190 likes | 208 Views
A Study of …. GIS ASSESSMENT. By Tim RJBR. GIS di RJBR. GIS GITET Saguling Merk : Mitshubishi/Alsthom Sistem 500 kV Outdoor GIS Kiaracondong Merk : Alsthom Sistem 150 kV Indoor GIS Cibabat Merk : Alsthom Sistem 150 kV Indoor. GIS Cibabat. Failure Path untuk assessment GIS.
E N D
A Study of … GIS ASSESSMENT By Tim RJBR
GIS di RJBR • GIS GITET Saguling • Merk : Mitshubishi/Alsthom • Sistem 500 kV • Outdoor • GIS Kiaracondong • Merk : Alsthom • Sistem 150 kV • Indoor • GIS Cibabat • Merk : Alsthom • Sistem 150 kV • Indoor
Failure Path untuk assessment GIS Fungsi Current Carrying Partial Discharge Fungsi Switching Fungsi Insulasi Losses Transfer Daya Terbentuknya partikel bebas Perubahan Fisik Konduktor Kegagalan driving mechanism Kelembaban SF6 tinggi Korosif Kontak/ Konduktor Adanya Uap Air (H2O) Decomposition products (gas & powder form) Kegagalan fungsi rele bantu Timbulnya Kadar Asam (HF) Adanya Kebocoran (gas leakage) Arcing
Pemeliharaan berdasarkan Manual Instruction GIS Cibabat 150 kV - Alshtom
PT.PLN (PERSERO) P3B REGION JAKARTA DAN BANTEN UNIT JASA TEKNIK JAKARTA Hasil Pengujian gas SF6 di GIS Kiaracondong
Penutup • Pengujian yang telah dilaksanakan meliputi: • a. Pengujian Fungsi Insulasi: • i. Pengukuran Purity • ii. Pengukuran dewpoint • iii. Pengukuran decomposition product • iv. Pengukuran Parial Discharge • b. Pengujian Switching • Pengujian dengan menggunakan breaker analyser • Penggantian SF6 merupakan tindakan yang telah dilaksanakan untuk perbaikan kondisi insulasi • Hasil uji fungsi insulasi di atas, perlu dilakukan analisis lebih lanjut dengan komparasi terhadap hasil uji seperti Partial Discharge