Low Voltage Power Supply SpecificationDCS Workshop 8 Sept 03L.Jirden
LV PS LV PS Electrical Characteristics • AC Input • 230 VAC +- 10%, 50 HZ +- 6%, PF >0.9 • DC Output • Modular design 2 – 7 V, 125 A 8 outputs/crate 24h stability < 5mV or 0.1% 6m stability < 20mV or 0.5% Noise & ripple < 10mV p to p 2 – 7 V, 25 A 12 outputs/crate
FRONT VIEW SIDE VIEW VENTILATOR & CONTR. 4U 300 mm 600 mm 1U HEAT EXCHANGER LV PS LV PS SPACE FOR CABLES 4U LV PS LV PS 4U 1U HEAT EXCHANGER LV PS Mechanical Characteristics TYPICAL RACK LAYOUT
PVSS OPC CL ethernet Provided by manufacturer OPC SRV External interlock PCI “Kvaser” Min 4 per PC CANbus LOCAL PANEL LVPS 1 LOCAL PANEL LOCAL PANEL LVPS 1 LVPS 16 Min 16 per bus Monitoring & Control
POWER ON/OFF SCHEME 1 LV POWER SUPPLY CAN I/F DC POWER MODULES CANbus AC/DC LOCAL SWITCH HAZEMEYER 220V AC RACK POWER DISTRIBUTION STRIP
POWER ON/OFF SCHEME 2 LV POWER SUPPLY CAN I/F DC POWER MODULES CANbus POWER AC/DC HAZEMEYER 220V AC RACK POWER DISTRIBUTION STRIP
POWER ON/OFF SCHEME 3 LV POWER SUPPLY CAN I/F DC POWER MODULES CANbus REMOTE CONTROL AC/DC LOCAL SWITCH HAZEMEYER 220V AC RACK POWER DISTRIBUTION STRIP
MON = MONITOR CON = CONTROL ESS = ESSENTIAL DES = DESIRED FUNCTIONS/PARAM REMOTE MONITORING AND CONTROL FUNCTIONS
MON = MONITOR CON = CONTROL ESS = ESSENTIAL DES = DESIRED FUNCTIONS/PARAM REMOTE MONITORING AND CONTROL FUNCTIONS
MON = MONITOR CON = CONTROL ESS = ESSENTIAL DES = DESIRED FUNCTIONS/PARAM GROUP MANAGEMENT THE POSSIBILITY TO CONFIGURE AND PERFORM FUNCTIONS ON GROUPS OF CHANNELS WITHIN A CRATE
OPC SERVER • General • Compliance with OPC standards • No effect on PS output due to failure of remote control • Restart of OPC remotely • Not send set points automatically at startup – read from device • PS shall maintain its set points during PS power failure? • Genuine device and cache access • Interactive list of device functions
OPC SERVER • Maintenance • To support future versions of Windows and OPC standards • To support future versions of PS firmware • Configuration • Allow appropriate management of the fieldbus • Human readable configuration file (such as XML) • Obtain actual configuration by scanning • Setting of ranges for analog values and setting of the dead band
OPC SERVER • Performance • Change in Device to OPC: max 10 sec at full bus load max 1 sec for a single PS • Device cache to OPC client: max 3 sec for all parameters • Write from OPC to device: max 1 sec • Interlock to start ramp-down: max 5 ms
Cooling • Forced air • Environment • Radiation < 0.01 Gy < 108 n/cm2 • Magnetic Field < 80 Gauss • Construction • Halogen free material • Safety regulations • CE certification • Reliability • MTBF > 90 000 hours
Quality assurance • Production tests • Functional tests • Load tests • Documentation • User’s guide • Reference manual • Test and calibration reports
Questions • Who wishes to use the spec? • For Wiener, CAEN, Arem Pro, other? • Individual or common purchasing? • When? • Adapt spec for HV supplies as well?