E N D
1. PowerLogic PM5350High-performance multifunction power meter For entry-range metering applications
2. A high-performance multifunction power meter for the entry-range meter market
3. Offer overview
4. Applications Panel instrumentation
Energy management
Sub-billing and cost allocation
Electrical installationremote monitoring
Circuit breakermonitoring and control
5. Features Comprehensive measurement package
Energy and demand monitoring
THD/TDD & Min/Max reading
Pre-configured alarm functions for more than 30 conditions
Time stamp & internal time clock
4 digital inputs for circuit breaker status indication
2 relay outputs for circuit breaker control
Active Energy compliant with IEC62053-22 class 0.5S
Temperature range confirmed with IEC61557-12 standard
Modbus RS-485 communication port
Sealable features (V,I)
6. Easy operation Intuitive navigation with self-guided, language selectable menus
Language customization (English & simplified Chinese)
Bright, anti-glare dot matrix display (backlit)
Summary screens with multiple values
Front panel LEDs provide at-a-glance information
Orange LED (configurable) w/ 3 modes: Off, Alarm, Energy pulses
Green LED w/ 2 modes: Off, Diagnostic
Two meter reset levels (global, single parameter)
Makes commissioning faster and easier
7. Easy installation Mounting clips (2) hold the meter in place
No other tools required
Ultra compact (44mm depth)
Save valuable space
Connectable up to 480 V L-L without PTs
For installations compliant with category III
Wetted digital inputs
No needs of external power supply
Clear identification for all connections
Electrical drawings on the meter itself
Green connector for communications
Avoid mistaking it for the power supply
8. Alarming 29 standard alarms to cover most common needs
Pickup magnitude and delays
Dropout magnitude and time delays
4 unary alarms
Power up, meter reset, self-diagnostic, phase reversal
4 digital input alarms
Association alarm – D/O possible
4 levels of priority (None/Low/Med/High)
40 alarms saved in non volatile memory
Alarm counter to measure occurrence
Alarm time-stamped (1s)
9. Specifications & dimensions 15 pre-defined system configuration types for 4, 3 or 2 wires
Data Update: 1 s nominal (50/60 cycles)
Input Voltage:
20 to 690 V AC L-L
20 to 400 V AC L-N
Input Current: Through CTs
CT primary: 5A - 32767 A
CT secondary: 5 A nominal
Burden: < 0.024 VA at 9 A
AC control power: 85 - 265 V ac
DC control power: 100 - 300 V dc
Temperature:
Operating: -20 °C to +70 °C
Storage: -40 °C to +85 °C
10. Measured parameters / accuracy ratings
11. Measured parameters / accuracy ratings
12. Additional measurements Load timer with adjustable settings
With Low set up calculates total operating feeder time
Beyond nominal current settings calculates the overload time
Digital Input/Output timers
Measurement in (s) for Time On
13. Standards compliance Accuracy
Class 0.5S for active energy according to IEC 62053-22
Class 2 for reactive energy according to IEC 62053-23
IEC 61557-12
PMD /S/K70/0.5
Safety
CE as per IEC61010-1
cULus as per UL61010
Mechanical characteristics according to IEC 60529
IP degree 51 for front of meter
IP degree 30 for meter body
14. Standards compliance Electromagnetic compatibility
Electrostatic Discharge Level III (IEC 61000-4-2)
Immunity to radiated fields Level III (IEC 61000-4-3)
Immunity to fast transients Level III (IEC 61000-4-4)
Immunity to impulse waves Level III (IEC 61000-4-5)
Conducted immunity Level III (IEC 61000-4-6)
Immunity to magnetic field Level III (IEC 61000-4-8)
Immunity to voltage dips Level III (IEC 61000-4-11)
Conducted and radiated emissions CE commercial environment / FCC part 15 EN55011 Class A
Harmonics IEC 61000-3-2
Flicker emissions IEC 61000-3-3
15. Environmental friendly
RoHS Compliant
Low energy consumption
Possibility to turn off Display and backlit
Consumption typical 2 Watts
ISO 14001 plant manufactured