High Density Cooling Air conditioning for high density applications Coolblade: chilled water in-row cooler 16&27kW Coolmate: chilled water pumping module & hydraulic splitter 90&160kW
High Density Cooling The increase in heat removal requirements makes it necessary to adopt different stategies for datacenter cooling
High Density Cooling It may be necessary to reject more than 30 kW of heat from a single rack
High Density Cooling Typical datacenter arrangement: hot aisle – cold aisle with perimetral cooling One perforated tile of the raised floor will hardly deliver more than a few kW of cooling
High Density Cooling In-row cooling: hot air is treated “on the spot” Air flow & cooling capacity and are greater than with a raised floor
High Density Cooling Preferred application High density racks in a hot or cold aisle containment, with or without perimetral cooling in mixed high density-low density situations
High Density Cooling System operation and layout water out 18°C water in 13°C water out 12°C water in 7°C Coolmate will supply controlled temperature water to avoid condensation Coolblade units will modulate fan speed according to actual heat load from the racks
High Density Cooling Coolblade: main features Galvanized sheet metal frame and panels, epoxy-polyester powder coated outside, A2 class insulating foam inside Mounting feet with wheels
High Density Cooling Coolblade: main features Variable speed diagonal fans G2 pleated air filter (EN779)
High Density Cooling Coolblade: main features High efficiency aluminium fin, copper tube water coil Dual circuit coil (model size 30)
High Density Cooling Coolblade: main features Upper & Lower hydraulic connections Stainless steel condensate tray
High Density Cooling Coolblade: main features Loss of air flow, dirty filter and water leakage detectors
High Density Cooling Coolblade: main features 230V/1ph/50Hz dual power inlet IEC320 with manual switch Microprocessor control with LCD display
High Density Cooling Coolblade: options Condensate pump Lack of water detector BMS communication cards
High Density Cooling Coolmate: main features Self-supporting galvanized sheet metal structure epoxy-polyester powder coated outside A2 class insulating foam inside
High Density Cooling Coolmate: main features Hydraulic connections on the bottom Brazed plate heat exchanger Dual water pump
High Density Cooling Coolmate: main features 0-10V servo controlled water valve Ambient T°C/h% sensor
High Density Cooling Coolmate: main features Outlet water temperature sensor Microprocessor control with LCD display
High Density Cooling Coolmate: options control valve on primary circuit 2-way control valve on primary circuit
Options b Flow switch on secondary (a) or primary (b) circuit (excluded with 2-way water valve) a Hydraulic connections on the top