An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Power quality measurement with the electricity meter, model LZQJ-XC Autor : Ing. František Horváth , Šp. Mlyn 18.4.2013

  2. LZQJ-XC – Description Electricity meter versions • Voltage • Ranges: • 3x58/100V; 3x63/110V • 3x230/400V; 3x240/415V • 3x290/500V; 3x400/690V • 3 x 100V Aron (3-wire versions) • Broad range inputs • Suitable for FVE (fotovoltaic power generation sources) • from 58/100V to 240/415V • Current • Through MT x/1 A : 1A; 1(2) ; 1(6)A; 5II1A - universal; • Through MT x/5 A: 5 A; 5(10)A; • Direct measurement: • 5(100)A; 5(60)A; 10(100)A; 10(60)A; • Frequency: 50 Hz; 60 Hz; 16 2/3 Hz Parameterisation button Q-LED P-LED Optical sensor Electric cell – reading in voltage-free state Communication module Variability of modules: PSTN GSM GPRS Ethernet 2nd interface RS485

  3. Model LZQJ-XC – not only a four-quadrant device LZQJ-XC: a four-quadrant + Actual values in the servicing table TS per phases, measuring period 1 s: U, I, P, Q, S, P/S, f Work registers P+, P-, Q+, Q- Q1 , Q2, Q3, Q4 Profiles P.01 /P15/ P.02 /P10/ Monitoring of grid quality parameters – EN 50 160 Harmonic analysis U, I after 31st Measurement of losses in distri-bution transformers /Rfe, Rcu/ Registration of Imax within overall measurement in transforming stations Registers of events in logbooks – e.g. voltage dumps, tampering, ... Registration of rapid voltage fluctuations with time resolution in ms

  4. Power quality measurement with the electricity meter LZQJ-XC • Evaluation complies with the standard EN 50160 • Source: measured values in P.02 with MP 10min /LP10/ • Model LZQJ XC meets the requirements for Q-meters of the Class B, the newest model NXT 4 meets the requirements of the Class S • Evaluations in the electricity meter LZQJ-XC : • Checks of non-exceeding of limit values • Extended records in the electricity meter: Profile P.130 , LP 1440 – register C.88 - exceeding of limits for P.02 : U, THD, Pst, f • Visualisation on PC • Evaluation of measured values by EMH software –focused on non-exceeding of limit values

  5. Measured quantities in the profiles P.01 and P.02 - basis for the grid quality measurement: exact values • Measured values in P.01 with the measuring period 15 min. /LP15/ : P, Q, S, D up to 32 channels • Measured values in P.02 with the measuring period 10 min. /LP10/ : • P, Q • Uavg (L1, L2, L3) • Umax (L1, L2, L3) • Umin (L1, L2, L3) • Iavg(L1, L2, L3) • Imax (L1, L2, L3) • Total Harmonic Distortion THD U (L1, L2, L3) • THD I (L1, L2, L3): It exceeds even the requirements of EN 50 160 ! • Flicker (L1, L2, L3) • Frequency • Other channels: - Register for checks of installation C.86.0 • /up to 60/ - Register for checks of voltageC.86.1 • - Channels for the registration of individual harmonics in the grid

  6. Configuration for grid quality monitoring Registerchecks of voltageC.86.1 Optional setting of parameters for quality monitoring: 2 independent bands for U, f and limits of THD U, Pst Register C.86.1

  7. Power quality measurement with the electricity meter LZQJ-XC • Register C.86.1() = register for voltage monitoring (EN 50160) • Monitoring of two frequency bands (10 s average values) • Monitoring of two voltage bands (10 min average values P.02) • THD U (10 min average values P.02) • Short-term flicker Pst (10 min average values P.02) Record of exceeded limit value in P.211, with time stamp Register C.88.xx = Register of events – total of exceeding cases / decrease of monitored U, THD, f, Pavg - for a long-term monitoring • C.88.96() registers completely checked 10-second average values • C.88.97() registers completely checked 10-minute average values • C.88.98() time stamp for start time

  8. Evaluation of quality measurement data Evaluation of long-term monitoring of U, f, Pst and THD from P.02 Register C.88.XX – Number of over- / under- passing of defined limit values • % of measured values which did not exceed • a set limit Profile P.130, LP 1440 – Register C.88

  9. Power quality measurement with the electricity meter LZQJ-XC EN 50160 IEC 61000-4-xx (EMC) register kvality napätia(C.86.1) Vyhodnotenie nameraných hodnôt s hranicami podľa EN 50160 v elektromere • Užívateľský profil • (P.02) • Presné merané hodnoty • Vyhodnotenie cez SW Počty prekročení nastavených hraníc (C.88.xx) Zaznamenávanie prekročení hraníc s časovou pečiatkou (P.211) Dlhodobé zaznamenávanie Denný profil(P.130)

  10. Principles of harmonic analysis • Harmonic voltages • 95% of 10-min average effective values of voltage of each harmonics must not exceed specified values in any weekly period – the standard stipulates after 25th , in LZQJ XC until 31st • Total harmonic distortion THD must not be greater than 8%

  11. Evaluation of harmonics in LZQJ – XC Example of representation of harmonics with evaluation of limit values: LZQJ XC evaluates even harmonics in current

  12. History of phase voltages – Record in LZQJ – XC Fast voltage fluctuations Raster in ms , Window -0.3 to +1 sec from the event Optional analysis of short-term dumps on the level of ms

  13. Measurement of actual values in LZQJ-XC • Measured values in the service table of TS – period of measurement 1 s: • P per phases and the sum • Q per phases and the sum • S per phases and the sum • P/S (PF) per phases and the sum • I (L1, L2, L3) • U (L1, L2, L3) • f - Frequency In combination with “Loger XC” it is possible to read and store actual values in a 6-sec raster on SD card

  14. U 8 kV 6 kV t Accurate measuring system – essential element of the electricity meter LZQJ-XC • Due to an accurate compensated current converter at the input and due to a strong measurement processor: LZQJ-XC works in the Accuracy class 0.2S LZQJ-XC is protected by robust input circuits -it is suitable for FVE

  15. Blackout -Rozpad siete 4.11.2006 Porovnanie sieťovej frekvencie