An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Electricity Restructuring Roundtable (89)New York’s DG/CHP Experience To Date Challenges & Opportunities Doug Lutzy NYS Department of Public Service June 17, 2005

  2. Basics of the New York Electric System • 6 Major Investor-Owned Utilities • 2 Large Power Authorities • 47 Small Municipalities • 4 Small Rural Electric Co-ops • Diverse territory • 47,000 square miles • Con Edison/NYC, 600 square miles, 3.1 million customers • Adirondack Park, 3900 sq mi, less than 100,000 customers • Load: 32,000 MW at peak -- 16,500 MW in NYC & Long Island • Extreme electric transmission congestion downstate • Generating capacity: 39,000 MW

  3. DG - Rules of Grid Interconnection • New York has standard interconnection requirements • 2 MW and under • Includes networks • Model contract language • Defines process/deadlines • Con Edison to use NY SIR timing requirements for units up to 5 MW • Development of rules a collaboration • Utilities implement rules • PSC enforces rules and resolves conflicts • Guidelines for connection charges vary • Small units - no fee • Larger units -- cost reimbursement • Connection is governed by utility • Safety

  4. DG - Rules of Grid Interconnection • Engineering reviews of system characteristics for DG units • units under 15kVa using certified equipment get minimal review • Net Metering allowed • Residential PV up to 10 kw • Farm waste up to 400 kw • Wind – Residential up to 25 kw • Farms up to 125 kw • Final rules still pending • NY active in efforts by FERC and others to develop National Interconnection Standards

  5. Standby Rates • Basic provisions of Standby Rates • Monthly customer and contract demand charges reflecting costs associated with service and customers maximum annual demand for access to the delivery grid • as-used on-peak daily demand billing element reflects incremental delivery costs associated with on-peak deliveries for all interval metered customers (> 50 kW) • produces stronger price signal to run OSG/DG and displace more expensive utility on-peak deliveries • increases delivered on-peak grid commodity (energy) prices • Standby Rates Option • Hourly load-integrated market commodity prices available for all interval metered (> 50 kW) standby customers • commodity service bill directly reflects cost consequences of customer’s individual behavior (not class average) • OSG/DG have better information upon which to choose between buying energy from the grid or generating themselves

  6. Standby Rates • Existing Units • immediate billing @ full standby rate OR • phase-in to full standby rate (fixed 8 year period) • initial 4 years at standard rates • 2nd 4 years at equal % increase • Exempt Technologies • Fuel cells, wind, solar thermal, PV, sustainably-managed biomass, geothermal, methane waste, and small (=/< 1 MW) efficient CHP • Options • immediate billing @ standard delivery rates OR • may choose immediate billing @ full standby rates • Need to commence operation between July 29, 2003 and May 31, 2006

  7. CHP Incentive/Development Programs • NYSERDA Funding, primarily via SBC • Demonstration projects, studies, and technology development • Project commitments to date • 84.6 MW -- 12.6 MW operational • $43 million in funding, • $160 million committed by developers • Standby Rate CHP Exemption • =/< 1 MW, serving no more than 100% of customer’s maximum potential demand • 60% overall annual efficiency • thermal loads utilize at least 20% of CHP total usable annual energy output

  8. Emergency Demand Response (EDRP) • Voluntary load curtailment program activated by the NYISO during periods of potential shortfall in electricity supply. • Incentive based, no penalties. • Current registration over 1100 customers, representing nearly 600 MW of load-- about 250 MW from emergency generators.

  9. Emergency Demand Response (EDRP) (cont’d) • Environmental concerns for generating units in EDRP programs. • NY DEC ‘s proposal is for exempting allexisting DG resources until 2008, providing these units with a 3-yr pass on emissions limits, and setting standards for all existing engines to achieve in 2008 (i.e., 27 lb/MWh NOx limit). • New Emergency Diesel non-EDRP Generators installed after 2005 face 16 lb/ MWh NOx limit. After 2010 a 6 lb/MWh NOx limit. • New Emergency Diesel Generators opting into EDRP after 2005 face 1.6 lb/MWh NOx limit. (This provision currently under debate) • Proposed rule implementation recently delayed from 2005 to 2006.

  10. Installed Capacity-Special Case Resources(ICAP-SCR) • Pays customers to provide load reduction capability during a contractual period. Program is called when system reserve shortfall expected. • Current registration over 1050 customers, representing nearly 800 MW of load-- about 27 MW from generation.