250 likes | 375 Views
Technical update. Service meeting Codroipo 13/14-06-05. IDROWALL Range. NEW. Wall fan-coil. Range from 1,3 up to 2,5 kW. Index. COMPARISON OLD NEW REATURES ACCESSORIES ELECTRONIC FUNCTIONS MASTER SLAVE. IDROWALL. IDROWALL. 4 models. 3 models.
E N D
Technical update Service meeting Codroipo 13/14-06-05
IDROWALL Range NEW Wall fan-coil Range from 1,3 up to 2,5 kW
Index • COMPARISON OLD NEW • REATURES • ACCESSORIES • ELECTRONIC • FUNCTIONS • MASTER SLAVE
IDROWALL IDROWALL 4 models 3 models Cooling capacity 1,02 ÷ 3,4 Cooling capacity 1,32 ÷ 2,48 Features External valve in the frame Work with water temperature till 55°C Features 2 Versions: - With inside valve - Without valve Work with water temperature till 70°C Microtech electrical board Carel electrical board master-slave function Dimensions Models 10-20-30: 800x280x200 mm Models 40: 950x280x155 mm Dimensions Models 22-33-44: 950x280x155 mm Accessories Remote control Wall control panel Wall recessed box with valve Wall recessed box with electronic 3 way valve Accessories New infrared remote control New wall control panel New wall recessed box Comparison OLD - NEW NEW OLD
Comparison OLD-NEW • Cooling power Acqua: 7/12°C Aria: 27°C B.S. 19°C B.U. • 3 modelli
Comparison OLD-NEW • Thermal power Acqua: 70/60°C Aria: 20°C B.S. Acqua: 45°C / portata come in raffredd. Aria: 20°C B.S. • 3 modelli
Features – application field t °C = inlet water temperature U.R.% = ambient air relative humidity
features – Version with electrovalve. Air vent valve easely accessible Water discharge valve on the coil
NEW Supplyed loose accessories KPCM – new control board with 11 keys
Accessori forniti separatamente KTCM – LCD infra-red remote control NEW
Supplyed loose accessories • KVDF – wall recessed box for the predisposition of the system side piping before the installation,completed of : • Quick connection with ball valve • Flexible connection piping NEW
Electrical board Lay-Out Valve Fan Serial Flap ST1 ST2 Hall Riceiver
Clamps • Idrowall 22 - 44 • SCR = remote On-Off • KPCM = control board • C = aux contact • EIR = remote summer winter • SIC = remote safety • ECO = energy save • Serial connection • Available soon KPCM Idrowall 10 - 40 SCR = remote On-Off KPAN = control board CKRP = aux contact RS 485 = serial connection VI = on – off valve
NEW OLD Allarmi
Funzioni • Regulation functions : • Full auto • Cool • Heat • Fan • Dry • confort functions: • Orienting/Swing (selection of the deflector position: swingin or fixed ) • Auto Fan / Fan speed (manual or authomatic ventilation) • Sleep (night climatization function) • Too cool (summer block for temperature over 18°C ) • Hot start (winter consent of minimum temperature [32; 36; 40 °C] )
Functions • Advanced functions: • Security control(il possible to subordinate the unit running to a remote control, clean contact. For example is possible to interrupt the running if a window is open with a control positioned in the window itself .) • Economy (‘’save energy’’ function. You can enable it from a DIP switch positioned in the electrical board and activate it with a clean contact in alternative of the function ‘security control’) • On/Off remote control(allows the switching on and off of the unit from a remote switch ,clean contact) • Lock function(conditioning bounded for Hotel rooms) [Full auto; Free vent ; auto mode if not SEI] New New New
Funzioni • Le funzioni avanzate: • Continuous ventilation(when the temperature set-point is reached the ventilation is forced to the lower speed) • Timer(allows 1 daily ciclic programmed switching on/off of the unit) • Probe in / Probe out(the ambient tmeperature can be felt by an inside probe (PROBE IN) or by a probe fixed in the unit (PROBE OUT)). • Memory(after a black-out ,the unit will restart in the way that had immediatly before the supply black out). New
FUNZIONI • Periodical ventilation • activ in cool/dry heat • Not active with probe in • super-periodic ventilation at the start of the full-auto function (shorted after the remotation of the inside probe) • Is possible to read and change the parameters through the KPCM • The infrared remote control has to be configured at the first start up New New New New
Configurazione telecomando • Page 9 of the user manual
CONTROLLO A FILO o TELECOMANDO New Till a max N° of 5 slave units Master - SlaveFunction MASTER SLAVE SLAVE SLAVE MAIN FEATURES • “broadcasting”logic:the units are all working in the same zone making exactly the same functions set in the MASTER • In the sign of continuity:easy electric connection between the control board of the single unit • More flexible:new for IDROWALL
Master-Slave function • Master-Slave net with remote control: connect the electrical heater (rpower 1,2 Kohm 0,5W) • The electronic board self-configures itself as master for the presence of the panel or of the electrical heater in the first unit Con pannellino si può scegliere Probe in/out • Diagnostic on Slave only with the LED • Inlets Slave ECO, EIR, Lock Func., are disactivated • SCR Master: blocks all the chain • SCR Slave: Blocks only the specific unit • SIC:Blocks only the specific unit New New