1 / 5

CARBON MANAGEMENT BOARD – October 2011

CARBON MANAGEMENT BOARD – October 2011. Carbon Management Steering Board 7 th October 2011 Filter Survey - Update. CARBON MANAGEMENT BOARD – October 2011. Initiative Trials on filter medium used in AHU’s in SAF suggest significant energy / carbon savings are possible.

swain
Download Presentation

CARBON MANAGEMENT BOARD – October 2011

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. CARBON MANAGEMENT BOARD – October 2011 Carbon Management Steering Board 7th October 2011 Filter Survey - Update

  2. CARBON MANAGEMENT BOARD – October 2011 Initiative • Trials on filter medium used in AHU’s in SAF suggest significant energy / carbon savings are possible. • Improvements can be achieved in two respects: • Reducing HEPA supply air medium in non-critical areas. • Replacement of standard AHU filter medium with more efficient filters, where plant space is available. • Optimisation of filter changing; study to measure energy consumption over lifetime of filters to identify the time when energy costs exceed the value of maintenance costs

  3. CARBON MANAGEMENT BOARD – October 2011 Progress to date • A survey of all College buildings is 80% complete, with only two building groups ongoing. • HEPA filters on the supply air to SAF AHU’s 1, 2, 3, 4, 17 & 18 in SAF building, have been changed fro H13 to H10 grade • Study of filter media efficiency has commenced on AHU 3 in Biochemistry.

  4. CARBON MANAGEMENT BOARD – October 2011 SAF HEPA filter changes • H13 filters changed on AHU’s to H10 media, between 23rd and 31st August 2011 • Immediate reduction in fan speed resulted across all six AHU’s, although a fault on a pressure transducer serving AHU 2 was discovered • Savings identified across the units are: • 55,419 kWhr per annum • 30.15 tonnes CO2 per annum • £3,602 electricity cost per annum • Plus lower maintenance costs per annum

  5. CARBON MANAGEMENT BOARD – October 2011 AHU 4 - 50% reduction in power consumed