An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. DESIGN AND CONSTRUCTION OF AN INDUCTION FURNACE(COOLING SYSTEM) Presented by MG THANT ZIN WIN Roll No: Ph.D-M-7 Supervisors : Dr Mi Sanda Mon Daw Khin War Oo 20th Seminar 10.11.2004

  2. Net Positive Suction Head Available (NPSHA) It depends upon the elevation or pressure of the suction supply friction in the suction line, attitude of the installation, and the vapor pressure of the liquid being pumped. hsp = static pressure head (absolute) applied to the fluid, m or ft hs = elevation difference from the level of fluid in the water tank to the pump inlet, m or ft If pump is below water tank, hs is positive. If pump is above water tank, hs is negative. hf = fraction loss in suction piping, m or ft hvp = vapor pressure of the liquid at the pumping temperature in meters or feet of the liquid

  3. Net Positive Suction Head Required (NPSHR) • It varies with flow, temperature and attitude have no effect. N = required motor speed, rpm Q = the water flow rate of pump, m3/min

  4. Checking for Suction Performance of Cooling System of UNIDO Induction Furnace Pump GI Pipe 15.6972m Water tank PVC Pipe 3.6576m Fig – Suction line arrangement

  5. Pump Ball valve 0.2032 m Foot valve Water cooling tank Fig – Side view of water cooling tank with pumping station Known data : Capacity to be pumped 0.69 m3/min Required motor speed 2900 rpm Size of all pipes, valves and fittings

  6. Determine the Fraction Losses for GI Pipe where, From Moody diagram, f = 0.0195

  7. where,

  8. Determine the Fraction Losses for PVC Pipe where, From Moody diagram, for smooth pipe f = 0.0139

  9. where,

  10. Absolute pressure = Atmospheric pressure - gage pressure = Atmospheric pressure – water tank Pabs= 101.25 kPa 0 where,

  11. Fig – Vapor pressure of water

  12. Finally, It may be suitable to use or select a centrifugal pump for cooling system of UNIDO Induction Furnace.

  13. THANK YOU