Oregon Joint Use Violation Examples. Stump The Panel. Question 1. Question 2. Question 3. Question 4. Question 5. Question 6. Question 7. Question 8. Question 9. Question 10. Question 1 Answer. Obstruction on pole creates climbing hazard. 217A4. Question 2 Answer.

mahon
Download Presentation

Oregon Joint Use Violation Examples

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Oregon Joint Use Violation Examples Stump The Panel

  2. Question 1

  3. Question 2

  4. Question 3

  5. Question 4

  6. Question 5

  7. Question 6

  8. Question 7

  9. Question 8

  10. Question 9

  11. Question 10

  12. Question 1 Answer Obstruction on pole creates climbing hazard. 217A4

  13. Question 2 Answer “Boxed” pole creates climbing hazard. 213, 236, 237, 238

  14. Question 3 Answer Inadequate vertical clearance between Power Company primary riser and communication cable. 239G

  15. Question 4 Answer Inadequate vertical clearance between power supply conductor and communication cable. Deteriorated pole hardware, standoff bracket rusted and broken.. 235C1, 214A

  16. Question 5 Answer Inadequate vertical clearance between power supply conductor and deck. 234C3d

  17. Question 6 Answer Inadequate vertical clearance between communication cable and roadway. 232, Table 232-1

  18. Question 7 Answer Inadequate mid-span clearance between power supply conductor and communication cable. 235C2b(1)a

  19. Question 8 Answer Fire hydrant has inadequate horizontal clearance from anchor guy. Down guy in pedestrian area does not have substantial and conspicuous marker. 231A, 217C

  20. Question 9 Answer Service conductor has inadequate vertical clearance over roof. 234C3d

  21. Question 10 Answer Sign has inadequate horizontal clearance from communications cables at mid-span. 234C, Figure 234-1(b), Table 234-1