1 / 14

SPD Control System: status report Domenico Elia – INFN Bari

SPD Control System: status report Domenico Elia – INFN Bari. Updates to the URD Global Detector Control Layout Prototyping activities. Updates to the URD. HV system : none LV system : type and location of PS sources type, number and location of Voltage Regulators

vlora
Download Presentation

SPD Control System: status report Domenico Elia – INFN Bari

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. SPD Control System: status report Domenico Elia – INFN Bari • Updates to the URD • Global Detector Control Layout • Prototyping activities ALICE DCS workshop - March 10, 2003

  2. Updates to the URD • HV system: none • LV system: • type and location of PS sources • type, number and location of Voltage Regulators • preliminary cabling scheme • FERO: preliminary architecture overview (Peter) • Cooling: more detailed description (meeting with ST/CV people this week) ALICE DCS workshop - March 10, 2003

  3. VRs Internal PP 10 mt 30 mt LV PS and Voltage Regulators Current scheme: • regulators outside magnet door (>10 mt from SPD): • no need for rad-hard devices • spaces, cabling, cooling issues much less critical • reduced amount of power lines (A+D grouping): • 2 regulators each half-stave (instead of 7) • 1 LV power source each half-sector (instead of 2) ALICE DCS workshop - March 10, 2003

  4. Cabling scheme (I) ALICE DCS workshop - March 10, 2003

  5. Cabling scheme (II) ALICE DCS workshop - March 10, 2003

  6. SPD Control sub-systems (I) SPD HV LV FERO Cooling Equipment bias PS V/I-monitor plant VME crate V-reg. board temperature detector configuration ALICE DCS workshop - March 10, 2003

  7. SPD Control sub-systems (II) • High Voltage: - 1 CAEN SY1527 crate (located in counting room) - 10 A1519 boards (floating 12 ch., 250V/1mA) - cables: 120 micro-coax Ethernet CAEN 1 crate PX UX 120 channels SPD ALICE DCS workshop - March 10, 2003

  8. SPD Control sub-systems (III) PX • Low Voltage: - 4 Wiener PL500F boxes (located in the cavern) • - 20 LV modules • (single channel, 5V/50A) • - Voltage Regulators: • - new location • - smaller number • - open control issues • - cables: •  see cabling scheme UX CAN bus Wiener 4 crates Wiener Ethernet Wiener 20 channels JTAG VMEJTAG ctrl V-reg. board V-reg. board V-reg. board 240 voltages 20 boards (total of 240 VR) ? SPD For each VR: • Over-Current • Inhibit ALICE DCS workshop - March 10, 2003

  9. SPD Control sub-systems (IV) ALICE DCS workshop - March 10, 2003

  10. Prototyping activities (I) Test station setup in Bari lab: (in collaboration with Antonio Dalessandro, Leonid Vinogradov) • PC with Win2K devoted to SPD control developments • PVSS2 and Framework 1.2 software installed HV control sector: • CAEN OPC Server 2.0 installed and configured on same PC • CAEN SY1527 equipped with A1519 board (12 HV channels) ALICE DCS workshop - March 10, 2003

  11. Framework selection of SY1527 with 1 HV board Prototyping activities (II) PVSS2 Framework CAEN OPC Server CAEN SY1527 HV board: A1519 ALICE DCS workshop - March 10, 2003

  12. Hierarchical structure Prototyping activities (III) SPD HV-LV preliminary control panel ALICE DCS workshop - March 10, 2003

  13. Prototyping activities (IV) Example of monitoring panels for 12 HV channels (1 half-sector) ALICE DCS workshop - March 10, 2003

  14. Prototyping activities (V) LV control sector: • WIENER PL6021 PS equipped with Kvaser PCIcan-Q card • Kvaser card drivers installed and tested (OK) • CANbus tested (OK) • Wiener OPC Server not available • SLiC.OPC Server working with Applicom OPC Client • still problems using PVSS OPC Client  investigating with IT/CO people (open issue) ALICE DCS workshop - March 10, 2003