An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. PHOENICS User Group Meeting Benelux User Group Aristo Centre Eindhoven Netherlands May 2005

  2. Modelling Discharges from Rooftop Stacks in Confined Environments A CFD presentation by Dr. Paddy Phelps ( Flowsolve Ltd )

  3. Presentation encompasses the results of three different projects, performed over a period of time Each project used CFD to satisfy a different objective Eindhoven 2005Outline of Presentation

  4. A Classical “Planning Consent” Project Using simulations to determine the dispersion consequences of releases from a “yet to be constructed” facility Predictions assist building services design team to arrive at an effective venting strategy PROJECT # 1

  5. A “Diagnose and Remedy” Project CFD simulations used to investigate cause of environmental nuisance or potential hazard, and assist in design of appropriate retro-fit remedial measures PROJECT # 2

  6. A “Compare and Contrast” Project Comparing possible extract strategies, for a situation where tall stacks cannot be used for aesthetic / planning reasons PROJECT # 3

  7. PREDICTING THE DISPERSION CONSEQUENCES OF FUME RELEASES FROM BUILDING ROOF-TOP STACKS PROJECT # 1

  8. Consequences of release dispersion from an urban university research facility • Industrial Context • Objectives of Study • Benefits of using CFD • Description of CFD Model • Outline of simulations performed • Sample Results Obtained • Conclusions

  9. Emissions Dispersion Study : Industrial Context • A research facility is housed in a pre-existing building on the campus of a city-based UK University. • The site is a built-up area with a mix of private and college accommodation, shops, and university laboratories and buildings in the immediate vicinity.

  10. Emissions Dispersion Study : Industrial Context • It is planned to construct a large extension to the existing research building, effectively doubling its size

  11. Flow Geometry Close-up

  12. Emissions Dispersion Study : Industrial Context • The building extension will contain new research laboratories, from which air and fume-cupboard extracts will need to be vented thoughtfully and considerately to atmosphere .

  13. Emissions Dispersion Study : Industrial Context • Low levels of allergens may remain in the vented fumes • Whilst not always necessarily toxic, the releases may be tainted by unpleasant aromas • There is a history of local complaints about poor dispersion of “unpleasant smells”

  14. Emissions Dispersion Study : Industrial Context • The building extension will create a significant additional impediment to the local ambient airflow • This may have a big influence on the air flow patterns at the vent stack release points

  15. Emissions Dispersion Study : Industrial Context • Will releases from the roof-top stacks of the research building have adequate dilution / dispersion consequences ? • Could effluent plumes impinge upon openable windows or HVAC intakes in nearby buildings, or public access areas ? • If a hazard to the public exists, what is the extent, and how may it be eradicated ?

  16. Flow Geometry Close-up

  17. Consequences of release dispersion from an urban university research facility • Industrial Context • Objectives of Study • Benefits of using CFD • Description of CFD Model • Outline of simulations performed • Sample Results Obtained • Conclusions

  18. Emissions Dispersion Study: Methodology • Use simulation tools to predict trajectory of effluent discharge • Determine dispersion envelope of potentially toxic components in effluent • Confirm any new discharges will not exacerbate existing discharges

  19. Emissions Dispersion Study Objectives • Model predictions will provide input to the design of discharge arrangements which will lead to acceptable environmental impact

  20. Emissions Dispersion Study Objectives • What constitutes “acceptable environmental impact” ? • The Plume Core is diluted and dispersed to a safe level at nearby • HVAC intakes • Opening windows • Public access areas

  21. Criterion of Acceptability • A safe level is taken in this instance to be a dilution level of 1:104 ( i.e. a concentration of 100 ppm ) from stack release • The plume core is the spatial envelope of this critical dilution / concentration

  22. Overview of Release Conditions

  23. Consequences of release dispersion from an urban university research facility • Industrial Context • Objectives of Study • Benefits of using CFD • Description of CFD Model • Outline of simulations performed • Sample Results Obtained • Conclusions

  24. Benefits of CFD Approach (1) • No scale-up problem • Three-dimensional, steady or transient • Interrogatable predictions • Handles effect of • blockages in domain • recirculating flow • multiple inlets and outlets • multiple interacting sources

  25. Project #1: Emissions Dispersion Study • Industrial Context • Objectives of Study • Benefits of using CFD • Description of CFD Model • Outline of simulations performed • Sample Results Obtained • Conclusions

  26. 3-D PLUME DISPERSION MODEL Solution Domain • Solution domain encompasses the principal neighbouring buildings for at least one block on each side of the research facility • Domain 260m by 260m by 66m high

  27. 3-D PLUME DISPERSION MODEL Solution Domain • PHOENICS VR object primitives used to represent building blockages, in the absence of CAD models to import • Some bespoke objects created [e.g. for roofs)

  28. CFD Model Description - 1 • Representation of the effects of : • blockage due to presence of neighbouring buildings, obstacles • resistance and mixing in tree canopy [summer only] • ambient wind vector and temperature profile • multiple interacting releases (chillers, laboratory extracts etc)

  29. CFD Model Description - 2 Dependent variables solved for : • pressure (total mass conservation) • axial, lateral and vertical velocity components • air / effluent mixture temperature • effluent concentration in mixture • turbulence kinetic energy • turbulence energy dissipation rate Independent Variables: • 3 spatial co-ordinates (x,y,z) and time

  30. Roof-top Release Sites • Extract Stacks from Basement BSU • 2 off • Air Chiller Unit discharges • 12 off • Laboratory Extract Stacks • 8 off • Laboratory Discharge Stacks • 3 off

  31. Overview of Release Conditions

  32. Internal Sources:Rooftop Release Specification Basement Laboratory Extract Stacks • Two Vertical stacks • Stack diameter 0.95 m. • Height 3 m. above plant room roof • Release temperature - 24 deg.C • Release velocity - 15 m/s • Flowrate 2.84 m3/s each stack

  33. Project #1: Emissions Dispersion Study • Industrial Context • Objectives of Study • Benefits of using CFD • Description of CFD Model • Outline of simulations performed • Sample results Obtained • Conclusions

  34. Environment Parameters Studied • Domain extent • extended down-wind domain • Ambient Wind • summer and winter wind directions • summer and winter temperature effects • Adjacent buildings • Influence of layout and topology • Environmental Factors • Tree canopy height, layout and resistance

  35. Release Parameters Studied • Basement Extract Stacks • Release temperature - 24 deg.C • Release velocity - 15 m/s • Air chiller discharges • Release temperature - 24 deg.C • Release velocity - 2.6 m/s • BSX stack height • Reference - 3m. above chiller top • High - 6m. above chiller top • Also try - 9m. & 12m. above chiller top

  36. Ambient Parameters Studied • Summer • Ambient temperature - 24 deg.C • Wind from SW • Winter • Ambient temperature - 5 deg.C • Wind from NNE • Wind Speed (Pasquill D stability profile) • High - 8.0 m/s • Low - 2.5 m/s • Still - 0.5 m/s

  37. Project #1: Emissions Dispersion Study • Industrial Context • Objectives of Study • Benefits of using CFD • Description of CFD Model • Outline of Simulations performed • Summary of findings • Conclusions

  38. Summary of findings - 1 • Under high wind conditions, from SW and NNE directions, plume trajectory is sufficient to clear neighbour buildings with stack at original elevation. • SW (“summer”) wind direction is worse than NNE (“winter”) direction. • Under low wind conditions, raising stack by 3 m. should be adequate

  39. Summary of Findings - 2 • Under still SW wind conditions, adjacent chiller discharge air curtains dominate flow pattern in vicinity of release. • BSX stack emission is entrained in complex flow pattern on roof, and dragged down to ground level. Flow reversal at low level spreads plume around side & rear of building. Raising stack 3m. alleviates, but does not eradicate, the problem.

  40. Summer “still” wind flow patternOriginal Stack location

  41. Run 21 : Summer; still windOriginal Stack location

  42. Run 21 : Summer; still windOriginal Stack location

  43. Project #1: Emissions Dispersion Study • Industrial Context • Objectives of Study • Benefits of using CFD • Description of CFD Model • Outline of simulations performed • Summary of findings • Conclusions

  44. Project #1: Dispersion Study Conclusions • Raising stack by 3m. would ensure adequate dispersion of plumes except under still, summer conditions. However, in mitigation, . . . . • Is the predicted flow reversal at low level in the adjacent road a realistic scenario, or would occasional vehicular traffic in road be sufficient to prevent occurrence ?

  45. Project #1: Dispersion Study Conclusions • Such very tall stacks were not an acceptable option and so that (for the time being) was that.

  46. Project # 2 Dispersion Problem Diagnosis & Remedy

  47. Project # 2Dispersion Problem Diagnosis & Remedy • Problem Definition • Study Methodology • Benefits of using CFD • Description of CFD Model • Outline of Simulations performed • Synopsis of Results • Conclusions

  48. Project # 2Problem Definition - 1 • The buildings of interest here are adjacent to the research facility building, whose proposed extension was the subject of the earlier emissions dispersion study. • The buildings, to be referred to as “Building B” and “Building P” are parallel to the road. • A linkage building forms an enclosed courtyard.

  49. Overview of Site from South

  50. Flow Geometry Close-up