ALICE Safety Systems

The ones managed by TS: Fire and gas detections, incl. SNIFFER Radiation monitors for personnel protection (RAMSES) Access control Alarms (AUG, evacuation, red tel…) Alarm transmission (CSAM) The other ones: CO 2 flush in racks, N 2 flush in detector areas

missy
Download Presentation

ALICE Safety Systems

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. The ones managed by TS: Fire and gas detections, incl. SNIFFER Radiation monitors for personnel protection (RAMSES) Access control Alarms (AUG, evacuation, red tel…) Alarm transmission (CSAM) The other ones: CO2 flush in racks, N2 flush in detector areas Radiation monitors for material protection ( Rad-Mon + BCM) The missing ones: Public address system Safety Information Panel (SIP) ALICE Safety Systems M.Tavlet, H.Taureg - ALICE

  2. Synopsis of Alarm transmissions via CSAM and DSS Info in ACR ?? ? ? DIP (non secure) DCS Info & SW actions Info in ACR Secure, local link Pre- alarms Alarms (AL3) C S A M D S S SNIFFER ODH gas smoke Cut power togroup of racks Smoke det. in areas ? Cut power Interlock equipment ODH in areas ??? CCC (TCR) Action Flam. gas in areas Close coolingwater valves Cut power/gas Cooling water temperature Waterflooding Start pumps Detectorspecific action Ambient temperature Dead-man detector Fire Brigade Action Water leakCRs Blocked lifts … Presenceof power Evacuation buttons ITS N2 Release ? Evac. signal Detectorspec. inputs Emergency Stop buttons Cut power Stop flam. Gas ? … Red telephones Local/directactions M.Tavlet, H.Taureg - ALICE

  3. Want all information in ALICE Control Room (ACR) Re-use synoptic where available ALICE requirements aboutSafety systems managed by TS-CSE M.Tavlet, H.Taureg - ALICE

  4. Fire Detection Systems in Areas (halls, pits, cavern…) Installed, tested, in operation Gas Detection Systems in Areas (SG, CR5, cavern) Partially installed Not yet in operation Action matrix defined ALICE requirements aboutSafety systems managed by TS-CSE M.Tavlet, H.Taureg - ALICE

  5. SNIFFER This has become an expensive system Therefore, we have minimized it It appears to be ‘impossible’ (or very expensive and long) to add additional features, such as SF6 sensors It appears not to be allowed (feasible ?) to change the individual threshold per sensor. Want all info in the ACR Adding a full information screen in the ACR appears to be expensive (~ 7-10 kCHF) ALICE requirements aboutSafety systems managed by TS-CSE M.Tavlet, H.Taureg - ALICE

  6. CSAM Designed only to transmit AL3 Want all info concerning ALICE in ACR RAMSES Installation ongoing. Want information in ACR Should it be connected to the access safety system ? Information available at access points ? Should access be forbidden in case of high radiation level ? ALICE requirements aboutSafety systems managed by TS-CSE M.Tavlet, H.Taureg - ALICE

  7. Access Control System (ACS) Access to the site should be dissociated from access to the underground. Example: someone wanting to come at night to the ACR would only need Safety Course Level 2, and we would not have to grant him an underground access (today, LHCI-24). ALICE internal sectorisation is managed locally (with padlocks and procedures) by ALICE, ACS is not involved ALICE requirements aboutSafety systems managed by TS-CSE M.Tavlet, H.Taureg - ALICE

  8. Other Alarm transmissions via DCS Rack control Smoke det. [all racks] CO2 flush in racks of C area Temp. switch [all racks] or Cut power+ Flam. gas D C S Main Temp.Sensor SW action(non secure) ? Cut power /rack Radiation Monitors Local/direct actions SW action(non secure) ? Extra Temp.Sensors Cut equipment Cut power toequip-t or rack(s) Equipment Stop buttons Part of TS-EL control ? Info in ACR M.Tavlet, H.Taureg - ALICE

  9. CO2 flush for rack fire-protection (area C) (This was a project initiated by S.Fratianni who is now in TS.) Part of the hardware is installed: bottles and hoses. Still no triggering system; experiments are left on their own to think about, design, build and implement it. ALICE requests TS to centralize and implement the system N2 flush for fire-protection of L3 solenoid and FASS Tanks and pipes still to be installed Automatic or manual triggering to be decided Other ALICE Safety Systems M.Tavlet, H.Taureg - ALICE

  10. Public Address System Useful to transmit info from the ACR to UX Have common technical solution Safety Information Panel Idea from Safety Commission Display useful info at the entrance of underground areas and in ACR Essential to have it installed Missing Safety Systems in ALICE M.Tavlet, H.Taureg - ALICE