MPE-EI Resistance measurement in 13kA interconnection bus bars in S3-4

MPE-EI Resistance measurement in 13kA interconnection bus bars in S3-4. Electrical measurements in S34, zone D, Week14. Measurements…. Equipment used: DLRO 010 Measurement are taken over 160 mm (distance between voltage taps), 5 mm apart

sue
Download Presentation

MPE-EI Resistance measurement in 13kA interconnection bus bars in S3-4

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. MPE-EIResistance measurement in 13kA interconnection bus bars in S3-4 Electrical measurements in S34, zone D, Week14

  2. Measurements… • Equipment used: • DLRO 010 • Measurement are taken over 160 mm (distance between voltage taps), 5 mm apart each side of the interconnection which is 150 mm long. Temperature is also recorded. • The value stored is the average of 10 measuring points.

  3. Raw measurements… S34 samples • Interconnection opened and measured with DLRO…

  4. Histograms… S34 samples • M1-M2 in D-zone • 32 measurements • M3 in D-zone • 22 measurements

  5. Conclusion • Waiting to confirm measurement in M3-QBBI.B25R3, by X-ray. • Should be able to detect big defects. • It can be a complementary measure to visual inspection before insulation and closing the lines.