An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. TECHNICAL TRAINING 2008

  2. STATIC BLOWER & ROOFTOP

  3. Content • Introduction • Features • System & Control • Installation • Selection Process • Troubleshooting

  4. INTRODUCTION

  5. DUCTED BLOWER

  6. Introduction • Static Blower (SB) – Ducted Fan Coil Unit • Capacity range: - Cooling: 7.5hp – 75hp - Heatpump: 7.5hp – 60hp R407C R407C R407C R407C

  7. Coil Blower Supply Air Return Air Pulley V-Belt Motor Drain Pan Introduction • Basic Configuration

  8. Introduction • Draw-through Operation Air Air Draw-through Blow-through

  9. Introduction • SB series: - Available in R22 & R407C - Horizontal & Vertical air discharge - Belt-Driven (for SB125 and above) - Sequential Controller (for > 1 compressors model) - Phase Sequencer - Wide range (7.5 – 75hp for cooling ; 7.5 – 60hp for heatpump)

  10. Ducted Split Unit • Indoor Unit SB125 C SB125 CR SB150 B SB125/150 D SB125/150 D2 SB125/150 ER SB125/150 ER2 SB75/100 B SB75/100 D SB75/100 BR SB75/100 ER

  11. Ducted Split Unit • Indoor Unit SB200/250/300 D2 SB400/500 D4 SB200/250 B2BR2 SB300/350 B3/BR3 SB400/500 BE/BR4 SB200/250/300 ER2 SB300/350/450 ER3 SB400/500/600 ER4

  12. Introduction • MSS-F series - Horizontal air discharge - Anti corrosion fin - Outdoor motor protection – IP54 - Flexibility of service access - Safety device protection • HP & LP switch • Discharge thermostat • Phase Sequencer • Crankcase heater • Compressor internal overload protection

  13. Ducted Split Unit • Outdoor Unit MSS100/125 B MSS100/125 BR MSS75/100 C MSS75 CR MSS75/100/125 F MSS75/100/125 FR R407C R407C

  14. Ducted Split Unit • Outdoor Unit MSS150 C MSS75/100/125/150 D (4)MSS75/100/125/150 ER MSS200/250/300 D2

  15. ROOFTOP

  16. Blower Supply Air Pulley V-Belt Motor Outdoor Coil Motor Compressor Return Air Drain Pan Introduction • Basic Configuration

  17. Introduction • Rooftop A - Available in R22 or R407C - No additional refrigerant work - Horizontal side throw or vertical down throw - Sequential Controller (for > 1 compressors model) - Phase Sequencer - Capacity range:5.5hp – 42hp

  18. Rooftop A • RT-A RT55 A RT55 AR (4)RT60/80/100/120/150/200 A (4)RT60/80/100/120/150/200 AR (4)RT250/300/360/420 A (4)RT250/300/360/420 AR R407C R407C

  19. Introduction • Rooftop B - Available in R22 only - No additional refrigerant work - Belt-Driven - Sequential Controller (for > 1 compressors model) - Phase Sequencer - Higher EER - Netware III (RT60 only) - Capacity range:6hp – 18hp

  20. Rooftop B • RT-B RT60 B RT60 BR RT90 B RT90 BR RT120/150/180 B RT120/150/180 BR

  21. FEATURES

  22. Features • Standard air discharge configuration as manufactured. • SB-B series

  23. Features • SB-D series • SB-E series

  24. Features • RT-A series • RT250/300 A(R) – FXAD : Vertical down throw • RT-B series

  25. Test Run Operating Mode ON / OFF Temperature set ON / OFF Timer Sleep Heater Temperature set Save Fan Hold Timer set SLM 3 SQ Controller Features • Come with SLM 3 for single compressor model • Come with Sequential Controller for > 1 compressors model Operating Mode

  26. Operating Mode Fan ON / OFF Sleep Temperature set Swing Timer set Timer Active Netware III Features

  27. Features • SB-B series • SB750 B does not come with controller

  28. Features • SB-D series • SB-E series

  29. Features • RT-A series • RT-B series

  30. SYSTEM & CONTROL

  31. System & Control • L2 Board - Single compressor, 3 fan speed • U1SB125 Board - Single compressor, single fan speed • SQ board - Multi compressors, single fan speed

  32. L2 / U1SB125

  33. To indoor sensor To outdoor sensor To room sensor Connect to wired handset L2 / U1SB125 Main Board • L2 L2 Board

  34. Mode of Selection • Mode can be selected via the value of resistor RMODE MODES AUTO COOL DRY HEAT FANRMODE () AP X X X X X 3K AT X X X X X22K EC X X X 110K X : Modes available

  35. Features • Compressor 9 minutes force ON • Memory backup: Auto Random Restart • Cold Start / Hot Start / Hot Keep • Sleep function • Self – Diagnostic • Protections

  36. Auto Random Restart • Auto random restart with last state memory • Shorted at JLST jumper at main board

  37. Power Up JLST Shorted JLST Opened User Set Mode Unit = OFF User Set Temperature Mode = COOL User Set Fan Speed Set Temperature = 24°C Fan Speed = High Power Up Settings

  38. SLEEP set on SLEEP set off Troom°C ½ 1 2 t (hr) Ts Ts-1 Ts-2 Ts-3 Sleep Function Troom°C COOL Ts+2 Ts+1 Ts+½ Ts t (hr) 1 ½ 2 SLEEP set off SLEEP set on HEAT

  39. Self – Diagnostics

  40. Hot Start / Hot Keep • Hot Start - ID fan depends on ID coil temperature User set speed – ID coil temperature > 40 °C ID Fan Stop – ID coil temperature =< 18 °C • Hot Keep - ID fan depends on ID coil temperature - 4 options

  41. Hot Start / Hot Keep 1. Fan Always ON option User set speed – ID coil temperature > 40 °C ID Fan Low – ID coil temperature < 37 °C 2. Fan ON option at the start of Heat mode User set speed – ID coil temperature > 40 °C ID Fan Stop – ID coil temperature < 30 °C For thermostat cut off User set speed – ID coil temperature > 40 °C ID Fan Stop – ID coil temperature < 18 °C

  42. Hot Start / Hot Keep 3. Fan OFF option User set speed – ID coil temperature > 40 °C ID Fan Stop – ID coil temperature < 30 °C 4. Fan Low cycle ON & OFF option ID Fan cut in 30 seconds and subsequently cut off for 120 seconds

  43. Protections • Compressor - 3 minutes Minimum OFF Time - 150 seconds Minimum RUN Time - Overload Protection COOL, AUTO COOL and DRY Comp & OD Fan ON OFF OD coil temp 68 o C HEAT, AUTO HEAT Comp, OD Fan & 4WV ON OFF ID coil temp 68 o C

  44. Protections - Hardware Switch Detection A counter is increased by 1 during the first cycle of thermostat The counter will be reset after 3 minutes Declare E4 if counter > 5 • OD Fan speed control - Cooling OD Fan will run whenever the compressor is cut-in - Heating OD Fan ON 50 o C OFF ID coil temp 55 o C

  45. Protections • ID Coil Anti Freeze - Cooling mode only - ID temperature = 1 °C for at least 1 minute - Compressor has been running for 10 minutes ON Comp & OD Fan OFF 1 oC Comp & OD Fan ON OFF 10 oC

  46. SQ2.0

  47. SQ C 2 SQ H 2 2 No. of Heater No. of Comp No. of Comp Cooling Heatpump Sequential Control Sequential Control Type of Models • Cooling: SQC2, SQC3, SQC4 • Heatpump: SQH22, SQH32, • Heater: SQHT22, SQHT32, SQHT42 • RT360/420AR:SQSIM01

  48. Mode of Selection

  49. SQ Main Board Dip Switch To outdoor sensor - Located in the indoor - Signal to compressors, ID/OD fan, valve & auxiliary heater with timer & protection - Compressor relay cut off - H/L trip - Manual reset button To high pressure switch ON / OFF Dry Contact Connect to Wired Handset

  50. Features • Sequence Control • Balance loading up to 4 compressors • 7 days programmable timer • Auto Mode • Cold Blast / Spurt Heat / Hot Start / Hot Keep • Self – Diagnostic • Energy Saving • Protection