An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Welcome Welcome to Yaskawa Electric America’s Training Café Express Today’s Topic is Selecting E7/P7/F7 Drives for Single-Phase Input Applications • To make this Café enjoyable for all, please follow these tips on web class etiquette. • Please do not put us on hold. Others will hear the hold music. • Do not use a speaker phone. Background noise can be heard. • Don’t be shy, we welcome comments and questions. (Press *6 to mute and unmute your phone) • Questions not answered during the Café can be e-mailed to training@yaskawa.com or can be entered into the survey sent to you at the end of the class.

  2. Single-Phase to Three-Phase Conversion • Why the need for single-phase to three-phase power conversion? • Areas not originally designated for industrial manufacturing with only single-phase power subject to increased demand to support small manufacturing operations • Small start-up companies • Custom manufacturing (specialty) operations • Residential/ Commercial expansion needing increased water demands • Remote pumps (submersible/booster) • Increased pump HP (moving water further distances) • Increased activity in energy sector • Oil/Natural gas wells • De-watering pumps Need three-phase power to support increased demand!

  3. Single-Phase to Three-Phase Conversion • Methods of converting single-phase to three-phase power: • Phase Converters • Rotary Phase Converters (RPC) • Static Phase Converters (SPC) • Motor-Generator (M-G) Sets • Variable Frequency Drives (VFDs) • Single-Phase input models • Three-Phase input models (with appropriate derating)

  4. Methods of converting single-phase to three-phase power: Single-Phase to Three-Phase Conversion • Phase Converters • Rotary Phase Converters (RPC) • Use “idler” motor to generate third phase • Static Phase Converters (SPC) • Use inductors/capacitors to generate third phase Unbalanced phase impedance Difficult to balance phase voltages especially with varying load Requires de-rating applied motor (by as much as 50%)!

  5. Single-Phase to Three-Phase Conversion • Methods of converting single-phase to three-phase power: • Motor-Generator (M-G) Sets • Uses multiple sets of windings on single rotor to generate three individual “new” phases • Good voltage balance  suitable for three-phase motors • Easily convert voltage level and frequency from incoming supply • Commutators require high maintenance • Expensive and bulky

  6. Single-Phase to Three-Phase Conversion • Methods of converting single-phase to three-phase power: • Variable Frequency Drives (VFDs) • Single-phase input models • Three-phase input models (with appropriate derate) • Provide balanced three-phase voltage • Can easily vary the voltage and frequency • No tuning of capacitors to varying loads • Soft start feature, PI control, extensive flexibility/programmability • Provides superior protective features (overload, under-voltage, etc.) • Reliable/maintenance-free operation

  7. Single-Phase Motors • Single-Phase Motors: • Readily available up to 5HP • Available up to and above 15HP but much less common • Expensive • Long lead times • Frequent maintenance Trend is to use three-phase motors (even below 5HP)!

  8. Single-Phase Applications • Common Single-Phase Applications: • Submersible Well Pumps • Irrigation Pumps • Fountain Systems • Pump Jacks (oil/natural gas well pumps) • Machining Centers/Lathes • Vacuums/Blowers

  9. Single-Phase Input Products • Yaskawa Single-Phase Product Offering: • VS-Mini (GPD205) • 115Vac, 1/8 HP to 1 HP, 0.8 Arms to 5 Arms • J7 (GPD305) – Available through March 2010 • 230Vac, 1/8 HP to 2 HP, 0.8 Arms to 8 Arms • V7 (GPD315) – Obsolete (subject to inventory on-hand) • 230Vac, 1/8 HP to 5 HP, 0.8 Arms to 17.5 Arms • V1000 • 230Vac, 1/8 HP to 5 HP, 0.8 Arms to 17.5 Arms • J1000 (use caution – output phase loss cannot be disabled) • 230Vac, 1/8 HP to 3 HP, 0.8 Arms to 9.6 Arms (ND)

  10. Single-Phase Input Products • Yaskawa Single-Phase Product Offering: • VS-Mini (GPD205) • 115Vac, 1/8 HP to 1 HP, 0.8 Arms to 5 Arms • J7 (GPD305) – Available through March 2010 • 230Vac, 1/8 HP to 2 HP, 0.8 Arms to 8 Arms • V1000 • 230Vac, 1/8 HP to 5 HP, 0.8 Arms to 17.5 Arms • J1000 (use caution – output phase loss cannot be disabled) • 230Vac, 1/8 HP to 3 HP, 0.8 Arms to 9.6 Arms (ND) • Single-Phase models up to 5 HP only! • All models run 230V three-phase motors!

  11. Single-Phase Input Products • What about single-phase applications at 480V or applications larger than 5 HP? • Use E7/P7/F7 and three-phase motor with appropriate derating as outlined in application note AN.AFD.15 “Applying E7/P7/F7 Drives To Single-Phase Input Applications” • What does document AN.AFD.15 contain? • Let’s take a look!

  12. Important Considerations When Using a Three-Phase Drive with Single-Phase Input Drive Specifications (w/ derating) Drive HP Output Current Input Current DC Link Choke Selection Input Voltage Specifications Different than three-phase Output Voltage Limitation Effect on motor power Overload Rating Limited to low speeds Wiring & Branch Circuit Recommendations DC Link Choke Dimensions Single-Phase Input Power Application Specifications

  13. Single-Phase Input Drive Derating • Why is Drive derating required? • Three-phase VFD designed to accommodate 300/360Hz DC bus ripple (3-phase full wave rectification at 50/60Hz)

  14. Single-Phase Input Drive Derating • Why is Drive derating required? • Single-phase 60Hz input results in 120Hz DC bus ripple! • DC bus capacitors need to provide more power • DC bus level will decrease a larger amount than with three-phase input during this time

  15. Single-Phase Input Drive Derating • Why is Drive derating required? • Duration between bus peaks is longer in single-phase case • Dc bus circuit will have to supply power for longer period • More stress on input and DC bus components t3 Time t1 > t3 Tt1

  16. Single-Phase Input Drive Derating • Why is Drive derating required? • Drive components subject to greater stress with single-phase input • DC bus circuit (capacitors, DC link choke, bus bars) • Increased ripple voltage and current • Capacitors need to deliver more of the power to the load • Input diode rectifier • Increased input current • Higher harmonic content • Using only 2/3rds of the rectifier • Input terminals • Increased input current • Higher harmonic content • Using only 2 of 3 input terminals

  17. Single-Phase Input Drive Derating • Therefore, derating of Drive HP and output amperage will be required so that the Drive components operate within their ratings! • Table 1 contains single-phase ratings for 240V and 480V models

  18. Selecting the Proper Drive • Select Drive that meets or exceeds both motor HP and motor FLA requirements • When making selection be sure to take into account operation using the service factor of the motor if required by the application • Drive must be selected to accommodate motor S.F. amps and motor S.F. horsepower if applicable!

  19. Selecting the Proper Drive • Select Drive that meets or exceeds both motor HP and motor FLA requirements. Include Service Factor if required. Example: Pump Rating: 7.5HP, 230V, 20Arms cont., SF amperage 23Arms Application Requirements: Case 1) No SF required: 7.5HP @ 20Arms Case 2) SF is required: 8.6HP @ 23Arms Note: 8.6HP = 7.5HP x 23A/20A Select Drive according to load requirement!

  20. Selecting the Proper Drive Example: Pump Rating: 7.5HP, 230V, 20Arms cont., SF amperage 23Arms Application Requirements: No SF required: 7.5HP @ 20Arms SF is required: 8.6HP @ 23Arms Note: 8.6HP = 7.5HP x 23A/20A Model 2011: No SF Required

  21. Selecting the Proper Drive Example: Pump Rating: 7.5HP, 230V, 20Arms cont., SF amperage 23Arms Application Requirements: Case 1)No SF required: 7.5HP @ 20Arms Case 2) SF is required: 8.6HP @ 23Arms Note: 8.6HP = 7.5HP x 23A/20A Model 2011: No SF Required

  22. Selecting the Proper Drive Example: Pump Rating: 7.5HP, 230V, 20Arms cont., SF amperage 23Arms Application Requirements: Case 1) No SF required: 7.5HP @ 20Arms Case 2) SF is required: 8.6HP @ 23Arms Note: 8.6HP = 7.5HP x 23A/20A Model 2015: SF is required

  23. Selecting the Proper Drive Example: Pump Rating: 7.5HP, 230V, 20Arms cont., SF amperage 23Arms Application Requirements: Case 1) No SF required: 7.5HP @ 20Arms Case 2) SF is required: 8.6HP @ 23Arms Note: 8.6HP = 7.5HP x 23A/20A Model 2015: SF is required

  24. Selecting the Proper Drive Select Drive that meets or exceeds both motor HP and motor FLA requirements Drive must be selected to accommodate motor S.F. amps and motor S.F. horsepower if applicable!

  25. DC Link Choke Benefits • Using a DC Link Choke allows us to pull more power from the VFD • Reduces DC bus ripple • Lowers input harmonics (from over 100% to 90% ITHD) • Improves input power factor (to approx. 0.7 PF) • reduces input current DC Link Chokes are listed in Table 1 • Link Chokes selected to optimize performance for single-phase use • Note: Models 18kW and smaller use a different link choke than what is normally used with three-phase input • Select DC link choke according to Table 1 • Caution - DC link chokes are open style (no enclosure) Therefore, DC Link Chokes must always be used!

  26. DC Link Choke Benefits

  27. Input Voltage and Frequency • Input Supply Specifications: • Standard VFD specifications with three-phase input: • 208-240/480Vac, +10/-15% • 50/60Hz, +/-5% • VFD Specifications with single-phase input: • 240/480Vac, +10/-5% • 60Hz, +/-5% Thus, strict input voltage tolerance of +10 to -5% and 60Hz applies with single-phase use! Note: Wire input using terminals L1(R) and L2(S) to accommodate units that incorporate AC fans and soft-charge circuits (larger models)

  28. Input Voltage and Frequency • Why the stricter input voltage tolerance? • Average bus voltage is lower with single-phase input than with equivalent three-phase input • Therefore, output motor voltage will be reduced • Motor power will be reduced with lower motor voltage • Output voltage of 207V with input voltage of 228V (240V – 5%) • Output voltage of 414V with input voltage of 456V (480V – 5%) Consider using a 208V or 400V motor if rated power must be developed at base speed to eliminate the effect of voltage deprivation! 208V and 400V motor selections are included in Table 1 Note: Additional impedance at the input of the Drive will cause additional voltage drop!

  29. Reduced Voltage Motors

  30. Input Voltage and Frequency • Input Supply Specifications: • Standard VFD specifications with three-phase input: • 208-240/480Vac, +10/-15% • 50/60Hz, +/-5% • VFD Specifications with single-phase input: • 240/480Vac, +10/-5% • 60Hz, +/-5% Thus, strict input voltage of 240V(480Vac) +10 to -5% at 60Hz applies with single-phase use! Note: Wire input using terminals L1(R) and L2(S) to accommodate units that incorporate AC fans and soft-charge circuits

  31. Single-Phase Input Current • Drive input current will be approximately twice the motor current • Single-phase to three-phase conversion accounts for majority of input current increase (factor √3) • Overall input Power Factor of 0.7 can be expected • Input current is included in Table 1

  32. Overload Capacity • Overload capacity with single-phase input is limited to 120% of Drive single-phase current rating • Increased DC bus ripple means the DC bus level will drop to lower level • As output power increases (high torque and high speed) average bus voltage decreases • Motor voltage further decreases as load increases Therefore, expect 120% overload maximum for starting purposes only! Consult factory with cyclic applications (repeating overload) or when overload in excess of 120% is required

  33. E7/P7/F7 Drives with Single-Phase Input • Document AN.AFD.15 also includes wiring and branch circuit recommendations • Table 2 contains: • Wire gauge recommendations • Fuse recommendations • Circuit Breaker recommendations

  34. DC Link Choke Details • Table 3 contains DC Link Choke dimensions • DC Link Chokes are “open” type (no enclosure) • DC Link Chokes in Table 3 are different from chokes used for three-phase input • Wire DC Link Chokes to terminals +1 and +2 (remove factory supplied shorting bar)

  35. Single-Phase Input Specification Summary • Summary: • Input Specifications: • Voltage: 240/480VAC +10% / -5%, • Frequency: 60Hz +/-5% • Drive Ratings must meet or exceed both motor HP and FLA • Be sure to include Service Factor operation if required • DC Link Chokes are required on models 18kW and smaller • Consult factory if Link Chokes cannot be used • Maximum Overload of 120% for starting purposes only • Expect motor voltage of approx. 207Vac (414Vac) with input voltage of 228Vac (456Vac) • Consider a reduced voltage motor (208/400V) if full HP is required with low input voltage • Specifications not mentioned in this document remain the same as standard three-phase product

  36. Input Phase Loss (PF) Faults • Final Comments: • When using the Drive with single-phase input the Drive’s input phase loss protection must remain enabled • If Input Phase Loss (PF) faults are encountered, be sure to check the load current and horsepower along with incoming line voltage levels to insure all are within Drive specification • Input Phase Loss faults generally indicate the Drive is undersized for the connected load • Disabling input phase loss protection will result in permanent Drive damage and void the warranty • Reducing Drive output frequency will reduce HP requirement • Limiting the maximum frequency may allow an undersized drive to operate the load (Power = Torque x Speed)

  37. Input Phase Loss (PF) Faults • Final Comments: • Consult factory when using other Yaskawa products with single-phase • Other products have not been officially evaluated for single-phase use

  38. That’s A Wrap! • Thank you for attending the Yaskawa Electric America Training Café. • Please see the Café Schedule in the partner login section of Yaskawa.com for future classes. • Training Café classes are held approximately once per month. • Please complete the survey sent to you at the end of the class to help us improve the quality and relevance of the Training Café.