This forecast provides an analysis of recent sales and customer trends in Vermont, along with a preliminary state sales and demand forecast. It also includes projections for end-use saturation and solar load impacts. The forecast takes into account factors such as economic drivers, weather conditions, and price projections.

gtodd
Download Presentation

Vermont Long-Term energy and demand foreast

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Vermont Long-Term energy and demand foreast October 8, 2013 Eric Fox and Mike Russo

  2. agenda • Recent Sales and Customer Trends • Preliminary State Sales and Demand Forecast • Building a No DSM Forecast • End-Use Saturation Projections Integrating the New Appliance Saturation Survey • Estimating Solar Load Impacts

  3. VELCO System Energy 2003 to 2013 * 2013 – 7 mo actual /5 mo forecast While sales have been flat over the last ten years There have been two distinct periods – before and after the recession

  4. VELCO System peak Demand *WNLF_Peak = WN Energy / WN Peak Load Factor System peak shows a similar pattern Positive growth in 2013

  5. Peak-Day Temperatures 2013 was the hottest peak day in 11 years. Second hottest day based on a 3-day weighted THI

  6. GMP Year to Date Sales • January through August Beginning to see some sales and customer growth with improving economy

  7. System Forecast Approach Sales & Customers Customer Class and End-Use Energy Forecast Weather Conditions Economic Drivers Residential and Commercial Sales Forecasted using a SAE Modeling Framework Electric Prices Structural Changes DSM System Energy and Peak Forecast System Hourly Load Peak-Day Weather End-Use CP Factors System Hourly Load Forecast System Profile Solar Load and EVs Demand Response

  8. SAE Modeling Framework

  9. Key Forecast Drivers • Economic activity and population growth • Moody Analytics Vermont economic forecast • Weather conditions • Twenty-year normal HDD and CDD • Price projections • End-Use Intensity Projections • Saturation forecast – Vermont appliance saturation surveys • Baseline efficiency projections – 2013 AEO • Intensity adjustments for state efficiency programs • Residential and commercial solar net metering system market penetration • Electric vehicles • ???

  10. Preliminary Vermont Energy and Demand Forecast • Revenue class sales and customer data through March 2013 • Moody Analytics June 2013 economic forecast for Vermont • 2012 end-use intensity projections • Reflects the 2012 VEIC efficiency savings projections • No solar load adjustment • No price impacts Used as a basis for developing a No DSM Forecast

  11. Baseline End-use intensity trends • End-use intensity trends reflect both saturation and average stock efficiency improvements • Current intensity trends reflect KEMA state saturation survey, EIA New England forecasts, and past BED appliance saturation surveys

  12. DSM Adjusted end-Use intensities • Develop baseline end-use sales forecast from SAE models • Calculate adjusted end-use sales forecasts for DSM savings projections • Residential: assume 75% is embedded in the baseline forecast • Commercial: assume 50% is embedded in the baseline forecast • Adjust end-use intensity forecasts to reflect DSM savings adjustments DSM embedded assumptions based on calibration to actual sales

  13. DSM Adjusted water heating Intensity Baseline Adjusted

  14. Total End-Use Intensity projections Baseline Adjusted Residential Baseline Adjusted Commercial

  15. Residential average Use comparison New England Vermont (with DSM)

  16. Developing the “NO DSM” Forecast No DSM No DSM Commercial Residential • Adjust end-use intensities upwards – add back in 100% of projected DSM savings • Assume no future DSM is embedded in the baseline forecast

  17. Residential average use No DSM With DSM

  18. Commercial average use No DSM With DSM

  19. Vermont Energy Requirements No DSM With DSM

  20. Vermont Peak Demand No DSM With DSM By 2023, DSM programs reduce peak demand by 119 MW (10%)

  21. Updating end-use Saturation estimates • Incorporate new appliance saturation survey information • NMR 2012 Residential Home Survey (Reported February 2013) • Also have the KEMA 2005 survey, earlier BED survey, and the EIA estimates for New England • We were hoping to connect the dots between the KEMA and NMR survey • Problem: The two survey points are not all that consistent

  22. Electric Heat KEMA NMR Surveys show consistently lower shares than that implied by the billing data

  23. electric Heat Customer share and use There appears to be significant electric heating

  24. Secondary electric heat NMR KEMA Could be people with electric heat consider it a back-up source

  25. Central air conditioning NMR KEMA 2 out of 3 sources say CAC saturation is higher

  26. Room Air Conditioning NMR KEMA Reported RAC saturation is about the same but not consistent with the BED saturation growth

  27. Electric water heating KEMA NMR KEMA and NMR diverge from New England water heating saturation trends

  28. Second Refrigerators KEMA NMR NMR saturation is more consistent with New England

  29. Freezers KEMA NMR The two surveys imply an unlikely sharp decline in the number of freezers

  30. Clothes washers KEMA NMR

  31. Dryers KEMA NMR NMR survey closer to that reported by EIA

  32. Dish washers KEMA NMR KEMA survey closer to that reported by EIA

  33. PV Market Penetration Share of customers with PV systems (GMP solar customer data) • Though still relatively small net metering (particular residential and commercial photovoltaic systems) has been growing quickly Residential Commercial Through 2012

  34. Factors driving net Metering Penetrati0n • Federal Investment Incentives – Through 2017 • 30% of system installed cost • State Investment Incentives • Was $0.45 per watt now $0.25 per watt • On a 5 kW system incentive drops from $2,250 to $1,250 • But federal absolute dollar credit will offset some of this • High avoided electric rates • average residential rate $0.16 per kWh • Generous buy-back rate • Credit equal to $0.20 per kWh (retail rate plus $0.04 per kWh)

  35. Solar load is happening where State incentives are significant

  36. Should see strong PV Market Growth Assumes 10% annual decline in system cost Assumes continuation of federal tax credit Simple Payback

  37. residential simple Payback Model

  38. Residential pV Market Penetration fcst Base Case No Federal Tax Credit No State or Federal Tax Credit

  39. Residential and solar customer Forecast

  40. Residential Generation and Use Billed AverageUse 6,680 kWh per year Generated 6,700 kWh per year • Average kWh per month Own Use 5,200 kWh per year

  41. Residential solar Load Forecast Capacity estimated using a 0.17 load factor, assume average system size = 4.5 Mw