Oregon Joint Use Violation Examples Stump The Panel
Question 1 Answer Obstruction on pole creates climbing hazard. 217A4
Question 2 Answer “Boxed” pole creates climbing hazard. 213, 236, 237, 238
Question 3 Answer Inadequate vertical clearance between Power Company primary riser and communication cable. 239G
Question 4 Answer Inadequate vertical clearance between power supply conductor and communication cable. Deteriorated pole hardware, standoff bracket rusted and broken.. 235C1, 214A
Question 5 Answer Inadequate vertical clearance between power supply conductor and deck. 234C3d
Question 6 Answer Inadequate vertical clearance between communication cable and roadway. 232, Table 232-1
Question 7 Answer Inadequate mid-span clearance between power supply conductor and communication cable. 235C2b(1)a
Question 8 Answer Fire hydrant has inadequate horizontal clearance from anchor guy. Down guy in pedestrian area does not have substantial and conspicuous marker. 231A, 217C
Question 9 Answer Service conductor has inadequate vertical clearance over roof. 234C3d
Question 10 Answer Sign has inadequate horizontal clearance from communications cables at mid-span. 234C, Figure 234-1(b), Table 234-1