1 / 23

Classic and New VD4

Innovation within Continuity. Classic and New VD4. Classic and New VD4. Contents. Introduction / General Low/mid duty – high duty Ratings / Standard Design / Dimensions Operating mechanism Maintenance Accessories / Standard and on request Other / Special Marketing tools. Classic

ella
Download Presentation

Classic and New VD4

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Innovation within Continuity Classic and New VD4

  2. Classic and New VD4 Contents • Introduction / General • Low/mid duty – high duty • Ratings / Standard • Design / Dimensions • Operating mechanism • Maintenance • Accessories / Standard and on request • Other / Special • Marketing tools

  3. Classic and New VD4 Introduction / General • The product name VD4 does not change • VD4 as a brand-name for a high quality VCB is well-accepted • The actual VD4 name is now defined to “classic VD4” • Availability of “new VD4” • Production started in February 2003 • Market introduction almost completed according to marketing plan • “One CB factory: The advantage of EoS in VCBs • DECMS: Excellence in vacuum, casting and embedding technology • ITNIE: Excellence in AT & Logistics and production engineering

  4. Classic and New VD4 Introduction / General • An innovative concept for the maintenance • new VD4 has an actuator with a plug-in snapping-unit • just replacing the snapping-unit the c.breaker is basically a new c.breaker • new VD4 is the first MV circuit-breaker offering this feature • removal and mounting of the snapping-unit requires only 20 min. • the replacement operation is more reliable then any maintenance • operating life of the snapping unit up to 31.5 kA 17.5 kV (25 kA 24 kV) : • today: 10,000 operations already certified • today: 20,000 operations satisfactory carried-out • within 4Q 2003: 30,000 operations

  5. Medium Voltage Products Low/mid duty – high duty 12kV ...2500A ...31.5kA 17.5kV ...2500A ...31.5kA 24kV ...2500A ...25kA classic VD4 new VD4 12kV > 2500A ...31.5kA 12kV 1250...4000A 40...63kA 17.5kV > 2500A ...31.5kA 17.5kV 1250...4000A 40kA 36kV ...3150A ...40kA 40.5kV ...3150A ...31.5kA VD4 high duty low/mid duty and ANSI ratings for ADVAC

  6. Classic and New VD4 Ratings / Standard • new VD4 vacuum circuit breaker : • only embedded poles • fixed and withdrawable versions • compliance to IEC 62271-100 (2001-05) STDs • low/mid duty: • 12 kV, ... 2500 A, ... 31.5 kA • 17,5 kV, ... 2500 A, ... 31.5 kA • 24 kV, ... 2500 A, ... 25 kA ( up to 40/50 kA within 4Q 2003 )

  7. Classic and New VD4 Design / View

  8. Classic and New VD4 Design / Dimensions (*) 610 mm standardized with 570 mm (no changes in the pole distance) (**) 750 mm standardized with 700 mm (no changes in the pole distance)

  9. Classic and New VD4 Design / Dimensions Different position of ON / OFF buttons Classic VD4 fixed version 1212-25, P150 New VD4 fixed version 1212-25, P=150

  10. Classic and New VD4 Design / Dimension of front plate New VD4

  11. Classic and New VD4 Design / External dimensions Classic VD4 fixed version P1 P4 P2 P5 12kV, ... 1250 A, ... 31.5 kA 17.5 kV, ... 1250 A, ... 31.5 kA p H a b c d e mm mm mm mm mm mm mm 150 205 450 424 433 217.5 475 210 205 570 424 433 217.5 475 24 kV, ... 1250 A, ... 25,kA p H a b c d e mm mm mm mm mm mm mm 210 310 570 424 433 282.5 6311) 275 310 700 424 433 282.5 6311) • 12kV, 1600-2500 A, ... 40 kA • 17.5 kV, 1600-2500 A, ... 31.5 kA • p H a b c d e • mm mm mm mm mm mm mm • 210 310 610 424 433 237.5 599 2) • 310 750 424 433 237.5 599 2) • 24,kV, 1600-2500 A, ... 25,kA • p H a b c d e • mm mm mm mm mm mm mm • 275 310 750 424 433 282.5 642 2) 1) measuring point pole part 2) pole with heat-sink 616 mm 3) pole with heat-sink 661 mm - 6394 E 03-07-2001-

  12. Classic and New VD4 Design / External dimensions New VD4 fixed version P1 P4 P2 P5 12kV, ... 1250 A, ... 31.5 kA 17.5 kV, ... 1250 A, ... 31.5 kA p H a b c d e mm mm mm mm mm mm mm 150 205 450 424 433 217.5 475 (A) 210 205 570 424 433 217.5 475 (B) 24 kV, ... 1250 A, ... 25,kA p H a b c d e mm mm mm mm mm mm mm 210 310 570 424 433 282.5 631 1)(B) 275 310 700 424 433 282.5 631 1) (C) • 12kV, 1600-2500 A, ... 31,5 kA • 17.5 kV, 1600-2500 A, ... 31.5 kA • p H a b c d e • mm mm mm mm mm mm mm • 210 310 570 424 433 237.5 599 2) (B) • 310 700 424 433 237.5 599 2) (C) • 24,kV, 1600-2500 A, ... 25,kA • p H a b c d e • mm mm mm mm mm mm mm • 275 310 700 424 433 282.5 642 3) 1)measuring point pole part 2) pole with heat-sink 616 mm 3) pole with heat-sink 661 mm (A) fully interchangeability with classic VD4 by fixing points 345 x 400 (B) fully interchangeability with classic VD4 by fixing points 345 x 520 (C) fully interchangeability with classic VD4 by fixing points 345 x 650

  13. Classic and New VD4 Dimension / Design Withdrawable circuit breaker (available for the time being) • OK at 12 -17.5 kV; Under development at 24 kV with distance between terminals 380 mm • Under development • Yes with assembled pole; NO with embedded poles

  14. Classic and New VD4 B O D E F G A C L I M N H Operating mechanism (type EL / new VD4) A Open/closed auxiliary contacts B Auxiliary circuits terminal box C Charged/discharged closing springs mechanical indicator D Closing push button E Opening push button F Auxiliary releases (opening / closing / undervoltage) G Electrical accessories plug-socket connectors H Closing spring motor geared I Circuit-breaker open/closed mechanical indicator L Built-in closing spring charging lever M Mechanical operation counter N Opening spring O Damper (opening)

  15. Classic and New VD4 Operating mechanism / Characteristics (*) all new VD4 are Pehla certified O-0.3s-CO-3min-CO; VD4 17.20.32 and VD4 24.06.16 are already certified O-0.3s-CO-15s-CO (it is on going the activity for the certification of all new VD4 with the operation sequence O-0.3s-CO-15s-CO) (**) alternative solution with PR 521 and – MO3 already available

  16. Classic and New VD4 Maintenance • 1) cycles under normal operating conditions, depending on breaker type, given regularly and conscientiously performed maintenance • replacementmay be carried out only by ABB personnel or trained and qualified customer personnel • M2 class means 10,000 operations without maintenance; the activity is on going for 30,000 operations without maintenance; 30,000 operations without maintenance will be available within 4Q 2003 • replacement after 10,000 operations (depending on circuit breaker type) : blocking lever, half shaft, crank; replacement after 20,000 operations (depending on circuit breaker type) : latch, complete supporting crank, spring, shaft, cam disk, return rotation blocking • replacement after 10,000 operations: actuator unit (snapping unit only; see next slide; snapping unit for 30,000 operations without maintenance will be available within 4Q 2003) replacement after 15,000 operations: shock absorber (the damper “shock absorber” for 30,000 operations will be available within 4Q 2003)

  17. Classic and New VD4 Maintenance / Mechanical actuator New VD4 – actuator unit replacement: removal sequence 1) 1 Fixing screws 2 Fixing screws 3 Fixing screws 4 Fixing 5 Bearings 6 Kinematic linkage 7Same operations in reverse order for mounting • removal and mounting require approx. 20 min; the replacement is easier and faster respect to the replacement of single components in the classic c.breaker

  18. Classic and New VD4 Accessories / Standard • shunt releases are fundamentally wired with rectifiers (function as free-wheeling diodes if DC-supply) in order to obtain anti-pumping function; shunt releases are not mandatory with „new VD4“ in order to have anti-pumping function • mandatory for UniGear type ZS1, UniSafe, PowerBox; inclusive mechanical interlock (striker pin)if rated current is different from the panel • prevents the CB being racked into the panel with plug not inserted in the socket or no aux. Voltage; not available for motorized truck version

  19. Classic and New VD4 Accessories / On request 1) available free contacts depend on maximum of the requested applications

  20. Classic and New VD4 Accessories / Technical data 1) depending on supply voltage 2) the permanently supplied release ON carries out the electrical anti-pumping function 3) development on going

  21. Classic and New VD4 Others / Specials

  22. Classic and New VD4 Marketing tools English / German / Italian / other language (• under construction,• available,• available in “Inside ABB” )

  23. A global leaderin power and automation technologiesthat enable utility and industry customersto improve their performancewhile lowering environmental impact