PowerLogic EGX300. Integrated gateway-server for entry-level system monitoring. Outline. Two parts for training Sales/Market Information Product Information. Sales/Marketing Information Part I. Entry Range Monitoring – Why?. Not every customer needs ION Enterprise or EEM
E N D
PowerLogic EGX300 Integrated gateway-server for entry-level system monitoring
Outline • Two parts for training • Sales/Market Information • Product Information
Entry Range Monitoring – Why? • Not every customer needs ION Enterprise or EEM • Some just want the basics • Keep it simple • Not every sales person can sell a full function power monitoring system • Requires a lot of training • Long sales cycle • Keep it simple • Use entry range monitoring as a way to boost power meter sales
EGX300 • An Integrated Gateway-server? • What’s that? • Let’s see…..
View device data through a simple browser – no software needed EGX300 web page Trend plots Data log files EGX100 Pull information into web pages from other PowerLogic gateways (PM8ECC, EGX100) EGX300 ION 6200 PM800 Micrologic Sepam PowerLogic EGX300Integrated gateway-server • Use your existing Ethernet network to access basic electrical system data • View data with only a web browser, no power monitoring software needed • Log data onboard the EGX300 for historical system analysis
Benefits • Get a view of your complete electrical system including: • Meters • Circuit breaker control units • Protective relays • Motor controllers • Drives • Operating on an existing Ethernet network, the PowerLogic EGX300: • Accesses multiple Ethernet devices and gateways across the network and logs data from connected devices • Simple Ethernet connection with minimal configuration required • Offers high performance and reliable communication • Helps lower installation costs • Provides easy system expansion: Dynamic device additions • Is compliant with industry standards (UL, CSA, FCC, CE)
Benefits • View real time data using only a web browser • Analyse basic data from your electrical distribution system for cost allocation and trending reports • Use the embedded web page creation tool to customise your system data views and add additional devices • Detect serial devices with device Autodiscovery tool
Workstations Modbus TCP Web browser PLC Modbus TCP Master Modbus TCP/IP Filtering Feature controls access to critical devices • Example: • PLC allowed access • One workstation not allowed access • Level of access configurable for • read-only or full access Modbus serial line critical control devices Benefits • Functions as a gateway from Ethernet to serial line devices • Connects up to 64 devices per gateway • Offers field upgradeable firmware • Features Modbus TCP/IP address filtering • Features 512 Mb for onboard data logging
EGX300 user interface – per device View real time data per individual device
EGX300 user interface – per device View logged data per device
EGX300 user interface – summary views Overview of all connected devices Overview of all connected devices Overview of load current of all devices Overview of demand current all devices
EGX300 and EGX400 • Expected Sell Gate: March 2009 • The EGX300 will replace the EGX400 • Expected to have a lower CCV, but sell for similar market price • Easier to set up - no additional web page programming software needed for standard web pages • Same foot print as EGX100 • Power over Ethernet control power option for easy installation • But the EGX400 has 2 serial ports and has both fiber & copper Ethernet connections • The EGX300 can connect to devices via Ethernet and via other gateways, which the EGX400 can not • An EGX300 + an EGX100 should have about the same cost, or lower, than an EGX400 • Very few customers actually bring fiber to the devices or gateways, but if needed, third party adapters are available
Minimum System Requirements Although there is NO need to install any software, the computer accessing EGX300 will need to have a browser installed. We support: • Microsoft Internet Explorer 6.0 or higher
Physical Characteristic: Ethernet • Ethernet • 10/100BaseTx • Media Type: • 10T/100Tx Auto • 10BaseT-HD • 10BaseT-FD • 100BaseTx-HD • 100BaseTx-FD • Framing: Ethernet II & 802.3 (SNAP) • IP Parameters: Address, Subnet Mask, & Default Gateway • Protocols: HTTP, ModbusTCP/IP, FTP, SNMP (MIB II), SNTP, SMTP • Connector: RJ45 • Pinout: Industry standard • Supports 48 concurrent ModbusTCP/IP connections • Duplicate IP address detection (FDR basic)
Physical Characteristic: Serial • Serial Line • All lines optically isolated • Physical interface: RS485 4-wire, RS485 2-wire, RS232 • Protocols: ModbusRTU, POWERLOGIC (SY/MAX), ModbusASCII, Jbus • Baud: 2400–38400bps (RS485); 2400-57600bps (RS232 ASCII) • Parity: None, Even, & Odd • Response timeout: 0.1 to 10 seconds (default = 3 seconds) • Connector: • RS485 5 position plugable screw-terminal • RS232 RJ45 • Pinout: • RS232 Industry standard EIA561 for RJ45 • Note: EGX300 is internally connected: no need to physically connect the EGX300 for two wire mode.
Physical Characteristic: Exterior RJ45 Ethernet port (IEEE802.3af) Control power: 24 Vdc or Power-over-Ethernet (PoE) LED indicator for power & status Recessed reset button LED indicators for Ethernet and serial communications
Physical Characteristic: Exterior RS485 serial port Bias, Termination, and 2-wire / 4-wire jumper switches RS232 serial port (RJ45 connector)
Transparent Ready {TRe} • Embedded web server provides real-time tabular data views for all supported device types • Single Device Basic Readings • Summary Device Views • Circuit Summary • Load Current Summary • Demand Current Summary • Power Summary • Energy Summary • Advanced users can create custom web views
TRe: Setup • Ethernet & TCP/IP • Serial Port • Remote Device Connections • Device List • Device Logging • Device Log Export • Date and Time • SNMP Parameters • Modbus TCP/IP Filtering • Documentation Links • User Accounts • Web Page Access • Preferences
TRe: Setup => Auto Discovery • EGX300 features the ability to “Auto Discover” devices in its daisy chain • The EGX300 will not find remote devices; the user will need to define a locate address and remote address • Look under the device list and scroll to the bottom of the page • The user needs to setup the right baud rate and settings for this ability to work. Press to Discover
TRe: Setup => Data Export • Users have three options • Disable • Export via FTP • Export via E-mail • Users will have to setup logging first before choosing either option of FTP or E-mail • Uses can now only send “incremental” data versus ALL data with the EGX400
TRe: Monitor => Single Device Page • The EGX300 has the ability to display real time readings from devices. • The devices can be selected individually • All data displayed has been scaled and set at factory • Any unique requests will have to be done as a custom page
TRe: Monitor => Summary Pages Summary Pages are standard with TRe level 2 support. Users can select ALL or individual pages to be displayed the summary pages. Pages to be displayed: • Circuit Summary • Load Current • Demand Current • Power • Energy
Embedded web server provides user selectable topics per device Provides logging function to store data from serial devices on 5, 15, 30, or 60 minute intervals Stores up to 152 days (60 minute interval) of recorded readings for up to 32 connected serial devices Embedded web server provides a graphical view of stored data logs Provides Simple Mail Transfer Protocol (SMTP) to E-mail stored device data logs on user defined intervals Provides File Transfer Protocol (FTP) server to access device data logs Provides File Transfer Protocol (FTP) client to send device data logs TRe: Monitoring => Logging
TRe: Monitoring => Custom Pages • EGX300 will allow users to transfer their own custom pages • Custom pages will allow users to have the flexibility to create their own custom solution
TRe: Documentation • As part of TRe, users can transfer documentation or create documentation links • Users can store up to 512 Mb • The documentation can link to other devices that have web server capabilities
Control • On the Control page, users can reset the values of their individual devices.
Diagnostic • Users can: • Look at stats for the EGX300 • Read devices on this page • Check Communication Connection • The stats information will be used by design and tech support to analyze the system situation
Diagnostic: Accumulative Connections • Users can click accumulative connections and displayed previous connections • This is valuable in terms of security to keep track of users who have logged on before.
Maintenance Log • EGX300 provides the ability to record maintenance log files. • Typical users can record simple text information about system or challenges.
Advance Features: Remote Connection • Under Remote Device Connection, users can setup logging remotely and access devices remotely
Custom Logo Logo • Users can customize splash screen, logo, color, and favicon • Please refer to the white paper for detail specifications • This will allow Integrators to add more value for their services Splash Screen
ATS48 ATS48 ATV61 ATV71 CM100/200 CM2000 CM3000 CM4000 Enercept Energy Meter ION6200 ION7300 ION7650 Micrologic A Micrologic H Micrologic P Model98 -modbus Model98-plogic Motorlogic Plus Motorlogic Plus II MVSS/RVSS PM200 PM6-mdbus PM6-plogic PM700 PM800 Sepam 2000 Sepam Series 20 Sepam Series 40 Sepam Series 80 TeSys T Device Types for Support => Refer to next slides for level of support
Level of Support * Device not supported in ION E
Application Architecture • How to address the following situations: • Two and Four Wire Systems • Remote Access to Other Gateways
Two and Four Wire Systems Ethernet Network RS-485 (4 Wire) RS-485 (2 Wire) N < 32 Up to 64 Devices can be view by one EGX300 EGX300 can remotely connect to other gateways
Remote Access to Other Gateways Ethernet EGX100 EGX300 EGX300 can poll EGX100 through Ethernet
EGX300 will be introduced by Q1 2009 We will stop selling EGX400 by Q1 2010 We will have stock to replace existing EGX400 for warranty/repair purposes for about three years Special Substitution Use Cases (refer to following slides after): Second Serial Port Older Systems Obsolescence Plan
Second Serial Port Ethernet EGX100 EGX300 N <= 32 N <= 32 Up to 64 Devices can be viewed by one EGX300 EGX300 can remotely connect to other gateways
Legacy Systems Ethernet EGX300 CNV100 2 wire System 4 wire System
Accessory Kit • Allows configuration via RS232 serial or Ethernet port • Kit Contents • RJ45 to DB9F adapter • CAT5 Crossover cable, 3-meters (10-feet), orange • Instruction sheet • Ordering Information • TCSEAK0100 • Market Price (average) • $50 (USD)
IF USB ONLY, need converter to serial Configuration Kit
Accessories - PoE Injector (IEEE 802.3af) • Active mid-span device with universal power cord • Contents • Universal power cord (IEC-60320-C13 & IEC-60320-C14, 3-meters (10-feet) • Plug adapters for Australia, Europe, UK, USA • Instruction sheet • Ordering Information • TCSEAV0100 • Market Price (average) • $80 (USD)