1 / 14

Estágio Supervisionado

Estágio Supervisionado. Profº Luiz Sebastião Costa Marcos Benedito dos Santos. Criada em 1957, para a construção de uma usina que evitaria o colapso energético da Região Centro-Sul. 1965 – Inauguração da Usina Hidrelétrica de Furnas (MG).

macon-knapp
Download Presentation

Estágio Supervisionado

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Estágio Supervisionado Profº Luiz Sebastião Costa Marcos Benedito dos Santos

  2. Criada em 1957, para a construção de uma usina que evitaria o colapso energético da Região Centro-Sul 1965 – Inauguração da Usina Hidrelétrica de Furnas (MG)

  3. A partir da experiência adquirida na construção da Usina de Furnas novas usinas foram construídas. Usina de Estreito

  4. Usina de Funil

  5. Em 2004, FURNAS é responsável por 51% da energia produzida no Brasil.

  6. Furnas Centrais Elétricas S.A. Diretoria de Planejamento, Engenharia e Construção – DT Superintendência de Planejamento – SL.T Departamento de Planejamento da Transmissão – DPT.T Subestação Santa Cruz 500 kV Análise de Desempenho Elétrico

  7. : SÍTIO ELETRO - GEOGRÁFICO DA UTE SANTA CRUZ E ZONA OESTE DO RIO DE JANEIRO (GIS - FURNAS)

  8. FIGURA 8: DIAGRAMA UNIFILAR DA SE SANTA CRUZ 138 kV CONSIDERANDO A AMPLIAÇÃO ADICIONAL DE 4 x 175 MW em SANTA CRUZ Circuitos recapacitados na fase inicial. Circuitos a serem reconstruídos na fase final. Vãos superados por curto-circuito.

  9. SE ADRIANÓPOLIS SE C. PAULISTA SE SÃO JOSÉ 83 km SE ANGRA 500 kV 15 km P/ UTE SANTA CRUZ P/ VALESUL SE GRAJAÚ SE SANTA CRUZ 500kV P/ COSIGUA DIAGRAMA UNIFILAR SIMPLIFICADO DO SISTEMA DE 500 kV COM A CONEXÃO DA SE SANTA CRUZ `A REDE BÁSICA

  10. RELATÓRIO DE TENSÕES - MÓDULO (PU) RELATÓRIO DE CARREGAMENTO - MÓDULO (MW) 2006-UTE SANTA CRUZ no 500 kV-COSIGUA E VALESUL no 500 kV 2006-UTE SANTA CRUZ no 500 kV-COSIGUA E VALESUL no 500 kV CIRCUITOS BARRAS MÍNIMA MÍNIMA MÁXIMA MÁXIMA LEVE MEDIA LEVE PESADA MEDIA LEVE PESADA MEDIA LEVE PESADA MEDIA PESADA ITAORNA-138 1,037 1,042 1,039 1,030 1,031 1,039

  11. RELATÓRIO DE CARREGAMENTO - MÓDULO (MW) 2006 - UTE SANTA CRUZ no 500kV - COSIGUA E VALESUL no 500kV - DESP.MÁX . - LEVE CIRCUITOS – TRAFO - USINA BASE EMERGÊNCIAS CP-ANGRA CP-ADRIANOIII CP-GRAJAU SCRUZ-500/ANGRA-500 377 416 378 634 SCRUZ-500/GRAJAU-500 984 1023 985 1236 CPAULI-500/ADRIANO(BP) 493 461 613

  12. RELATÓRIO DE PERDAS (MW) 2006 - UTE SANTA CRUZ no 500 kV - COSIGUA E VALESUL no 500 kV ÁREAS MÍNIMA MÁXIMA LEVE MEDIA PESADA LEVE MEDIA PESADA REDE BÁSICA (RJ+ES) 397,6 635,0 666,6 291,7 470,4 535,7 REDE DE DISTRIBUIÇÃO 28,0 41,5 46,7 30,4 41,3 43,8 TOTAL 425,6 676,5 713,3 322,1 511,7 579,6

  13. CONEXÃO EM 500 kV BARRAMENTO C.C (kA) 1Ø 3Ø SANTA CRUZ - 138kV 13,7 18,5 JACAREPAGUÁ - 138kV 38,0 38,0 GRAJAÚ - 138kV 42,3 36,9

More Related