An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. SUPERVISÃO E CONTROLE OPERACIONAL DE SISTEMAS Prof. André Laurindo Maitelli DCA-UFRN

  2. RÁDIO MODEM

  3. É um radio-modem projetado para aplicações de sistemas SCADA. Possui as seguintes características: velocidades de 4.800 a 19.200 b/s, usando uma interface padrão RS-232; operação half-duplex ou simplex; 8 canais para VHF, UHF e 900 MHz; monitoramento e diagnóstico on-line. Possui um modem e um rádio separados. Características – T96SR

  4. Descrição Física

  5. Descrição Física

  6. Configuração • Características de operação do T-96SR são configuradas pelo “Radio Service Software” (T96RSS); • Programa para diagnóstico offline (OFLNDIAG); • Programa monitor para diagnóstico online (ONDMON); • Os três programas são MS-DOS e rodam em PC (2 MB de memória são requeridos).

  7. Diagnósticos e Comandos

  8. Endereçamento

  9. Configurações em rede • O T-96SR é projetado para substituir cabos em aplicações de sistemas SCADA, telemetria e controle; • A porta serial RS-232 permite a conexão direta com Controladores Lógicos Programáveis (PLCs) ou Unidades Terminais Remotas (RTUs).

  10. Configurações em Rede – Rede Básica

  11. Configurações em Rede – Rede Básica • Características: • Estação mestre pode ser half duplex ou simplex; • Diagnóstico on-line não é disponível em tempo real; • Diagnóstico Remoto/Local e Controle são disponíveis desconectando o PLC mestre e substituindo por um PC rodando a T-96SR OFLNDIAG.

  12. Operação – Painel Frontal recepção transmissão alimentação antena interface DE-15F (inclui a alimentação).

  13. Indicadores do LED

  14. RS-232

  15. RS-232

  16. Seleção do Canal

  17. Utilização com PLC SLC500

  18. Configuração do canal (RSLogix)

  19. Configuração do canal (RSLogix) • Model SLC 5/0x PLC Configuration • Driver: DF1 Half-duplex Master • Baud: 9600 bps • Parity: None • Stop Bits: 1 • Node Address: 1 (dependent on application) • Protocol Control • Control Line: Half-duplex w/o continuous carrier • Error Detection: CRC • Polling Mode: Msg don't allow remotes to initiate • Duplicate Packet Detect: Disabled • Reply Message Timeout (x 20 ms): 1 • (dependent on application) • ACK Timeout (x 20 ms): 50 • RTS Off Delay (x 20 ms): 3 • RTS Send Delay (x 20 ms): 8 • Message Retries: 3 • Pre Transmit Delay: 0

  20. Conexões

  21. Configuração do Rádio • Feita pela tela de setup de parâmetros do rádio/modem, a qual contém três sub-telas: • Setup dos parâmetros do modem; • Setup dos parâmetros do rádio; • Setup dos parâmetros de freqüência.

  22. Setup dos parâmetros do MODEM Long ID, Short ID:Factory Set/user programmable if desired. Comment: adiciona comentários Online Diagnostics: Active T-Base Option: Disabled Extended Turnoff (T2): Disabled Output Raw Diagnostics Data Only: Disabled Baud Rate: 9600 bps (dependente da aplicação) Data Format: 8 bits, 1 stop Data Type: Enhanced Network Type: T-96SR Native

  23. Setup dos parâmetros do rádio Radio: modelo do rádio Range: faixa de freqüências de rádio Redirect Channel 8 to Channel: disabled Channel: Specifies whether unit is half-or full-channel (12.5 or 25 kHz) PTT Watchdog: Enabled PTT Watchdog Timer: Sets max transmit time: set to 60.0 sec Tune Range: Low Rx Dynamic Carrier Detect Off Threshold: enabled Carrier Detect Thresholds: On:-110 dBm, Off:-115 dBm (beginning values)

  24. Setup dos parâmetros de freqüência Rx Frequency: Freqüência de Recepção Tx Frequency: Freqüência de Transmissão Tx Power (non-linear): Potência de transmissão - 255 é o máximo (5W)

  25. SLC – Instruções de Comunicação • SVC • Interrompe a execução do programa Ladder enviando uma mensagem. Em seguida, o programa retorna a seu fluxo normal; • MSG • É utilizada para envio e recebimento de mensagens. Quando a instrução é habilitada, a transferência de mensagem está pendente. A transferência de dados acontece ao término da última instrução do Ladder;

  26. Usando o SLC 5/03 • Ao usar SLC 5/03 é permitida a configuração dos canais de comunicação específicos (0, 1, ou ambos): • o canal 0 é o RS-232/DF1 Full-Duplex or Half-Duplex (mestre ou escravo), DH-485, ou ASCII • O canal 1 é DH-485;

  27. Instrução de parâmetros MSG • Read/Write; • Target Device: • 500CPU, se o dispositivo designado é o SLC; • 485CIF, para o PLC-2; • PLC-5, para o PLC-5. • Local ou Remote: • Local, se o dispositivo designado está na rede local; • Remoto, se o dispositivo está em outra rede. • Control Block: é um bloco de palavras, contendo os bits de status, endereço de arquivo designado, e outros dados associados com a instrução de mensagem. • Control Block Length: campo que indica o número de palavras de arquivo que estão sendo usadas pelo bloco de controle.

  28. Exemplo de Mensagem do SLC 5/03, SLC 5/04 e SLC 5/05

  29. Bits do Control Block • Error Bit ER (bit 12): é setado quando a transmissão de mensagem falha; • Bit DN (bit 13): é setado quando a mensagem é enviada; • Start Bit ST (bit 14): é setado quando o processador recebe o reconhecimento do dispositivo designado; • Enable Bit EN (bit 15): é setado quando as condições do programa são verdadeiras e há espaço disponível no buffer do MSG. Permanece fixo até a transmissão da mensagem ser completada e a condição de entrada seja falsa.