An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Standard 189.1-2100 Southern Alberta Chapter T. David Underwood, P.Eng., FASHRAE November 20, 2012

  2. TEACH ASHRAE Will Give You the World Give Back to ASHRAE NETWORK LEARN GROW SHARE This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee

  3. Complete the Distinguished Lecturer Event Summary Critique Forms are available at: www.ashrae.org/distinguishedlecturers • CTTC needs your feedback to continue to improve the DL Program • Distribute the DL Evaluation Form to all attendees • Collect at the end of the meeting • Compile the attendee rating on the Event Summary Critique • Send the completed Event Summary Critique to your CTTC RVC and ASHRAE Headquarters

  4. VOLUNTEER! ASHRAE Members who attend their monthly chapter meetings become leaders and bring information and technology back to their job. Find your Place in ASHRAE! Visit www.ashrae.org Become A Future Leader in ASHRAE – Write the Next Chapter In Your Career You are needed for: • Membership Promotion • Research Promotion • Student Activities • Chapter Technology Transfer Technical Committees

  5. Standard 189.1 Development Implementation Practical use

  6. What is Standard 189.1? A design standard not a rating system Developed in ANSI model code language Applies to all buildings except low-rise residential (same as ASHRAE/IES Standard 90.1) Optional compliance path to the International Green Construction Code

  7. Standard 189.1 provides • High-performance green buildings minimum requirements: • Mandatory criteria PLUS • Performance options • Prescriptive options • Evidence based requirements that complement green building rating programs

  8. Sponsors and Project Committee • Sponsor and co-sponsors: • ASHRAE • USGBC (U.S. Green Building Council) • IES (Illuminating Engineering Society) • Project committee: 35+ voting members ; variety of: • disciplines • industries • organizations

  9. Standard for the Design of High-Performance Green Buildings The Green Standard Standard 189.1-2011

  10. Standard 189.1 Building Blocks Std 189 CA DHS EHLB R-174 Std 62.1 Std 90.1 Std 180 Std 55 Guideline 0 BIFMA ASME ASTM US EPA US DOE IESNA USGBC Green Seal

  11. ASHRAE Standard 189.1-2011 XXXXXXXXXXXXXXX “…Choice of the construction team to use IGCC or Std. 189.1“ (International Green Construction Code)

  12. Standard 189.1 Sections §1.0 through §4.0 cover the Purpose, Scope, Definitions and Administration §5.0 through §10 are the working sections

  13. §1.o0 Purpose To provide minimum requirement for: • Siting • Design • Construction • Planning for operation ….of high performance green buildings.

  14. §2.0 Scope 2.1 Provides minimum criteria for: a. New 1. Buildings 2.Portions of buildings or 3.Systems & equipment in existing buildings b. Site sustainability, water use efficiency, energy efficiency, indoor environmental quality (IEQ), atmospheric impact, and resources. 2.2 Doesn’t cover single family dwellings or non water or energy use buildings. 2.3 Doesn’t supersede any health & safety requirements

  15. §3.0 Definitions, Abbreviations and Acronyms

  16. §4.0 Administration and Enforcement 4.1 Buildings shall comply with mandatory requirements in Sections 5 through 11 4.1.1 Normative appendices are mandatory 4.1.2 Informative appendices offer further information

  17. Compliance Paths Prescriptive Path Mandatory + (simple option, very few calculations) (more options, but more effort) Performance Path Mandatory +

  18. §5.0 Site Sustainability Mandatory Provisions • Allowable sites with limitations for Greenfield, Brownfield, orGreyfield • Mitigation of heat island effect including:% hardscape solar reflectance index (SRI) natural vegetation and shading by structures

  19. §5.0 Site Sustainability Mandatory Provisions (cont) • Light pollution reduction includes: backlight, uplight and glare (all tabularized) • Invasive plants removal • Mitigation of transportation impacts Connections of primary building entrances to pedestrian walkway for access to public ways or transit stops

  20. §5.0 Site Sustainability Prescriptive Option -Minimum 40% of site area shall have effective pervious area -20% of area shall be maintained as Greenfield Performance Option - For existing buildings 20 % of average rainfall to be managed - For new buildings on Greenfield or Brownfield sites 40% of rainfall to be managed. -For all other sites manage 50% of rainfall

  21. §6.0 Water Use Efficiency • Mandatory Provisions • Bio-diverse & adapted plantings for 60% of landscape • Hydrozoning • Smart irrigation controllers • Plumbing fixtures and appliances standards • Efficient drift eliminators on cooling towers and condensate collection for HVAC systems • Monitoring devices with data storage retrieval requirements

  22. §6.0 Water Use Efficiency • Prescriptive Option • Cooling tower and blow down rates • High efficiency Energy Star cooking equipment • Only air cooled refrigeration equipment • Performance Option • Site water reduction: • <35%potable water for irrigation • Proposed use < [mandatory + prescriptive]

  23. §7.0 Energy Efficiency • Mandatory Provisions §7.3.2 on-site renewable provisions for future installation §7.3.3 energy consumption management and recording • Prescriptive Options • 189.1 supersedes 90.1 • For building envelope, roof and solar heat gain coefficient (SHCG)

  24. §7.0 Energy Efficiency (cont) §7.4.3 HVAC • Based on Standard 90.1, but modified to gain improved energy performance over minimum code standards • Demand control ventilation (DCV) for occupied spaces. (Lower occupancy threshold than 90.1) • Economizers shown for equipment size and climate zone • Restricts amount of reheated or re-cooled air • Exceptions allowed from Standard 90.1

  25. §7.0 Energy Efficiency (cont) § 7.4.6 Lighting • Lighting power allowances as per Std. 90.1 multiplied by the data in the table in this section • Occupancy sensors to be installed to reduce power to <50% for • Hotel, motel hallways • Storage stack aisles • Library stacks • Exterior lighting control based on time of day use § 7.4.7 Other Equipment • High efficiency motors, appliances and Energy Star rated products required

  26. §7.0 Energy Efficiency (cont) § 7.5 • Performance option requires • both energy cost budget method and CO2 equivalent Or • Prescriptive paths of Section 5, 6 and 8 that reduce energy requirements - Refer to Normative Appendix D for the building model guidelines Proposed Performance < (Mandatory + Prescriptive)

  27. §8.0 Indoor Environmental Quality (IEQ) • Key Items • Outdoor Airflow • Tobacco Smoke Control • Outdoor Air Monitoring • Filtration and Air Cleaning • Day lighting • Thermal Comfort • Acoustics • Vibration

  28. §9.0 Impact on Atmosphere, Materials and Resources • Mandatory • Construction waste management • Divert 50% of non-hazardous waste, demolition debris • Limit total waste generated per floor • No CFC’s; fire suppression systems contain no ozone depleting substances (CFCs, HCFCs, Halons) • Prescriptive Option • Reduced impact materials (recycled, regional, bio-based) • Performance Option • LCA per ISO 14044 and must include land use, resource use, climate change, ozone layer depletion, human health, ecotoxicity, smog, acidification, eutrophication • Must show 5% gain in at least two categories

  29. §10.0 Construction and Plan for Building Operation • Only section where all requirements are mandatory • Mandatory CONSTRUCTION requirements include: • Protecting materials that might absorb water • Installing no materials with visual bio-growth • Placing vehicle staging areas away from air intakes for hospitals, schools, residences, etc. that may adjoin the project

  30. §10.0 Construction and Plan for Building Operation (cont) • Mandatory OPERATION requirements include: • Site sustainability • Water use efficiency • Energy efficiency • Indoor environmental quality … and Commissioning to assure verification of construction of these items as specified earlier in the Standard In addition to: • Maintenance • Service Life • Transportation Management

  31. §10.0 Construction and Plan for Building Operation (c0nt) • Site Sustainability • Maintenance procedures for healthy vegetation growth • Water Use Efficiency • Measurement and verification of water use benchmarked against criteria like Energy Star Portfolio Manager

  32. §10.0 Construction and Plan for Building Operation (cont) • Energy Use Efficiency • Initial measurement & verification using devices as specified in§ 7.0 • Procedures to track and assess energy: • Hourly load profiles • Monthly average daily load profiles • Monthly and annual energy use • Monthly and annual peak demand

  33. §10.0 Construction and Plan for Building Operation (cont) • Indoor Environmental Air Quality • Outdoor Airflow verified by: • Handheld devices or permanent stations • Procedures to react if 15% lower than minimum specified rates • Indoor Air Quality • Air cleaning equipment in restricted areas • Biennial monitoring through testing, occupant perception or complaint/response reports • Green cleaning materials and methods

  34. §10.0 Construction and Plan for Building Operation (cont) • Maintenance • Standard 180 for planning • Documentation of plan via electronic storage and maintenance manuals • Service Life • Maintenance and repair on structure, envelope and hardscape

  35. §10.0 Construction and Plan for Building Operation (cont) • Transportation • Preferred parking for car pools, etc. • Copy of plan distributed to all building occupants • Access to emergency transportation • If leased, parking space not in the lease rate

  36. Standard 189.1 Practical Use • Requires participation of all parties through: • Commissioning as specified in Guideline O including: • Well developed Owners Project Requirements (OPR) • Leads to Integrated Building Design (IDB) as an ideal approach to affordable Green Buildings

  37. CONCLUSION Standard 189.1-2011 raises the bar for the design of high performance Green Buildings The many players that contributed to developing this standard believe that it provides a realistic platform for responsible design