NuMI Radiation and Environmental Protection

NuMI Radiation and Environmental Protection. NBI2006 - 6th International workshop on Neutrino Beams and Instrumentation September 5-9, 2006 Mike Martens Fermilab. Environmental Concerns. Groundwater Protection NuMI tunnel is in an Aquifer Surface Water

haruki
Download Presentation

NuMI Radiation and Environmental Protection

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. NuMI Radiation and Environmental Protection NBI2006 - 6th International workshop on Neutrino Beams and Instrumentation September 5-9, 2006 Mike Martens Fermilab

  2. Environmental Concerns • Groundwater Protection • NuMI tunnel is in an Aquifer • Surface Water • Sump water is pumped from NuMI tunnel to the surface • Air Emissions • Air from Target Chase and Absorber region are vented to the surface • This is done after a long passage through the decay pipe to reduce the radioactivity levels of short lived radionuclides • Component Activation • Personnel Protection, Hot Handling, etc. • All of this is important and has our attention • Was expected during the design phase of NuMI • Being re-evaluated for the SNuMI upgrades • Much of this is “Standard Stuff” for  beamlines • I will say a few words on Tritium Production since this became an important topic as we started NuMI operations

  3. Chronology • Last November detectable levels of tritium were measured in the Indian Creek discharge from the Fermilab. • First observation ever of tritium in any water flowing off our site • Indian Creek flows through the Savannah subdivision • Measured 3.3 pCi/ml (site boundary) • DOE regulatory limit for surface water is 2000 pCi/ml • (20 pCi/ml for drinking water) • Task Force established and mitigation implemented • Currently measurements are all below the detection limit of < 1 pCi/ml NuMI Indian Creek Savannah Subdivision

  4. Indian Creek Measurements • The immediate source of tritium in Indian Creek in November was identified as water leaking into the creek from a damaged pipe connecting Main Injector ponds C and D. • The pipe was pumped out and blocked off: Currently under repair http://www.fnal.gov/pub/about/community/chart.html

  5. NuMI as Source of Tritium • Water flowing into the NuMI enclosure is collected in the MINOS cavern and pumped to the surface • ~175 gallons per minute • Design protects the aquifer by bringing tritiated water to the surface Sump discharge and holding tank

  6. Target Chase Cooling Chiller Concrete Shielding Blocks In practice some air exchanged between target chase and target hall Concrete Walls Cool air flows upstream on outside of pile, then downstream in the chase Target Pile

  7. Chiller Condensate SR-3 EAV-2 EAV-3 Target Hall Chiller Absorber Hall Decay Passage Target Chase Drain To Sump Chiller Condensate

  8. Chiller Condensate Collection Chiller Condensate Tank

  9. Condensate Collection

  10. Dehumidification Dry Air Humid Air SR-3 EAV-2 EAV-3 Target Hall Absorber Hall Decay Passage Target Chase Drain To Sump Desiccant Unit

  11. Desiccant Units

  12. Dehumidification Results

  13. Summary of Mitigation • As of November 2005 the major contributor to tritium within our surface waters is water being pumped out of the NuMI enclosure. • 175 gpm @ ~30 pCi/ml in November • Result: Essentially all Fermilab surface waters are in 1-5 pCi/ml range • In December 2005 we identified a major contributor within the enclosure: condensate from an air conditioning unit in the target area. • Represents ~60% of the November concentration. • Condensate is being collected and disposed (1-2 gph). • Result: Holding tank levels between 10-25 pCi/ml. • In March 2006 installed de-humidifers in the target hall • Prevents tritiated humidity from passing through the decay hall and mixing with the tunnel water • Result: Holding tank levels are between 5-6 pCi/ml