Circuits • (Will cover in next lecture) Lecture 8

  3. Administration • Laboratory Test Results • Quiz No. 3 • End of this lecture • can pick up quiz from Department Office next week. • Survey - Week 7 • power triangle • complete examples! • TopClass Lecture 8

  4. rms - root-mean-square (revision) • Looking for the value of current (or voltage) which has the effect of delivering the same amount of power whether the source is ac of DC • If the average power delivered by the ac Source is to = the average power delivered by the DC Source then ……………………… • We actually compute the root of the mean(average) of the square of the waveform. Root-mean-square or rms. This is our measure of “average”. • i(t) = Imcos t then Lecture 8

  5. Power in an ac circuit (revision) i(t) + v(t) Z=R- jX - • Instantaneous Power p(t) = v(t).i(t) • Let v(t) = Vmcos t = V2 cos t • then i(t) = Imcos (t+) = I2 cos (t+) • p(t) = [V2 cos t][ I2 cos (t+)] = VI [cos  + cos (2t+) ] • where: VI cos  is a constant term & VI cos (2t+) is a periodic-zero mean Lecture 8

  6. Power Terms (revision) • Average (Real) PowerP = VrmsIrms cos V-I Watts • units of W (Watts) • Case 1, Z = R : =tan-1 X/R = 0°  P = VI Watts • Case 2, Z = X : =tan-1 X/R =  90°  P = VIcos  90° = 0 Watts • Apparent power or complex power S = VI* VA’s • units of VA (volts-amps) • Reactive power is defined as Q = VIsin VAr’s • units are VAr’s (volt-amps-reactive) Lecture 8

  7. R   Z IZ -jX -jIX Power Triangle (revision) Average Power P =I2R IR  Reactive Power Q=I2XC   Complex Power S  |S| = V.I • Multiply Impedance triangle with I to get voltage triangle, then I again to get power triangle…. • S = P - jQ = VI* • Power Factor p.f. = cos  • dimensionless • lies in the range 0  pf  1 • power factor does not discriminate between capacitive (current leads voltage) or inductive (current lags voltage) loads. Hence need to specify about leading or lagging power factors. [e.g. inductive loads have lagging pf] Lecture 8

  8. Power Factor Correction (revision) • As pf decreases, situation gets worse • Distribution Authorities insist on consumers having a power factor of at least 0.8 • To correct power factor, consumers need to add a reactive load of opposite sign to the existing reactive load • Thus for a lagging (inductive) load (the most common type) we add a capacitive load • How do we calculate how much correction to add? • Why is power factor correction equipment usually added in parallel instead of in series? ZLoad ZAdded Lecture 8

  9. Example 1 240 V 50 Hz 100+j100 XA • Find XA such that the new power factor is 0.95 lagging? • Find XA such that the new power factor is 0.95 leading? Lecture 8

  10. Example 2 • A customer’s plant has two parallel loads : • a heating load of 30 kW resistive, and • a set of motors operating at 0.86 lagging power factor. The motors load is 100 kVA. • Power is supplied at 11kV. • Find • (a) total current flowing into the plant • (b) existing pf • (c) additional parallel load to bring pf to 0.95 lagging • (d) new value of current flowing into plant 100 kVA 0.86 lagging 11 kV 30 kW Lecture 8