An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Transients in 3ph CCTs • Two methods: 1-extension of 1ph approach 2-Sym Components The 1st emphasized, physical picture • Type of Neutral Connection: 1-solidly Gr 2-Isolated 3-Neutral Impedance

  2. Isolated Neutral Vs Solidly Gr • TRV in 3ph, Is. N. Sys, ~ TRV 1ph • In this 3ph CCT : TRV-peak=2√(2/3) V each ph. as clear • In 3ph CCT,Iso. N.: Balanced:O close to N □In Sw. 1st A open & Load N shift to P □VAP across phase A C.B.:√3V/2 & during transient, peak= 2√2x√3 V/2=√ 6 V □50% more than: 3ph with neutral Gr

  3. 3ph Isolated N, load disconnecton • 2 other Phs interrupt shortly after A • duties less sever, since 2ph in series with 2 breaks to open under V • In unGr N, duty of 1st ph to clear 3ph fault is the most severe • In Gr N, 3 poles of C.B. identical duty

  4. Switching 3ph Reactor, Iso. N. • open 3 ph reactor load L /ph, & stray C/ph, with Π model • N Gr through 3C □ If A open 1st: VA neg. Max, VB & VC Pos. half peak; C rising, B falling • Variation of I & V, 3ph • VBC=0 this instant, IB=-IC, peak :√3/2 I

  5. Reactor, Iso. N. switching • IB & IC when, IA interrupt, have sudden slope change & zero in a 90◦ • VBC derive I & now is zero, and 90◦ later at peak □ CCT is Sym. & if fold □Then Solve it for VAA’ by injecting opp. I to it, FIG

  6. Rearrangement of CCT • After folding CCT • CCT of this FIG examined in (3.4) • TRV of 2nd & 3rd pole, same method • Equal I inj. at BB’ & CC’ for simulation • And Simplified CCT

  7. CCT, 2nd & 3rd poles interrupt • Simulation CCT & Effective one • f =1/[2Π√LC] • An example of 3ph motor interruption

  8. 3ph Capacitance Switching • Cap. with unground N & isolated from source • S.S. , N at G level • CN discharged • A interrupt 1st IA0, VA peak IBC=IB=-IC=√3/2.Vp ωC • VB=VC=-Vp/2 • IBC max0, 1/4cycle • Case 1: B&C open VBC√3 VP (its peak)

  9. Discussion Continued • this I charge CB and discharge Cc  rise of VN & current flow to CN • Charge added to CB & removed from Cc Q=∫I dt=√3/2.VpωC∫cosωt =√3/2 Vp C t=0Π/2ω □ Change in potential of CB&CC: √3 Vp/2 □ Voltage on the Bank as in FIG

  10. Voltage Trapped & Phasor Diag. • CCT, after breaker open in B&C,1/4cycle □ After ¼ cycle VB=√3/2 Vp • CN<<C its current negligible • VN=VB-Vp(-1/2+√3/2)=Vp/2

  11. Max Voltages across CB contacts • High Voltages across C.B.restrikes • by Trapped charges, one side fixed , • The other driven by supply, their max: VA=2.5Vp (90◦ after B&C clear), VB=(1+√3/2)Vp (210◦ after B&C clear) VC=(1+√3/2)Vp(150◦ after B&C clear) □ Case 2: B&C do not interrupt in 90◦ after A □Voltage VAA’=VAC-VA’C’ assuming C not interrupted: □C &C’ at same potential, VA’N=Vp

  12. Case 2, Discussion continued • VA’C’=VA’N+VNC’, • initially VNC’=0.5Vp • Then half of ph-ph voltage: VBC=√3 Vp sinωt  VNC’=Vp(0.5+√3/2 sinωt) and : VA’C’=Vp(1.5+√3/2sinωt) • At source: VAC=√3Vpsin(ωt+Π/3)= =√3Vp(1/2sinωt+√3/2cosωt) VAA’=VAC-VA’C’=1.5Vp(cosωt-1)

  13. Case 2, Continued … • !80◦ later, 3Vp on A,if B&C not open • Against 2.5Vp when B&C opened • If C.B. can not withstand the Voltage across it: a- 1 or 2 contacts restrike & pass I • In 3ph Cap. Bank (isol. N) A cleared 1st , B&C after 90◦ (as case 1) then ph A restrike when VAA’=2.5Vp

  14. Restrike on Ph.A after B&C clear • Equivalent CCT: • Initial conditions: Vs=-Vp,VCA=VA’N=+Vp VCN=VNG=0.5Vp • Voltage on CA Osc. f=1/[2Π√LCeq] Ceq=CACN/[CA+CN] • CA>>CN, • f0≈1/2Π√LCN

  15. The Transient Current • I=2.5Vp/[√L/Ceq] sinω0t • since N swing to -4.5Vp at P on fig • corresponds to zero value in H.F. current • If C.B. clear a H.V. remain on CN & often B and C restrike • Swing of N,  B’ & C’ swing by CB & Cc • When VNG 4.5 Vp VB’G=[-4.5+(√3/2-1/2)]Vp=-4.134Vp VC’G=[-4.5+(-1/2-√3/2)]Vp=-5.866Vp

  16. Discussion continued…. • Now : VBG=0.5Vp=VCG therefore: VB’B=-4.634Vp, VCC’=-6.366Vp • one of phases likely to restrike, VLL across 2ph of bank • As if A & C closed simultaneously • Cap.Series CA & CC = ½ CA,induc=2L • ∆V=2x(sum voltages on breaks A &C) = 2x(2.5+1.366)Vp If initial restrike on pole A occur, when Vp across it

  17. Discussion on Restrike Continued… • This Shared equally CA & CC • CN<<CA not always prevail, i.e.: O.C. Transmission Line • Considerable Cap. To Gr. & as well as phases • Where C1/C0>1 Reach one asympt. As C0 rise Effect shown on TRV of Fig □C1/C0=1 when solidly Gr

  18. Discussion on CN Value & Effect • In Solidly Gr.:Vmax<2 PU (or in 1 ph) • Vmax=3 PU, Isolated N (function of C1/C0) • Affect the restrike of C.B. • 1 Ph. SW. analysis Principals employed □ Symmetrical Components Method

  19. The Symmetrical Component • Asymmetry removed by : replacing it, 3 sequence Network synthesize asymmetrical comp.s • Fortescue: extension, Transient study • Osc. freq. resolved in +,-,0 seq. comp • Voltages Asymm. When ph A of C.B. opens • VA,VB,VC have Sym comp. V0,V1,V2 • Opening A • ~ inserting Z between Contacts • Z∞ ≡ interrupting current

  20. CCT Breaker Interruption & Fault • A 3 Ph Fault &1stpole Opens • (if a=e^j2Π/3) & • VA=IAZ, VB=Vc=0 • V0=1/3(VA+VB+Vc) V1=1/3(VA+aVB+VC) V2=1/3(VA+aVB+aVC) • V0=V1=V2=VA/3 • I0+I1+I2=VA/Z

  21. Sym. Comp. for Transient Analysis • V0=I0Z0,V1=I1Z1+E1, V2=I2Z2 • Seq. Imp. seen from one ph. Contacts • or 3V0=3V1=3V2=VA •  3V0=I03Z0, 3V1=I13Z1+3E1,3V2=I23Z2 • VA across C.B. is TRV • When 2nd &3rd open similar CCT can be proposed • Not well adapted to: Assym. Faults

  22. Sym. Comp. Application …. • Viewed from contacts, not a balanced system • 2 Degrees of Asym.(Fault&Switch) • In Case of 1 ph to Gr Fault: Seq. Network as Fig. • As seen from Fault rather than breaker • Iloop=IF/3=I0=I1=I2 • Just if C.B. in branch develop across it & TRV across it

  23. Discussion of Seq. Comp. ph-G F • Network so Connected : seq. voltages add • C.B. clearing F not at F& elsewhere • Switches should opened simult. In 3 Networks • Seq. comp. currents must be injected at C.B. terminals in each ph seq. • TRV of C.B. is the sum of these 3 responses

  24. Practical Application • 1 ph-Gr F on a Cable System • The Eq. CCT • The seq. Network of fault needed • CQ:Iso-NCapBank CR: Neutral Cap. • CP: Cable cap./phase • L:source inductance

  25. Seq. Network of 1 Ph._Gr F • The Seq. Network • To apply Current Injection, E sh.cct. • Then remaining CCT Reduced simple CCT(2 Freq) • CR<<CQ & CP Then C0=Cp ω1=1/√[L(CP+CQ)], ω2=1/√LC0

  26. The current Injection • Ramp Current I’t inj. Parallel LC CCT V=I’L(1-cosωt) • I’, slope of current at zero,sym F Vp/L •  V=Vp(1-cosω0t) • Now Inj I0=I1=I2=1/3 IFault,SOLUTION: • V=2Vp/3(1-cosω1t)+Vp/3(1-cosω2t) • If N Gr with,4<R<20Ωs,2000>IF>400 • this affect Zero seq. network • Typical values:L=1mH,C≈5 μF • Z0=√L/C0=√1000/5=14.1Ω, • If R>28Ω Osc TRV suppressed, Fault Current control at Neutral

  27. Sym. Comp. Solution, Discussion • load rep. by resistance contr. Damp • Load N isol. Shunt + & - seq. networks only • Compare with classical method • The injected CCT • result of it=the seq network injection

  28. Traveling Waves & Transmission Line Model • example of Distributed parameter of: R, L, C • Phenomena of energizing a line • Travels with finite speed of EM Ws • If after ∆t a length ∆x is charged • C , F/m Q=C V ∆X

  29. Electromagneitc Propagation • Results in : 1- An Electric Field in ∆X 2- A Magnetic Field around Cable • The current determined: I=VC∆X/∆t=CV dx/dt (dx/dt=ν) •  I=CV.v • flux linkage : Φ=L∆X I =L∆X.CV.v • induced emf : (v=1/√LC) dΦ/dt=LCV v ∆X/∆t=LCV v V=LCV v2

  30. Transmission Line Fields • Z0=√(L/C) (typical line 400Ω, Cable 30-80Ω) • A Voltage Traveling wave & then V/Z0 A Current wave • VI  1/2CV2. v and 1/2LI2 .v (each ½ VI) • P=E X H magnitude & Direction of Energy Flow

  31. WAVE EQUATION • Small Segment • -∆V=L ∆X ∂I/∂t • ∂V/∂X=-L ∂I/∂t • current to ∆C is : -∆I=CV∆X ∂V/∂t • ∂I/∂x=-C ∂V/∂t • Combining them: ∂V/∂x=-L∂I/(∂X∂t) ∂I/∂x ∂t=-C∂V/∂t • ∂V/∂X=LC∂V/∂t • ∂I/∂x=LC∂I/∂t

  32. SOLUTION of WAVE EQUATION • I=f[x ±1/√LC] • I(x,t)=f1(x-vt)+f2(x+vt) • employing: ∂V/∂x=-L∂I/∂t= Lv[f’1(x-vt)+f’2(x+vt)] • V(x,t)=Lv[f1(x-vt)-f2(x+vt)]= Z0 f1(x-vt)-Z0 f2(x+vt) • Combing : • V(x,t)+Z0 I(x,t)=2Z0 f1(x-vt) • V(x,t)-Z0 I(x,t)=-2Z0 f2(x+vt)