Planning & Optimising the Green IT Datacentre: Design, Operation & Management Best Practices, Technologies & Challenges Pierre Ketteridge, IP Performance Ltd. Green IT Business Transformation Seminar. Introduction. Yes! Of course… …but only with careful planning, design and management!.
E N D
Planning & Optimising the Green IT Datacentre: Design, Operation & Management Best Practices, Technologies & ChallengesPierre Ketteridge, IP Performance Ltd Green IT Business Transformation Seminar
Introduction Yes! Of course… …but only with careful planning, design and management!
Introduction • The direct carbon impact (ie Carbon Footprint) of Data Centres on the environment is almost exclusively related to power consumption • Data Centres do not (when properly designed and managed) vent hot air or polluting gases into the atmosphere – cooling should be a ‘closed system’ • There may be indirect carbon impacts through staffing levels, travel to and from site, operational maintenace and housekeeping
Introduction 15% of business power consumption is accounted for by Data Centres & ICT… Cooling 50% IT Components 40% 10% Power Distribution …Lighting accounts for 1-3%, dependent on whether LO operation is implemented or not
Cooling Cooling falls into two categories: Air Cooling Liquid (water) Cooling
Cooling> Air Cooling Air Cooling The traditional way of cooling a Data Centre Computer Room: CRAC (Computer Room Air Conditioner) Water Chiller Cold Aisle/Hot Aisle Configuration
Cooling> Air Cooling Inherent limitations of CRAC-based Air Cooling Systems: CRAC capacity needs to be 30% greater than the actual demand Limitations in cooling (5kW – 7kW per rack) N+1 active equipment resilience/redundancy drives efficiency of cooling system down further
Cooling> Air Cooling Some Easy-to-Implement Air Cooling Optimisation Suggestions: Hot Aisle/Cold Aisle Arrangement Cold Aisle Containment Blanking Panels Raised Floor Brush Strips Underfloor, Inter- and Intra-rack Cable Management Free Air Cooling
Cooling> Air Cooling> Hot Aisle/Cold Aisle • With no hot aisle/cold aisle • arrangement, returning heated • air mixes with the CRAC-cooled • air and cooling to the DC CR • equipment is impaired. There is • also the issue of bypass cold • airflow, which can impact chiller • operation. • With a hot aisle/cold aisle arrangement, chilled air is forced out into the front-of-cabinet facing cold aisles, across the equipment surface, and warm air is channeled out into the rear-of-cabinet facing hot aisle for return to the chiller/CRAC.
Cooling> Air Cooling> Hot Aisle/Cold Aisle • Ineffective positioning of CRACs impair the • airflow around the DC CR. • CRACs along the side walls are too close to the • equipment racks, and will cause the airflow to • bypass the floor vents in those cold aisles. • Place cooling units at the end of the equipment • rows, not mid-row. • CRACs should be aligned with the hot aisles to prevent hot/cold aisle airflow crossover, which apart from increasing the temperature of air supply to the rack fronts but also can trigger the cooling unit to throttle back, reducing cooling overall. • Limit maximum cooling unit throw distance to 50'
Cooling> Air Cooling> Hot Aisle/Cold Aisle Separation of High-density Racks • Air cooling systems become ineffective • when high-density racks are co-located • “Borrowing” of adjacent rack cooling • capacity is not possible in this • configuration • An alternative (other than self-contained • cooling) is to spread out high-density • racks to maintain the cooling averages • Obviously this is not always practical – • witness the prevalance of blade server and • virtualisation technologies – two to five • times the per rack power draw of • traditional servers
Cooling> Air Cooling> Cold Aisle Containment ColdAisle Containment • Very simple to deploy / Retrofit • Hot and cold aisles physically separated • Greater watts per rack approx 10kW • Over sizing of the CRAC is reduced • CRAC efficiency is increased due to a higher delta T • CRAC fan speed can be reduced which provides: • - Reduced running costs • - Increased MTBF
Cooling> Air Cooling> Blanking Panels • Reduction and stabilization of equipment air-intake temperatures • • Elimination or reduction of the number and severity of hotspots • • Increased availability, performance, and reliability of IT equipment, especially in the top one-third of the equipment cabinet • Elimination of exhaust air recirculation within the cabinet, optimising cooling and reducing energy consumption and OpEx • Deferral of CapEx (additional cooling capacity) • The potential of greening the data center by reducing its carbon footprint
Cooling> Air Cooling> Raised Floor Brush Strips Raised Floor Brush Grommets • Cable openings allow approx. 60% • of conditioned air to escape • Use brush grommets to seal every • cabling entry point • Increases static pressure in the • under-floor plenum - ensures that • the DC airflow remains at a • pressure above atmospheric • Extend reach of Hot Aisle/Cold Aisle • system • Self-sealing and interwoven closure system • Brush grommets can be installed as DC is commissioned, or retro-fitted • No changes to existing wiring configuration • Fits into the raised floor tiles prior to cabinet installation • Simple • Inexpensive
Cooling> Air Cooling> Cable Management Cable Management – Intra-rack, Inter-rack and underfloor • Airflow within racks is also affected by unstructured cabling arrangements • Deployment of high-density servers creates new problems in cable management • Cut data cables and power cords to the correct length – use patch panels where appropriate • Equipment power should be fed from rack-mounted PDUs • Raised floor/subfloor plenum ducting carries other services apart from airflow: • Data cabling, power cabling, water pipes/fire detection & extinguishing systems • Remove unnecessary or unused cabling - old cabling is often abandoned beneath the floor – particularly in high churn/turnover Co-Lo facilities • Spread power cables out on the subfloor - under the cold aisle to minimize airflow restrictions • Run subfloor data cabling trays at the stringer level in the hot aisle - or at an “upper level” in the cold aisle, to keep the lower space free to act as the cooling plenum
Cooling> Air Cooling> Free Air Cooling What is Free Cooling?
Cooling> Air Cooling> Free Air Cooling Average UK Temperatures
Cooling> Air Cooling> Free Air Cooling Budgetary Example – Projected Cost of Running the System for a Year • Not using the Free Cooler • Chiller Capacity 150 kW • Energy needed to run the chiller 62 kW • Numbers of Hours running per year 8784 • Cost per kWh £0.0784 • Total Cost of Running per Year £42,697.00 • 100% free cooling 70% of the year • Chiller capacity 150 kW • Energy needed to run the chiller 62 kW • Numbers of hours running per year 2580 • Cost per kWh £0.0784 • Cost of running the chiller £12,540.00 • Cost of running Free Cooling (10.4kw) £ 5,058.00 • Total Cost of Running per Year £17,599.00
Cooling> Liquid Cooling High Density Data Centres and Liquid Cooling • When going above 10kW per rack a new, more targeted/directed cooling method is required • Most common methods is Water Cooling
Cooling> Liquid Cooling So What is Liquid – or Water – Cooling? • Delivery of chilled water to multiple heat exchange points from a central unit • The central unit circulates water from the buildings existing chilled water loop • Heat exchange units in rear doors (one per cabinet, capacity 30kW) or side doors (2 x dual cabinet resilience, 2 x 15kW) • Heat is carried away in the water - air is ejected back out into the DC at the same temperature it entered the rack - zero thermal footprint
Cooling> Liquid Cooling Why Use Water Cooling? • Water 3,500 times more thermally efficient than air • Air cooling only delivers 5-7kW of cooling per rack (10kW with hot aisle/cold aisle arrangement) • High Density DCs place increasing power and thermal control demands on the infrastructure • Blade servers - up to 80 servers in a standard 42u cabinet – and anything from 80 to 800 virtual machines! • Fully-loaded blade server rack can produce 25Kw of heat • Water Cooling can deliver 30kW of cooling to a fully-loaded 42u rack
Cooling> Liquid Cooling Adding the benefits of Free Cooling, some CapEx/OpEx implications of Water Cooling: • Water cooling has a slightly higher install cost (more terminations/ pipe work)…but greater kW per sq ft gives us… • 35-45%reduction in required real estate • 15-30%reduction lower in overall construction costs • 10-20%reduction on total annual fan power consumption • 12-14%reduction in power delivered to mechanical chilled water plant • For an average efficiency data centre, annual savings of £22,000 and £80,000 for small and large data centres respectively • Significant when the design life of the data centre is 10 years • Reduction in energy is a reduction in costs and also a reduction in your carbon footprint
Network Components Active Equipment (Networking) • Switches • Routers • Appliances • Load balancers • Caching/Proxying • Bandwidth Management • Application Acceleration & Optimisation
Network Components> Ethernet LAN Switches Data Centre Switch Requirements • Port density • Performance • Functionality • Feature set • Resilience/Redundancy • Security • Price • Power consumption/Heat output Feeds & Speeds Capabilities
Network Components Network Components> Ethernet LAN Switches Data Centre Switch Requirements • High port density per chassis • Low power consumption • Availability • High performance • Low latency Optimised for the environment Optimised for the application
Network Components Network Components> Ethernet LAN Switches
Network Components Network Components> Ethernet LAN Switches Ethernet Switch Power Consumption - A Comparative Example: 15,000 User Network • Across an installed network base of 15,000 ports, it was possible to save 102 kW/h, resulting in: • Lower Power Consumption • Less Cooling Equipment • Smaller Batteries • Smaller Data Centers
Network Components> WAN Routers Routers • Look at power consumption figures/thermal output • Deploy shared WAN architecture – MPLS, VPLS, IP VPNs • Investigate leveraging and integrating bandwidth optimisation and application acceleration technologies
Network Components> Appliances> Load Balancing LAN/WAN Optimisation Appliances • …an area where we can make a difference, in the way in which technologies are deployed to optimise LAN/WAN bandwidth usage and availability of back-end servers. • An excellent example would be application delivery, traffic management and web server load balancers: • High Performance through acceleration techniques • High Availability
Network Components> Appliances> DPI Bandwidth Management More LAN/WAN Optimisation Options… DPI Bandwidth Management solutions: • Inspection, Classification, Policy Enforcement and Reporting on all traffic: • Identification - application signature, TCP/UDP port, protocol, source/destination IP addresses, URL • Classification – CoS/ToS (IP Prec/Diffserv CodePoint/DSCP); user-defined QoS policy • Enforcement based on user-defined policy • Reporting – RT and long-term – extremely valuable for SLAs/SLGs in DC environments
Network Components> Appliances> WAN Optimisation LAN/WAN Optimisation Options (cont’d) WAN optimisation and application acceleration: • Usually deployed as a reverse proxy device • Provides some form of bandwidth management • Protocol optimisation – making LAN protocols more latency-tolerant • eg. TCP handshake spoofing • Object caching • Files, videos, web content, locally cached and served • Byte caching • Repetitive traffic streams, hierarchically indexed and tagged (inline only) • Compression • (inline only) • Proxy support for common protocols • HTTP, CIFS, SSL (HTTPS), FTP, MAPI, P2P, MMS, RTSP, QT, TCP-Tunnel, DNS etc
Network Components> Appliances> WAN Optimisation LAN/WAN Optimisation Options (cont’d) WAN optimisation and application acceleration: • Reverse Proxy • Bandwidth Management • Protocol optimisation – for latency-intolerant LAN protocols • eg. TCP handshake spoofing • Object caching • Byte caching • Compression (inline only) • Proxy support for all/most common protocols
Infrastructure Management Managing the Data Centre Infrastructure • “Lights Out” operation requires… • Little or no human intervention • Exceptions: • Planned maintenance • Fault rectification/management (emergency maintenance/repair) • Physical installs/removals • Housekeeping (cable management, MAC) • Cleaning • How are you going to control it? How are you going to manage it?
Infrastructure Management Remote Control and Management • RDC, VNC – In Band Management • Console Servers – Out of Band Management • KVM switching (local/remote) • KVM/IP switching & USB2 VM Remote Drive Mapping • IPMI Service Processor OOB Management • Intelligent Power Management (iPDUs)
Summary Summary - Cooling • Data Centre “Greening” is mainly down to managing power consumption • Cooling is the biggest consumer of power (50%) • Optimise your air-cooled CRAC system: • Cold Aisle/Hot Aisle arrangement • Cold Aisle containment • Blanking Panels • Raised floor/underfloor brush strips/grommets • Free air cooling system
Summary Summary – Cooling (Cont’d) • If deploying high-density bladeservers/virtualisation, consider water-cooling (max kW/hr cooling rises from 5-10kW/hr to 30kW/hr) • Targeted control • Even distribution of cooling • Full (42u) rack utilisation • Zero thermal footprint – design flexibility • Remember free air cooling reduces costs further • Real Estate savings
Summary Summary - Active Equipment (Networking) Switches: • high port density, low power consumption, PSU disconnect/fanless operation • Extrapolate power consumption over entire port count Routers: • Modular architecture, high density, low power consumption • Make full use of available bandwidth • Shared services: IP VPN, point-to-multipoint or meshed MPLS • Use/honour QoS marking • Deploy Bandwidth optimisation techniques
Summary Summary - Active Equipment (Networking) – Cont’d Appliances: • Load Balancing – Maximise performance, utilisation and availability of server resources • DPI Bandwidth Management • WAN Optimisation Maximise performance, utilisation and availability of WAN resources
Summary Summary – Infrastructure Management • Remote Infrastructure Control and Management enables “lights-out” operation • Remote console management gives CLI access to network infrastructure – routers, switches, firewalls, other network optimisation appliances • KVM-over-IP allows remote, distributed control of server and workstation systems • Service Processor Management allows remote control and management of system processor and environmental monitors/controls • Intelligent Power Management enables remote monitoring, control and management of PDUs, UPS and battery backup resources