1 / 7

Telenor Tier 3 Data Center April 2011

Telenor Tier 3 Data Center April 2011. About Telenor Tier 3 Data Center. Telenor built it´s own Data Centar in accordance with the latest industrial standards. Telehousing services in Telenor Data Center are available to customers from January 2011.

kmcdonald
Download Presentation

Telenor Tier 3 Data Center April 2011

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Telenor Tier 3 Data CenterApril 2011

  2. About Telenor Tier 3 Data Center • Telenor built it´s own Data Centar in accordance with the latest industrial standards. • Telehousing services in Telenor Data Center are available to customers from January 2011. • Telenor´s Telehousing services are tailored to the needs of large companies, financial institutions, ISP´s, content providers and others for whom the service availability and the equipment and IT systems security are of primary business importance. Standards • Telenor Group • Local Standards (SRPS) • RATEL regulations • ASHRAE recommendations • Fire Brigade Regulations • TIA-942 (Telecommunications Industry Association) • Site space and layout • Cabling infrastructure • Tiered reliability • Environmental considerations

  3. Data Center Tiers • Multi-million dollar business • 99,995% availability • Annual downtime due to site is 0,04 hours • Two independent utility paths • Fully redundant (2N+1) • Able to sustain 96-hour power outage Fault Tolerant Site Infrastruct. • Large company • 99,982% availability • Annual downtime due to site is 1,6 hours • Multiple power and cooling paths • Fault tolerant (N+1) • Able to sustain 72-hour power outage Concurrently Maintainable Site Infrastruct. • Medium-size business • 99,749% availability • Annual downtime due to site is 22,0 hours • Single path of power and cooling • Some redundancy in power and cooling system Redundant Site Infrastuct. Capacity Components • Typically small business • 99,671% availability • Annual downtime due to site is 28,8 hours • Single path of power and cooling • No redundant components Basic Site Infrastruct.

  4. Telenor Tier 3 Data Center One of the most advanced Data Centers in SEE region • Separate stand alone facility with 2.600m2 space with full N+1 redundancy on all mechanical, electrical and connectivity infrastructure • Technical space on three floors • Loading/delivery docking area • Freight elevator, capacity 2,500 kg • Built in the 2009th with the flat roof and without windows • Controlled access to facility via single entrance • More emergency exits Accommodation of user´s telecommunication equipment • Cabinets/racks - Pre-installed standard racks (600x1.070x42U) • Cage – optional • Data room – optional • Space with necessary infrastructure for collocation of storage racks • Web portal – real-time monitoring of all relevant service parameters • Hands & Eyes services • Anti-static floor • Raised floor, construction height 65cm, maximum load 1500 Kg/m2 • Structured cabling (Power cabling under raised floor, Data cabling overhead)

  5. Telenor Tier 3 Data Center Power supply • Two independent 10kV underground utility feeders, from different utility transformer substations 110/10 kV • Mains: 3x400/230V AC, 50 Hz (Dry transformers 10/0.4 kV) • Dual power feeds, possibility of maintenance one power branch without affecting the functionality of the system • Redundant UPS systems - 2x(n+1) with total power 2x(3x400kVA), 2h autonomy • Diesel generator backup for all critical loads, 72 hours autonomy (at full capacity) before refueling, 2N redundant • Dual UPS power feed for each rack, fused by 1x32A+1x32A • Power supply system with overload protection and protection discrimination (selectivity) of circuit breakers Air conditioning /Cooling • Redundant air-conditioning, free-cooling chillers, indoor CRAC (Computer Room Air Conditioner) units, (N+1) redundancy • Air-conditioning system separated from the rest of the facility • Environmental conditions control system maintaining constant levels of temperature (22°C - 26°C (24 ± 2°C)) and humidity (40-60% (50 ± 10%)) • Concurrently maintainable air-conditioning and power supply system without threat to availability of the telehousing services

  6. Telenor Tier 3 Data Center Security • Physical security system with 24x7x365 access control • Video surveillance of the entire facility providing archive recordings to 3 months • Monitoring elements are connected to alarm systems. All doors are built in accordance with • WK standard • Electronic access control system over ID cards and PIN codes –access allowed only to pre-defined areas, with continual monitoring • The security fence around the building of 2.2m hight is connected with concrete bollards. • Complete site perimeter is secured by IC barriers integrated in existing alarm system. Fire Detection and Suppression • Zoned fire detection system utilising VESDA (Very Early Smoke Detection Aspirating) • Zoned fire suppression system (IG-55) • Fire retarding walls (F90) • Monitoring elements are connected to alarm systems. • Smoke detectors are placed on the ceiling and under the raised floor; functioning in terms of power failor • The closest fire brigade is 12 minutes away from the facility

  7. Telenor Tier 3 Data Center Communication infrastructure • ~ 2700 km of fiber optic network in Serbia, Hungary and Bulgaria • Multiple connections with local Internet providers and operators • BGP (Border Gateway Protocol) over several Tier1 ISP`s • DWDM capacity of 40 wavelengths, 10 Gbps per wavelength (expandable up to 80 wavelengths with 40 Gbps per wavelength) • Completely redundant networking equipment with dual power supplies and spare units for all critical equipment • Telenor Serbia is building the best data (All IP) network in Serbia • Services (Dark fiber, Wavelength, SDH capacities, Ethernet solutions) Monitoring • All systems and network are monitored by Telenor`s NOC 24/7/365 • Trouble ticketing system

More Related