250 likes | 388 Views
Preferred Utilities Mfg. Corp. Fuel Oil System Design for Fire Safety & Reliability. Preferred Utilities Mfg. Corp. 31-35 South St. • Danbury • CT www.preferred-mfg.com. Fire Safety Design. Fuel Source. Oxygen Source. Heat. We’ll discuss both both heat and fuel source removal…….
E N D
Preferred Utilities Mfg. Corp. Fuel Oil System Design for Fire Safety & Reliability Preferred Utilities Mfg. Corp. 31-35 South St. • Danbury • CT www.preferred-mfg.com
Fire Safety Design Fuel Source Oxygen Source Heat We’ll discuss both both heat and fuel source removal…….
Simplified Fuel System Day Tank Tank Room Return Supply Suction Pump Main Oil Tank
Fuel Source Day Tank Tank Room Return Supply Suction Pump Main Oil Tank
Remove Fuel Source Detect Fuel Leaks Stop Fuel Flow
Remove Heat Source Detect Heat Source Stop Fuel Flow
Heat Source Day Tank FIRE FIRE Tank Room Return Supply Suction Pump Main Oil Tank FIRE FIRE FIRE
Fire Safety Shut-off Valves • Multiple Fusible Links • Fuel Shut-off and • Limit Switch Stops Pump
Stop Fuel Flow “Down Stream” Day Tank Tank Room • “Up Stream” Leak • Alarm • “Down Stream” Leak • - Stop Pump • Heat Detected • - Stop Pump Return Suction Pump Main Oil Tank “Up Stream”
The Thing About Fuel Pumps Positive Displacement pumping action
Shutdown Conditions • Leak in discharge piping • Leak in day tank • Leak in pump set • Low level in main tank • Loss of flow in pump, to protect pump • High level in day tank • With and without Active PLC
Preferred Utilities Manufacturing Corp For further information, contact... Preferred Utilities Manufacturing Corporation 31-35 South St. • Danbury • CT T: (203) 743-6741 • F: (203) 798-7313 www.preferred-mfg.com