Restoring Factory Configuration For Honeywell UDC3200 Controllers

This procedure restores the configuration of the instrument back to the Factory Settings per Section “Error! Reference source not found.”<br><br>ATTENTION: Restoring the factory configuration overwrites all user-entered configuration changes.<br><br>This procedure cannot be undone, it is a one-way process.<br><br>=================== Restoring Factory Configuration ===================<br><br>What to do:<br><br>1. Turn off the power to the instrument for at least five seconds.<br><br>2. Turn the power back on and simultaneously press the “SETUP” and UP keys. This must be done while “TEST DONE” is being displayed.<br><br>3. If step 2 was performed correctly, the instrument will now display “UDC” [Upper] “UPDATE” [Lower].<br><br>4. Press the Function Key. The instrument will now display “DIS” [Upper] “RESTORE” [Lower].<br><br>5. Press the UP key. The instrument will now display “CFG” [Upper] “RESTORE” [Lower].<br><br>6. Press the Function Key. The instrument will now display “DOIN” “RESTORE”<br><br>7. When the instrument finishes the restore operation, it automatically resets itself and restarts in the product mode. The instrument configuration will now be the same as it was when the instrument left the factory and all user- entered configurations since that time have been overwritten.<br><br>For more Industrial HVAC Equipment and Controls visit http://DtiCorp.com/

noblex
Download Presentation

Restoring Factory Configuration For Honeywell UDC3200 Controllers

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. DtiCorp.com - Industrial HVAC Equipment and Controls U U UD D DC C C 3 3 32 2 20 0 00 0 0 A A Ap p pp p pl l li i ic c ca a at t ti i io o on n n N N No o ot t te e e Restoring Factory Configuration Introduction This procedure restores the configuration of the instrument back to the Factory Settings per Section Error! Reference source not found.. ATTENTION: Restoring the factory configuration overwrites all user-entered configuration changes. This procedure cannot be undone, it is a one-way process. Restoring Factory Configuration Step What to do Turn off the power to the instrument for at least five seconds. 1 2 Turn the power back on and simultaneously press the “SETUP” and keys. This must be done while “TEST DONE” is being displayed. 3 If step 2 was performed correctly, the instrument will now display “UDC” [Upper] “UPDATE” [Lower]. 4 Press the Function Key. The instrument will now display “DIS” [Upper] “RESTORE” [Lower]. 5 key. The instrument will now display “CFG” [Upper] Press the “RESTORE” [Lower]. 6 Press the Function Key. The instrument will now display “DOIN” “RESTORE” 7 When the instrument finishes the restore operation, it automatically resets itself and restarts in the product mode. The instrument configuration will now be the same as it was when the instrument left the factory and all user- entered configurations since that time have been overwritten. Page 1 of 1 Revision 1

More Related