1 / 8

Test room 1 : V 1 = 18,5 m 3 H= 2,46 m

raanan
Download Presentation

Test room 1 : V 1 = 18,5 m 3 H= 2,46 m

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Project codePN-II-RU-TE-2011-3-209Area : Stiinte inginerestiPrincipal InvestigatorAssoc. Prof. PhD. Eng. IORDACHE VLADPhone: +40749218162; Email: viordach@yahoo.comInstitutionUniversitatea Tehnica de Constructii BucurestiResearch project titleIEQ-Atmospheric pollutants transfer indoors. Tools for indoor pollution level prediction and occupants protectionWeb Sitehttp://www.cambi.ro/ieq/index.html Prezentare succinta a ideilor legate de constructia standului experimental in vederea studiului in laborator al transferului de O3 de la exterior la interior Conf. Andrei Damian – CAMBI Center

  2. Imagine de ansamblu al standului experimental cu cele doua camere-test si zonele-tampon: holul de acces in stand (Hallway-BZ1) si incaperea laterala de depozitare (Hallway-BZ2)

  3. Test room 1 : V1 = 18,5 m3 H= 2,46 m lTestRoom =2,59 m LTestRoom =2,90 m lFe/hFe =1,10 m/1,10 m l = 4 cm Injection zone : V = 0,285 m3 Imagine – Zoom a camerei-test din stanga usii de legatura dintre cele doua camere, cu dimensiunile geometrice ale acesteia Ipoteza de pornire pentru simularea mediului exterior incarcat cu O3: Prevederea unei “zone de injectie-tampon” cu latimea de 4 cm, adiacenta camerei-test pe toata lungimea sa (2,90 m), in care sa se faca injectia unui debit constant de O3=1g/h, pana la atingerea unei concentratii maxime de 50 ppb, echivalenta cu aprox. 100 g/m3 de O3

  4. Test room 1 : V1 = 18,5 m3 H= 2,46 m lTestRoom =2,59 m LTestRoom =2,90 m lFe/hFe =1,10 m/1,10 m l = 4 cm Injection zone : V = 0,285 m3 GO3 Timpul in care se atinge aceasta concentratie, in conditiile date :Cinitial =0 , este: Pentru reducerea acestui timp, cea mai fezabila solutie este marirea debitului de injectie a ozonului (de ex. 32 g/h), de unde rezulta:

  5. In concluzie, cu generatorul de O3 actual, concentratia maxima dorita (50 ppb) se obtine in 28,5 ore (maimult de douazile), in timpce cu un generator de 32 g/h, ea se obtine in maiputin de o ora (50 minute)! • La concentratiimaimici de O3 in zona de injectie, timpii de obtinere a acestoravorfi, evident, simairedusi • Solutia propusapleaca de la premisa ca ozonul nu interactioneazachimic (fenomene de adsorbtie-desorbtie) cu materialele de constructie din care suntexecutatiperetiizonei de injectie (PAL, lemn, ciment..e.t.c.) • Pentruobtinereauneiconcentratiiuniforme in spatiul-tampon al zonei de injectie, recomandgasireauneisolutii de injectie-multipunct a debitului de ozon in cavitate (de exemplu, prinmontareaunuidistribuitor la iesirea din generatorul de ozon, cu maimulteduze de injectiecuplate la zona de injectie, in puncteaflate la distantemari). • Recomand, de asemenea, achizitia a inca 4-5 sonde de O3, care sa fie amplasate in zona de injectie, pentrugasireamomentului in care s-a atins o bunauniformitate a concentratiei de O3 ETAPELE NECESARE DESFASURARII UNUI SET DE EXPERIMENTE PRIVIND TRANSFERUL DE OZON DE LA EXTERIOR LA INTERIOR • Etansare a ferestrei, usii si gurii de aspiratie din camera-test (banda adeziva perimetrala) • Injectarea debitului de O3 in zona de injectie pana la obtinerea concentratiei dorite • Dez-etansarea ferestrei si a gurii de aspiratie • Deschiderea orificiului de patrundere a aerului de compensate in zona de injectie • Pornirea ventilatorului cu turatie variabila (VTV) la debitul dorit de utilizator • Masurarea concentratiilor exterioara (din zona de injectie) si interioara (din camera-test) la diverse momente de timp, pana la obtinerea stabilizarii acestora

  6. VTV – Ventilator cu Turatie Variabila GA – Gura de Aspiratie Test room 1 : V1 = 18,5 m3 l = 4 cm Injection zone : V = 0,285 m3 q q=0 – 2 h-1 (3,7 – 37 m3/h) q Orificiu de patrundere a aerului de compensare din zona holului de acces Imagine din timpul functionarii ventilatorului cu turatie variabila: aerul va fi “obligat” sa treaca prin ne-etanseitatile ferestrei si prin orificiul de compensare, cu debitul q, cuprins intre 0 si 2 schimburi/h, adica intre 3,7 si 37 m3/ h

  7. VTV – Ventilator cu Turatie Variabila GA – Gura de Aspiratie Test room 1 : V1 = 18,5 m3 l = 4 cm Injection zone : V = 0,285 m3 q q=0 – 2 h-1 (3,7 – 37 m3/h) q Orificiu de patrundere a aerului de compensare din zona holului de acces PROBLEMA: Pentru a mentine constanta concentratia din zona de injectie dupa pornirea ventilatorului este necesar ca si concentratia din debitul de aer de compensare sa fie aprox, egala cu concentratia din zona de injectie, pentru a nu mai avea nevoie de injectie suplimentara de O3 in timpul functionarii ventilatorului; daca in hol concentratia de O3 este zero, am avea nevoie de o injectie de O3 egala cu 3700 g/h (!!), pentru a mentine 50 ppb in zona de injectie la debitul maxim de 2 h-1

  8. VTV – Ventilator cu Turatie Variabila GA – Gura de Aspiratie Test room 1 : V1 = 18,5 m3 l = 4 cm Injection zone : V = 0,285 m3 q q=0 – 2 h-1 (3,7 – 37 m3/h) q Orificiu de patrundere a aerului de compensare din zona holului de acces SOLUTIE: Introducerea unui debit de aer de compensare q cu concentratia de O3 egala cu valoarea stabilizata, fixa, intre 0 si 50 ppb (0 si 100 g/m3); de discutat cum se face asta practic……