190 likes | 290 Views
Net Zero Study on a Community College. By: Amanda O’Connell Doenges. My Background. University of Dayton Bachelor’s in Mechanical Engineering Masters in Renewable and Clean Energy Heapy Engineering – LEED & Energy Services Energy Master Plan for Sinclair Community College.
E N D
Net Zero Study on a Community College By: Amanda O’Connell Doenges
My Background • University of Dayton • Bachelor’s in Mechanical Engineering • Masters in Renewable and Clean Energy • HeapyEngineering – LEED & Energy Services • Energy Master Plan for Sinclair Community College
Sinclair Pre-2004 • Proactive campus • Facilities department – energy aware • IT development • Added monitors, projectors, etc. to classrooms and offices
What was already done • T12 to T8 lighting retrofits • LED lighting • CRT to LCD computer monitors • De-lamping of exterior lighting • Variable frequency drives to all air and water side systems • Addition of return air to 100% outside air systems
House Bill 251 • 20% energy reduction by 2014 (compared to 2004)
Net-Zero? • HB 251 is a good first goal • Possibility of going beyond 20% reduction • Steps: • Decrease current energy consumption • Renewable Energy
Renewable Energy • Large Flat Roof Areas – Solar PV • 2,200 MWh/year – could produce • Current consumption at 300,000 MWh/year (only electric) • Low Velocity Wind Turbine
Utility Analysis + Benchmarking • Campus Energy Use Intensity: 134 kBtu/sf • Commercial Building Energy Consumption Survey (CBECS) Database: 120 kBtu/sf • Campus density factor? • Average Campus: 250-450 users per 100,000 GSF • Urban Campus: 550-750 users per 100,000 GSF • Sinclair: 970 users per 100,00 GSF • Using Urban Campus Average = 179 kBtu/sf
Year to Year Comparison • Square Footage • Occupants • Weather (CDD and HDD) • All
Energy Conservation Measures • Daylight Harvesting • Occupancy Sensors • Revise Temperature Set Points to 75F and 70F
Energy Conservation Measures • PC Automatic Shutoff
Energy Conservation Measures • Vending Miser • Exterior Lighting Controls
Energy Conservation Measures • Boiler Retrofits • Very high base load natural gas consumption • Central boilers – DHW and Summer Reheat • Summer Boiler or Heat Recovery Chiller • Boiler Plant Upgrades (Parallel positioning) • 16%+ overall energy reduction through boiler replacements/retrofits
Retro-Commissioning • Identifies operational issues • Original design intent • Lawrence Berkeley National Laboratory Study • 5-15% savings in total building energy use • Commission all new buildings Photo courtesy of CTG Energetics, Inc.
Next Steps • Energy Conservation Measures and Retro-Cx will help to move towards 20%, but will not be Net Zero • Future: • Retro-Commissioning • Energy Metering • Sustainability Coordinator • Education • Renewable Energy
Energy Metering • Meter each building individually • Sub meter large energy consuming processes • Lighting • Ventilation • Heating • Cooling • Plug Loads • ASHRAE Journal – April 2011 – 1-20% savings
Sustainability Coordinator • Individual or a firm • Directly under a President or VP • Position strictly focused on campus energy and/or sustainability • Education to address energy related behavioral changes
Summary • Short Term Energy Savings • Energy Conservation Measures + Retro-Cx • Campus Awareness • Long Term Plan • Capital Improvements • Energy Metering • Sustainability Coordinator • Education • Renewable Energy
Questions? Amanda O’Connell Doenges