Rack cooling in building 904. Primary side. Secondary circuit. 13/18oC. Total flow= 21.5m3/h, DN80. Chiller side. DP=1bar. 9 rooms 50kW. Total flow=14.35m3/h DN65. Flow per room= 0.8m3/h, 5.5kW, DN25. 45 racks, Max Power per rack 10kW, 1.4m3/h DN25.
E N D
Secondary circuit 13/18oC Total flow= 21.5m3/h, DN80 Chiller side DP=1bar 9 rooms 50kW Total flow=14.35m3/h DN65 Flow per room= 0.8m3/h, 5.5kW, DN25 45 racks, Max Power per rack 10kW, 1.4m3/h DN25