520 likes | 675 Views
IEEE Power Engineering Society Toronto Chapter. Ontario Wind Turbines – Testing of Electrical Safety Kinectrics Seminar May, 2007 Eugene Peter Dick IEEE Senior Member 49 Lynngrove Ave Toronto, Ontario epdick@ieee.org 647 438 8116. 1.5 MW GE Wind Turbine. Foundation - Elevation.
E N D
IEEE Power Engineering Society Toronto Chapter Ontario Wind Turbines – Testing of Electrical Safety Kinectrics Seminar May, 2007 Eugene Peter Dick IEEE Senior Member 49 Lynngrove Ave Toronto, Ontario epdick@ieee.org 647 438 8116
Tower • Height: 65 to 80+ m • Base Flange: 5 m f , circa 200 bolts (ext, interior) • Sections: 3 joined by interior flanges, platforms • Access: ladder with fall restraint • Bus type: rigid or locomotive flexible cable • Section: 500+ mm2 (1 000+ mcm) • Erection: 500 tonne crane
Rotor Blades • Diameter: 71 m • Speed: 12 – 22 rpm • Gearbox: 3-step planetary spur gear, ratio 72 • Power vs wind speed: kWk/hr 50 14 150 21 450 28 900 36 1 500 43 cut out 90
Generator • Rating: 1.5 MW, 1.72 MVA, 575 V, stator 1 509 A • Type: double fed, 3 f, (induction?) synchronous • Rotor via PWM drive rated 300 kW • Poles: 6, - / + 20 % speed (864 to 1 440 rpm) • H (inertial const): 6.55 s (gen alone 0.8 s) • Xd” (subtransient reactance): 0.27 pu • Protection: V over / under / unbal, f over / under • Control: pf or current compensated V
Typical Interconnect Requirements • < 88 % V trip in 2 s, < 50 % V trip in 0.16 s • > 110 % V trip in 1 s, > 120 % V trip in 0.16 s • < 59.8 Hz trip in 300 s, < 57 Hz trip in 0.16 s • DV on synch: < 5 %, flicker IEEE Std 519, 1453 • dc: < 0.5 % on I • harmonics: < 4, 2, 1.5, 0.6 % (h<11, 17, 23, 35) • islanding with load: trip in less than 2 s • no impact on utility feeder protection
Transformer / Collection System • Xmer: 575 / 34.5 kV, Yg / D, Z = 0.76 + j 5.70 % • 35-kV, 67 mm2 (AWG 2/0) concentric Neu cable • several units daisy-chained to riser pole • may run Neu / bond back to main substation • overhead line may be 3 or 4-wire • typically 4 collection lines to main station, CB • each collection line may have gnding Xmer • main Xmer: 34.5 / 230 kV, 100 MVA
Grounding - Objectives • limit V between touchable objects • provide low Z path so protection sees fault I • direct fault I, lightning away from equipment • minimize interference
Grounding - Definitions • Remote earth: soil not rising in potential on faults • Bonding: to connect two objects with low Z path • Grounding: to provide bonding to remote earth • G System: all conductors that facilitate grounding • G Current: fault current that enters a G system • G Electrode: conductors that dissipate I into soil • G Potential Rise: V between G system, remote soil • Step Potential: foot-to-foot V during system fault • Touch Potential: hand-to-foot V on system fault
Grounding – Tested Quantities • GPR: general hazard indicator, telco pairs • Step V: coord to safe body withstand (180, 1 550 V) • Touch V: coord to safe body withstand (168, 663 V) • Touch types: structure, mesh, fence, gate, exterior • Current splits: on external connections: Neu, Ohg • Soil resistivity: model all of above • Surface stone resistivity: check for deterioration • Conductor integrity: mW measured and modelled
Ig - Vg + Telco GPR = Rg Ig
C2 C1 P2 P1 x c Measure Rg with Fall of Potential
4 5 1 3 6 2 Locate Probe P at 62 % of Probe C
C2 C1 P2 P1 x c r1 h r2 When Soil Has Two Layers
C2 C1 P2 P1 x c Interconnections Affect P to C Ratio
C2 C1 P2 P1 x low r c high r Soil Anomalies Affect P to C Ratio
x C2 C1 P2 P1 low r c high r Proximity Correction: Arbitrary P, C
Split- Core CT Network Analyzer C1 C2 low r c high r Network Analyzer for Current Splits
P1 x P2 Network Analyzer C1 C2 low r c high r Network Analyzer for Impedance
Zd Ic + Vp - a Ic + a Ic Rgp - Rg - Ic Rcp + - Ic Rcg + Xcg Xgp Xcp Equiv Cct for Proximity Corrections
Proximity Correction Method • Zg = Zm + a Rgp + b Rcg – Rcp • b = Zd / ( Zd + Rg ) • a = b + Rcg / ( Rcg + Zd ) • measure Zm and a • read Zm at several locations for P • find Zg for each, average these estimates • calculate standard deviation as quality check