Rand Westbrook Senior Manager Real Time Operations August 3, 2011
Manual Load Shed • Load Shed Application
Manual Load Shed 9 13 4 1903 1913 1910 270 260 E E E
EMLR Folders • From the EMS Web • Select Transmission Dispatching (RTO) • Select Load Curtailment Summary • Select Block 4 • Select Manual Load Shed List • EMLR will need to be deactivated in order to close breakers while restoring feeders.
Manual Load Shed • SCADA Unavailable • Dispatch Substation Performance crews to the Block 4 substations to trigger EMLR
Mechanics (typical substation) System Frequency RTU Auxiliary Relay UFC Relay EMLR 59.3 Hz 58.9 Hz 58.5 Hz 55.0 Hz Distribution Feeder Breakers