Rx Monitoring Services, Inc.

Rx Monitoring Services, Inc. How to read the RxMS site reports. RxMS Equipment. EPA-1500 & EPA1000 3 Phase Voltage (10 Channels) Ph-Ph, Ph-N, Ph-G, N-G 5 Channels Current DC Voltage (EPA1000 only) Temperature & Humidity Dust Particle Indicator Download via USB (1500 only) or Ship Back

kordell
Download Presentation

Rx Monitoring Services, Inc.

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Rx Monitoring Services, Inc. How to read the RxMS site reports

  2. RxMS Equipment • EPA-1500 & EPA1000 • 3 Phase Voltage (10 Channels) • Ph-Ph, Ph-N, Ph-G, N-G • 5 Channels Current • DC Voltage (EPA1000 only) • Temperature & Humidity • Dust Particle Indicator • Download via USB (1500 only) or Ship Back • Z-Brick • Add-on to measure Impedance

  3. New EPA 1500 Front Panel Software • Shows Phase-Phase voltages L1-L2/L1-L3/L2-L3 (unless only L1 phase is connected – then it reads Phase-to-Ground) • Phase current L1/L2/L3 • Temperature • Humidity • Date • Time

  4. Two types of Z-Bricks Stand alone Z-Brick Z-Brick used with EPA1000 • Date is saved in No internal memory internal memory Stores the data on EPA1000 • Can be done very early in installation

  5. RxMS Report Format • Color Document • Delivered Electronically via E-mail • You will be sent a password protected link to download the report from our server • Or attached Acrobat Format (PDF) • Free Adobe Acrobat Reader http://www.adobe.com/products/acrobat/readstep.html • 100 – 200 Pages (500 – 1,500 kbyte) • Length and Size Depends Upon: • Days Surveyed • Number of Events

  6. Bookmarks • Assist in Report Navigation • Automatically take you to Selected Section Click this button if Bookmarks are not shown when the file is opened!

  7. RxMS Tech NotesExplains what was found in the report and a prescribes a solution

  8. RxMS Reports: Title Page

  9. RxMS Reports:Title Page • Site Information

  10. Site Information

  11. RxMS Reports: Title Page • Site Information • Power Quality Disturbance Summary

  12. Power QualityDisturbance Summary Expert Analysis Manufacturer’s Specs Rx Rating Sags, Surges, Impulses, And Power Failures Per Channel

  13. RxMS Reports:Title Page • Site Information • Power Quality Disturbance Summary • Logging Summary

  14. Power QualityDisturbance Summary Manufacturer’s Specs Expert Analysis Rx Rating Actual Site Conditions Equipment Requirements

  15. RxMS Reports:Title Page • Site Information • Power Quality Disturbance Summary • Logging Summary • Rx Ratings

  16. Rx Ratings • Good • Meets Manufacturer’s Specifications • Minor • Damage Unlikely. Disruption is Possible. • Moderate • Damage is Possible. Disruption is Likely. • Severe • Damage is Likely. Disruption is Highly Likely. • Safety • NEC Violation or other Safety Hazard

  17. RxMS Reports:Event Log • Summary of Disturbances • Start / Stop • Power On / Power Failure • Sags / Surges • Impulses • Ground current surge • Comments

  18. Detail Event LogStart and System Power-Up Start: Monitoring Begins System Power-Up: EPA-1500 Power Applied Date and Time Stamp

  19. Detail Event LogHF Transients (Impulses) UniqueEvent ID # Channel P1: Peak Voltage Positive or Negative P2: Impulse Duration Micro-seconds P3: Phase Angle On 60 Hz Sinewave Date and Time Stamp (to nearest 1 msec)

  20. Detail Event LogSags and Surges UniqueEvent ID # Channel P1: RMS Voltage Minimum or Maximum P2: Duration Milli-seconds P3: Nominal At the time of event Date and Time Stamp (to nearest 1 msec)

  21. RxMS Reports:Initial Waveforms / Snapshot • EPA-1500 Takes a Snapshot • 5 Minutes after the unit is plugged in • Once a Day (Default is 10:00 AM) • Voltage Waveforms Recorded • Phase-Phase, Phase-Neutral • Phase-Ground, Neutral-Ground • Current Waveforms Recorded • Phases, Neutral, Ground • Harmonics are Calculated

  22. RxMS Reports: RMS Voltage and Current Logs • AC Voltages Logged: 10 Channels • Phase-Phase, Phase-Neutral • Phase-Ground, Neutral-Ground • AC Currents Logged: 5 Channels • Phases, Neutral, Ground • One cycle resolution, True RMS • Slow moving events will not create a sag • Minimum / Maximum / Average • Five Minute Window (Default Setting)

  23. 24 Hour Window Scaled for Best Illustration Color Coded Red: Minimum Black: Average Blue: Maximum Daily Trends Patterns Sags / Surges >5% nominal Voltage Log

  24. Current Log • 24 Hour Window • Scaled for Best Illustration • Color Coded • Red: Minimum • Black: Average • Blue: Maximum • Daily Trends • Patterns • Equipment Use

  25. RxMS Reports: Sag & Surge Summary Graph • Plot of Voltage Sag & Surge Events • Vertical Scale • Sag or Surge as a Percent of Nominal • Horizontal Scale • Duration of Event in Milliseconds • Color Coded for Rx Rating • Red Severe • Yellow Moderate • Blue Minor • Green Good • Based on Nominal Voltage • Floats over time

  26. RxMS Reports: Impulse vs. Time Summary Graph • Plot of Voltage Impulses vs. Time of Occurrence • Vertical Scale: Impulse Voltage • Additive / Subtractive Relative to Sine Wave • Horizontal Scale: Time of Occurrence • Survey Duration is Full Scale • Useful in Recognizing Patterns • Time of Day • Primarily Additive or Subtractive • Caused by Equipment Use or Start-up

  27. RxMS Reports: Impulse vs. Duration Summary Graph • Plot of Impulse Peak Voltage vs. Duration • Vertical Scale: Peak Voltage • Horizontal Scale: Duration of Impulse • Microseconds • Color Coded for Rx Rating • Red Severe • Yellow Moderate • Blue Minor • Green Good • Each Channel Displayed Separately • Identifies Severity of Impulses

  28. RxMS Reports: Swell Waveform: Sag or Surge • Triggered on Sag or Surge • Active for Duration of Sag / Surge • Up to 200 msec • EPA Records All Voltage and Current Channels • RxMS Reports Most Useful ChannelsExamples: • Three Voltage Phases • One Phase Voltage and Current • Phase-Neutral vs. Phase-Ground (One Phase) • Neutral-Ground Voltage and Currents

  29. Impulse Waveform • High Frequency • Flash Converter

  30. Impulse Waveform • High Frequency • Flash Converter • AC Voltage • 256 Samples / Cycle • 2 Cycles Shown

  31. Impulse Waveform • High Frequency • Flash Converter • AC Voltage • 256 Samples / Cycle • 2 Cycles Shown • AC Current • 2 Cycles Shown • Assist in Determining if Load-Generated

  32. Temperature & Humidity • Similar to RMS Logs • 24 Hour Window • Identify Trends • Absolute Value • Rate of Change

  33. Basic Site information as to where the Rx Monitor was connected and what channels you connected. Also include why you are monitoring

  34. Detailed information as to when the monitor was installed and any system issues (date/time)