PowerLogic Branch Circuit Power Meter (BCPM) Need monitoring at each branch circuit?
PowerLogic BCPM The BCPM monitors a complete Power Distribution Unit (PDU) • CT strips monitor the circuits • Monitor 84 circuits with a single BCPM • Auxiliary inputs monitor the mains • Two inputs for auxiliary CTs (3-phase, 4 wire) • Auxiliary CTs ordered separately
Product Selection Guidance:Branch Current Monitor (BCM) and Branch Circuit Power Meter (BCPM) Select the BCPM for the following: • Power and energy measurements at either the branch circuit or mains level • Power, energy or current measurements on 84 branch circuits with a single device • Current, energy or power measurements on the mains • Advanced alarming capabilities, including trip alarms and user-defined thresholds for high-high, high, low and low-low alarms • Accurate measurements at low current levels, down to ¼ A, on each branch circuit • Select the BCM for the following: • Current only measurements on 42 branch circuits • Simple alarming, including high and high-high alarm levels • Need a split –core CT option
BCPM does the work of an MCM + BCM • Auxiliary (mains) metering • Auxiliary metering is equivalent that of the MCM • Two 3 phase, 4 wire auxillary inputs • 1/3 V output CTs • Auxillary CT’s ordered separately Circuit metering: • Two or four CT strips with 21 channels per strip • Max Current: 100 A CTs
BCPM Accuracy • Auxillary metering: • Current: 2% of reading from 1-10% of rated current; 1% from 10-100% of rated current • Voltage: 1% of reading from 90 to 277 V, Line to Neutral • Circuit metering: 0.25 A to 2 A2 A to 100 A Current: 3% of reading 2% of reading Energy: 4% of reading 3% of reading
New Measurements on the BCPM Key Measurements: • Energy • Real Power per phase • Power Factor • Total • Per phase • Voltage • Line to line and average L-L of 3 phases • Line to neutral and average L-N of 3 phases • Current per phase • Frequency (Phase A)
BCPM Benefits • Low cost per meter point • Monitor 84 circuits plus mains with a single BCPM • High accuracy and Dynamic Range • Monitor loads from ¼ A to 100 A • Flexible installation options • ¾” and 1” CT spacing available • Multiple strip configurations supported: Inline, Top feed, bottom feed • Enhanced alarming capability • Four configurable alarms: High, High-High, Low, Low-Low • Distinguish between a low load and zero current flow • Monitors low circuit currents down to ¼ A at 3% accuracy • Cost effective communications • Easily integrates into PowerLogic system or existing Modbus network • Three feature sets, to meet your specific needs • Basic – Current only in the circuits and mains • Intermediate – Current in the circuits, power and energy in the mains • Advanced – Power and energy in the circuits and mains
BCPM Alarming Advanced Alarming Capabilities • Multiple alarm levels, to protect your system • Low-low, low, high, high-high • Multiple alarm levels provide a warning of potential issues and allow operators to respond proactively • User defined alarm set-points • Alarms are both instantaneous and latching • Alarm counters ensure valuable historical data is maintained and potential problem areas are tracked
BCPM ApplicationsDesigned for data centers and critical power operations • The BCPM provides data center managers with information that allows them to: • Maximize uptime and avoid outages • Efficiently use existing infrastructure • Effectively plan future infrastructure needs • Simply and easily allocate costs
BCPM Application Maximize uptime and avoid outages • The BCPM advanced alarming capabilities provide alerts before a breaker trip occurs • High-high, high, low and low-low alarm levels • Set alarm levels as a percent of breaker rating to ensure advanced notice of potential issues • The BCPM uses modbus communication to easily integrate into your existing monitoring network
BCPM ApplicationEfficiently use existing infrastructure • The BCPM provides you information on energy use at the circuit level • Track infrastructure usage levels • Adjust circuit loading to distribute load • Avoid capital cost investments by maximizing usage of existing infrastructure
BCPM ApplicationEffectively plan future infrastructure needs • The BCPM can provide historical usage data, to ensure that new infrastructure projects are sized correctly • Track usage at the circuit level • Develop reports on historical usage patterns • Use reporting to accurately predict future needs • Create infrastructure projects that are appropriately • sized
BCPM ApplicationSimply and easily allocate costs • Use accurate energy consumption data to allocate costs • Track usage patterns and determine areas of potential savings • Create ongoing reporting structures to effectively manage costs
BCPM Performance and Specifications • Specifications • Update rate: 1.2 sec. per panel board, 2.4 sec for aux inputs • Sampling Frequency: 2560 Hz • Frequency: 50/60 Hz • Overload capability: 10 k AIC • Input power: 90-277 V AC • Ribbon cable support: up to 20 ft • Operating temperature range: 0º - 60º C (<95% RH, non-condensing) • Storage temp. range: -40º C to 70º C • Standards and Safety • UL 508, “open type” device • Installation category: CAT III • IEC/EN 61010 CE
Circuit Monitoring 4 CT Strips Monitor 84 Circuits Mains Monitoring (CTs Ordered Separately) Current Transducers (1/3 VAC) BCPM PCB 21 CT Strip BCPM Installation Details
BCPM Dimensions – PCB Main PCB and Bracket Dimensions
BCPM installation configurations • The BCPM supports four configurations: • Top feed • Bottom feed • Inline odd/even • Inline sequential Configuration is set by the user as a Modbus register
Single Row Sequential Single Row Odd/Even BCPM Installation Configurations
BCPM Software Support The BCPM is supported in the following software: • Initial Setup and Configuration: • ION Setup • Ongoing Monitoring and Status: • PowerLogic System Manager Software (SMS) • Device driver • Optional device type downloadable from www.powerlogic.com • Software based alarms only • No device resets • PowerLogic ION Enterprise (ION E) Full device support • ION Vista support (real-time displays) • Default OPC support • Alarm notification • Automatic onboard data uploads (as supported by device) • Default metering parameter resets (as supported by device) • Default ION Reporter support
Frequently asked questions • Can the new BCPM printed circuit board (PCB) be used to replace the old BCM PCB for a retrofit application? • No. The CT strips shipped with the BCPM are different from those used with the BCM and therefore wont work when interchanged. • What is the standard length of the ribbon cable shipped with the BCPM? • Three feet • Does the BCPM support various type breaker (single, 2 and 3 pole) in a single panel? • Yes, but this type of installation must be performed by PowerLogic Services due to the complex register mapping for this device.
CompetitionPDI BCMS and BCMS Plus - Overview • Competitor: PDI • Product: BCMS and BCMS Plus • Number of Circuits Monitored: 84 • Mains Monitoring: No, summation of branch currents only • Split-Core CT Support: Yes • Power per Panelboard: Yes (BCMS Plus Only) • Power per Branch Circuit: No • Onboard Memory/Event Log: None • Communications: Modbus over RS-485 • Software: None
Two feature sets available: BCMS and BCMS Plus BCMS measures current only BCMS Plus adds voltage measurements and power and energy at the panel board level The BCMS and BCMS Plus do not monitor the mains current. They sum the branch breaker currents to report current per panelboard. CompetitionPDI BCMS and BCMS Plus - Measurements
CompetitionPDI BCMS and BCMS Plus - continued • BCMS Plus differs from the BCPM in the following ways: • No No inputs for Mains CTs. The BCMS does not monitor mains current, but instead calculates total current by summing the individual current values for each breaker • The BCMS only reports power and demand values for the entire panel board, not per phase • The BCMS quotes 2% accuracy for measured current, but does not give an accuracy range Accuracy: Current – 2% or 0.1 Ampere, whichever is greatest • BCMS specification does not provide a range of current where it is accurate • PDI has suffered in the past from poor product quality and questionable accuracy • PDI makes hardware only and is not able to sell a system or end-to-end solution
CompetitionLiebert LDM - Overview • Competitor: Liebert • Product: LDM • Number of Circuits Monitored: 84 • Mains Monitoring: Yes • Split-Core CT Support: No • Power per Panel Mains: Yes • Power per Branch Circuit: Yes • Onboard Memory/Event Log: Yes, 128 event alarm log, FIFO • Communications: Modbus over RS-485 • Software: Configuration Tool, Monitor Tool, Liebert Sitescan Web
CompetitionLiebert LDM - Measurements Mains Measurements • Line to Neutral Voltage • Line-to-Line voltage • THD Line to Neutral Voltage • Phase Currents • Ground Current • Neutral Current • Real Power • Apparent Power • Power Factor • Percent Load/phase • THD Phase currents • Crest Factor • Phase Currents • Panel kWh • Branch Circuit Measurements • Current per breaker • Load per breaker (%) • Power per Breaker • kWh per breaker • 2- and 3-Pole Power and Energy Calculations
CompetitionEaton EMS - Overview CT Strips • Competitor: Eaton • Product: Powerware Energy Management System (EMS) • Number of Circuits Monitored: 84 • Mains Monitoring: No • Split-Core CT Support: Yes, in EMS Upgrade Kit • Power per Panelboard: Yes • Power per Branch Circuit: Yes • Onboard Memory/Event Log: No • Onboard Clock: Yes • Communications: Modbus RS-485, upgrade to Ethernet/SNMP with x-slot comm card in Eaton PDU • Software: Powerware Energy Management System (EMS) Note: Eaton EMS solution can be sold installed in an Eaton PDU, or as an upgrade kit for field installation in a third–party manufacturer’s PDU. EATON PDU, with 4 CT strips and PCB at Top Left.
CompetitionEaton EMS – Measurements Branch Circuit Measurements and Parameters • Alarm status • Ratio (in percent) of present current compared to breaker rating • Phase assignment • Current (RMS value) • Average W • Average VA • Average power factor • Threshold load (in percent) at which a warning alarm is logged • Threshold load (in percent) at which an overage alarm is logged • Kilowatt hours per month • Kilowatt hours per year • Total kilowatt hours • Maximum current logged • Maximum W logged • Maximum VA logged • Minimum power factor logged • Panel Measurements and Parameters • Alarm status (Warnings, Alarms) • Ratio (in percent) of present load compared to maximum • Average voltage • Phase with highest current • Voltage per phase • Current per phase • Ratio (in percent) of present current compared to maximum • Average kW • Average kVA • Average power factor • Number of breakers • Kilowatt hours per month • Total kilowatt hours • Maximum voltage logged • Maximum current logged • Maximum ground current logged • Maximum neutral current logged
CompetitionSatec BFM - Overview • Competitor: Satec • Product: Branch Feeder Meter (BFM) • Number of Circuits Monitored: 36 • Mains Monitoring: No • Split-Core CT Support: Yes? • Power per Branch Circuit: Yes • Onboard Memory/Event Log: Yes, 2 Mb, 1 Event Log • Onboard Clock: Yes, with one-week backup • Communications: Standard Com 1:Modbus RS-485, Optional Com 2: RS 232, RS-485, Modem, Ethernet • Software: PAS
CompetitionSatec BFM - Models and CT Options BFM 036 – No Display BFM 136 – Integrated Display 9 CT Card Single CTs 3 CT Card