CONTROL BOX RMO88.530. Dedicated to:. Light oil burners. PRESS SERIES ONE STAGE TWO STAGE THREE STAGE. RL SERIES ONE STAGE TWO STAGE. Dedicated to:. Heavy oil burners. PRESS SERIES TWO STAGE THREE STAGE. RN SERIES TWO STAGE. MODELS. FEATURES. RMO88.530A2RL.
E N D
Dedicated to: Light oil burners PRESS SERIES ONE STAGE TWO STAGE THREE STAGE RL SERIES ONE STAGE TWO STAGE
Dedicated to: Heavy oil burners PRESS SERIES TWO STAGE THREE STAGE RN SERIES TWO STAGE
MODELS FEATURES RMO88.530A2RL RMO88.530A1RL Mode operation………….…... Intermittent Intermittent Main voltage…………….…... AC 220-240 V +10% -15% AC 100-120 V +10% -15% Frequency…………….…... 50-60 Hz +/-6% 50-60 Hz +/-6% Under Voltage protection…... Approx. AC 170 V Approx. AC 70 V Primary fuse…………….…... Max 16 A Max 16 A Power consumption……..…... 20 VA 20 VA Internal fuse…….……..…... T6.3H250V (IEC 127-215) T6.3 Polarity...………….……..…... To be observed To be observed >450 K (pre-purge) <200 K (operation) >450 K (pre-purge) <200 K (operation) Flame signal (photoresistence)
RMO88.530A2RL RMO88.530A1RL Timings of cycle NOTES Waiting time………….…... 2 sec………………………….. Beginning when both # 4 & # 8 are energised. If not input to # 4 within 600 sec since # 8 is energised lock out Pre-purge time (min)….…... 23 sec…………………………. Interval between # 11 # 10 outputs Pre-ignition time………….…... 22 sec………………………... Interval between # 12 # 10 outputs Post-ignition time……….…... 5 sec Ignition safety time……..…... 5 sec Interval 1st 2nd stage..…... 7 sec…………………………. Interval between # 10 # 13 outputs Interval 2st 3rd stage..…... 7 sec…………………………... Interval between # 13 # 14 outputs
SELF-DIAGNOSTIC Operating concept · Burner control has initiated lockout Þ Red fault LED on · Reset Press lockout reset button for about 1 s · Diagnosis of cause of fault – Press lockout reset button for > 3 s – Press again lockout reset button for > 3 s – Read blink code of red fault LED Þ «Error code table A»
Error code table A Blink code Possible cause 2 x ··· No establishment of flame at the end of ignition safety time – Faulty or soiled flame detector – Faulty or soiled fuel valves – Poor adjustment of burner – Faulty ingnion equipment 4 x ····· Extraneous light during pre-purging – Or internal device fault 7 x ········ Loss of flame during operation – Poor adjustment of burner – Faulty or soiled fuel valves – Faulty or soiled flame detector 8 x ········ · Time-out release contact for oil pre-heater does not close 10 x ·········· · Wiring error or internal fault, output contact, unidentifiable fault, e.g. faults that occurred simultaneously