An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. UTICAJ PROMENE RADNE TEMPERATURE NA DIELEKTRIČNU ČVRSTOĆU TRANSFORMATORSKOG ULJA Ljubiša Nikolić, Nikola Ilić,Slađana Teslić – ETI”Nikola Tesla”, Beograd Slavče Jevtić – TENT-A CG-Cigre-2011

  2. 1 RELATIVNA OVLAŽENOST ULJA

  3. 1.1 Relativna ovlaženost ulja(po zapremini ili po težini) RH = Cw/Cw-max = f(Cw-max) RH(%)= 100*Cw/Cw-max = f(Cw-max) • RH – relativna ovlaženost ulja • RH(%) - relativna ovlaženost ulja u procentima • Cw(ppm) – sadržaj vode u ulju na nekoj temp. • Cw-max(ppm) – maksimalni sadržaj rastvorene vode za datu temperaturu. • PS: Kod ulja uobičajeno govorimo o težinskim odnosima, • kod gasova su uobičajeni zapreminski odnosi

  4. 1.2 Kriva zasićenja ulja vodom(Sadržaj vode pri RH=100%)

  5. 1.3 Odnosi abs.sadržaja vlage u transf.ulju i sadržaja vlage u papiru(u stanju ekvilibrijuma: Nielsen-ove krive,...)

  6. Sadržaj vlage u ulju Srednja temperatura Ekvilibrijum Kriva zasićenja Dinamičko praćenje RH u vremenu i procena DČu 1.4 ON-line kontrola rel.ovlaženosti ulja

  7. 1.5 Kapacitivna sonda za merenje RH ulja • Kapacitivna sonda se sastoji od dve elektrode, jedna je porozna, i higroskopnim dielektrikom. Rel.diel.konstanta vode je 80. Merenjem promene kapacitivnosti ovakve sonde, uređaj se kalibriše da meri RH.

  8. 1.6 Kontrola ovlaženosti drveta, papira,...

  9. 1.7 Uređaji za merenje ovlaženosti papira

  10. 1.8 Relativna i apsol. ovlaženost papira

  11. 1.9 Rel.ovlaženost papira u funkciji absol.ovlaženosti papira i temperature

  12. 1.10 Promena RH(%RS) transf.ulja za vreme ogleda zagrevanja ET

  13. 1.11 Promena RH (%RS) transf.ulja za vreme ogleda zagrevanja ET

  14. 1.12 Negativne posledice ovlaženosti ET • Ubrzano starenje celuloznih materijala (papir +presbord/kraftbord) • Smanjenje DČ ulja sa povećanjem RH • Smanjenje DČ čvrste izolacije • Rizik od stvaranja mehurića pri naglom povećanju temperature namotaja

  15. 2 ZAVISNOST DČ i RHULJA

  16. 2.1 Zavisnost DČ i RH DČ = DČmax*(1 – RH), • DČmax –je DČ potpuno čistog i suvog ulja i znosi≈85kV/2,5mm • RH –ovlažnost ulja, • RH=(RH(%)=(Cw/Cw-max)*100 Linearnost ovakve relacije je sasvim zadovoljavajuća u opsegu RH od 0,05 do oko 0,8. Realne promene vrednosti DČ u funkciji Cw, i RH pri nekoj temperaturi prikazane su sledećim grafikom. U IS ET sa uljno-papirnom izolacijom povećanjem temperature vlaga iz papira migrira i deponuje se u ulju, i tako menja dotadašnje stanje ravnoteže tj. količinu rastvorene vlage u ulju. To znači da se u jednom idealnom sistemu oba ova suprotstavljena efekta kompenzuju.

  17. 2.3 Ilustracija ET sa različitim Cp(%)(DČ u radu ET, i merena u Laboratoriji)

  18. 3 IZVORI KONTAMINACIJE VLAGOM jednog ET

  19. 3.1 Detalj namotaja VN

  20. 3.2 Odnosi masa i površina čvrste celulozne izolacije u funkciji njene namene tj.debljine izolacija • Primer blok transf.: 400MVA, 18/347kV

  21. 3.3 Raspodela temperature i vlage po visini ET

  22. 3.4 Primer promene sadržaja vlage u ulju i papiru u zavisnosti od pog. stanja ET

  23. 3.5 Difuzione vrem. konstante zauljno-papirni sistem u zavisnosti od debljine “papira”

  24. 4 ON-line MONITORING OVLAŽENOSTI TRANSF.ULJA

  25. 4.1 Primer 1: Promena RH transf.ulja sa promenom temperature

  26. 4.2 Primer 2: Promena RH transf.ulja sa promenom temperature

  27. 4.3 Primer 3: Promena abs.sadržaja vlage u papiru i u transf.ulju sa promenom temperature

  28. 5 ŽIVOTNI VEK ET U FUNKCIJI NJEGOVE OVLAŽENOSTI

  29. 6 Uticaj vlage kombinovan sa sadržajem čestica na DČ ulja

  30. 7 EKSPERIMENT • Na modelu uljno-papirnog izolacionog sistema za ET reda 200MW, 220kV: • 1,7 kg trafoborda 3mm • 0,6 kg trafoborda 1mm • 15 lit čistog i suvog transf. ulja Odnos papir-ulje: 1: (6-7)

  31. 7.1 Trafobord u modelu(1,7kg 3mm + 0,6kg 1mm)

  32. 7.2 Merenje DČ ulja u modelu(integrisane merne elektrode: fi 20mm, razmak 1mm)

  33. 7.3 Kondicioniranje uljno-papirnog modela: 600C, 4 dana x 24h

  34. 7.4 Simulacija naglog pada temperature ovlaženog ET (npr. ispad iz pogona posle visokog opterećenja pri ledenoj kiši)

  35. 7.5 Merenje DČ tokom pada temperature u modelu (negativni gradijent temp.)

  36. 7.6 Merni rezultati: DČ u f(temp. i vremena)

  37. 7.7 DČ = f(hlađenja i vremena)(grafički prikaz rezultata merenja) • Posle oko 90 min je došlo do zasićenja ulja vlagom u formi suspenzije kapljicama vlage , i do praktičnog gubitka DČ. Posle 60h DČ je totalno regenerisana. Na uzorku ulja na početku merenja sadržaj vode je bio 86ppm, na uzorku ohlađenog ulja posle 60 sati je bio 10,8ppm.

  38. OFF-Line (isključen i razvezan ET) RVM-Recavery Voltage Meter PDC-Polarization-Depolarization Current FDS-Frequently Domain Spectar Faktor diel.gubitaka papira, (tgdP=0,0021+0,0083CP2, εr=3,8+0,41Cp, pri 80°C, a tgδP preko tgδNAM i tgδULJA) direktna sa papira/uzorka KF ON-Line (za vreme normal. pogona) Na osnovu sadržaja vode u uzorku ulja uzetom na temeraturi t, i preko ekvilibrijumskih krivih Cp(%)=f(Cw(ppm)-lab. i t-pogon), npr. Nielsen, Piper,... (izvođenje zaključaka je regulisano standardima, i sa lab.rezultatima za DČulja učestvuje u proceni stanja ET) 8 Konvenc. dijagnostika ovlaženih ET(određivanje sadržaja vlage)

  39. HLADAN ET Cw(ppm) –nisko DČ(kV/2,5mm) – visoko TOPAO/VRUĆ ET Cw(ppm) - visoko DČ(kV/2,5mm) - nisko 8.1 Sistematska greška pri konvenc. proceni ON-line na osnovu ekvilibrijumskih krivi

  40. TENT-B 725MVA 21/400kV 9 gasova+ RH ulja ОN LINE MONITORING OVLAŽENOSTI ULJA

  41. 9.1 Primer ON-line monitoringaET 725MVA, 400kV (9 gasova+RH)

  42. 9.2 Primer ON-line monitoringaET 725MVA, 400kV (9 gasova+RH)

  43. 9.3 Primer ON-line monitoringaET 618MW, 400kV (9 gasova+RH)

  44. I-zona: polako nestajanje emulzovane vlage, pa stoga i oštro podizanje DČ II-zona: otklanjanje rastvorene vode iz ulja III-zona: zona bržeg sušenja ulja nego što difuziono pristiže iz papira 10 ILUSTRACIJA PROMENE DČ TOKOM SUŠENJA ET

  45. 11 PROCENJENI SIGURNOSNI NIVOI DČ u f-ji naponskog nivoa

  46. 12 PRIBLIŽNA PROCENA STANJA ET PO STEPENU OVLAŽENOSTI ET

  47. ZAKLJUČAK • 1. Vlaga u ET je vrlo nepoželjna. • 2. Ako je već prisutna u neželjenoj količini, sagledavanjem uticaja na izol.k-ke, može se uticati na pouzdanost rada ET, do termina za sušenje koji se može planirati. • 3. Detektovanjem rizičnih situacija, kada je proboj u ulju vrlo verovatan, možemo ga izbeći određenim manipulacijama. • 4. Pomoću aktuelnih kriva DČ, uz poznavanjeodnosa količina papir/ulje, moguće je odrediti i minimalno potrebnu količinu vlage koju treba iz ET eliminisati, da bi se teretio do željene max.temperature,naročito kod OFAN i OFAF

  48. HVALA NA PAŽNJI

  49. PITANJA ?