Energy Management with Dupline

Energy Management with Dupline. Gas. Water. Electricity. PC I/O Card. Pulse Output. Pulse Input. Data Logger. Multicore Cable. Pulse Output. Pulse Input. PLC. Handling Pulses- Conventional System. Serial Interface RS232/RS485 Modbus protokol. PC. Gas. Water. Electricity.

lilah
Download Presentation

Energy Management with Dupline

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Energy Management with Dupline Jens Neigaard

  2. Gas Water Electricity PC I/O Card Pulse Output Pulse Input Data Logger Multicore Cable Pulse Output Pulse Input PLC Handling Pulses- Conventional System Jens Neigaard

  3. Serial Interface RS232/RS485 Modbus protokol PC Gas Water Electricity CARLO GAVAZZI 1.1 1.1 1.1 1.1 1.1 1.5 1.5 1.5 1.5 1.5 2.1 2.1 2.1 2.1 2.1 2.5 2.5 2.5 2.5 2.5 Pulse Output 1.2 1.2 1.2 1.2 1.2 1.6 1.6 1.6 1.6 1.6 2.2 2.2 2.2 2.2 2.2 2.6 2.6 2.6 2.6 2.6 R Dupline Mastergenerator CARLO GAVAZZI ON LINE BUSY FAULT G 4420 7401 230 G 4420 7401 230 G 4420 7401 230 G 4420 7401 230 G 4420 7401 230 1.3 1.3 1.3 1.3 1.3 1.7 1.7 1.7 1.7 1.7 2.3 2.3 2.3 2.3 2.3 2.7 2.7 2.7 2.7 2.7 Dupline Bus Pulse Output 1.4 1.4 1.4 1.4 1.4 1.8 1.8 1.8 1.8 1.8 2.4 2.4 2.4 2.4 2.4 2.8 2.8 2.8 2.8 2.8 PLC Handling Pulses- Dupline based System Jens Neigaard

  4. Profibus-DP LonWorks Ethernet (Modbus TCP) Modbus Electricity Gas Water CARLO GAVAZZI 1.1 1.1 1.1 1.1 1.1 1.5 1.5 1.5 1.5 1.5 2.1 2.1 2.1 2.1 2.1 2.5 2.5 2.5 2.5 2.5 1.2 1.2 1.2 1.2 1.2 1.6 1.6 1.6 1.6 1.6 2.2 2.2 2.2 2.2 2.2 2.6 2.6 2.6 2.6 2.6 R Dupline Gateway CARLO GAVAZZI ON LINE BUSY FAULT G 4420 7401 230 G 4420 7401 230 G 4420 7401 230 G 4420 7401 230 G 4420 7401 230 1.3 1.3 1.3 1.3 1.3 1.7 1.7 1.7 1.7 1.7 2.3 2.3 2.3 2.3 2.3 2.7 2.7 2.7 2.7 2.7 Dupline Bus 1.4 1.4 1.4 1.4 1.4 1.8 1.8 1.8 1.8 1.8 2.4 2.4 2.4 2.4 2.4 2.8 2.8 2.8 2.8 2.8 Handling Pulses - Dupline based System Pulse Output Pulse Output Jens Neigaard

  5. Irrigation System Control with Dupline • 4 x S0 (10 mA @ 24VDC) count inputs • Internal Counting in EEPROM • Reset possibility • 32 Multiplex addresses • Selection of 2,4,6 or 8 BCD digits • Counter values can be read from • Master Generator via ModBus or via • Fieldbus Gateways • Possibility for ”ON-time” Counting • DIN-rail Mounting • 115 VAC / 230 VAC / 24 VDC Power Supply Jens Neigaard

  6. WM2-96 16-bit P TecH m Power Analyzer Free Cable topology CARLO GAVAZZI CARLO GAVAZZI CARLO GAVAZZI 32-bit P TecH m 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 WM3-96 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 R Smart Power Quality Analyzer R R system CARLO GAVAZZI line MODE CARLO GAVAZZI CARLO GAVAZZI L L DOWN Dupline ENTER PRG WM2-DIN WM2-DIN G 4420 7401 230 G 4420 7401 230 G 4420 7401 230 G 4420 7401 230 G 4420 7401 230 G 4420 7401 230 G 4420 7401 230 G 4420 7401 230 G 4420 7401 230 G 4420 7401 230 G 4420 7401 230 POWER ANALYZER POWER ANALYZER 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 UP L R 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 Electricity Electricity Water RS232 Gas Mastergenerator ! ! F PRG G 4420 7401 230 ON LINE BUSY FAULT measures S Simple Energy Monitoring System Jens Neigaard

  7. WM2-96 16-bit P TecH m Power Analyzer I/O module I/O module Free Cable topology CARLO GAVAZZI CARLO GAVAZZI CARLO GAVAZZI 32-bit P TecH m 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 WM3-96 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 R Smart Power Quality Analyzer R R system CARLO GAVAZZI line MODE CARLO GAVAZZI CARLO GAVAZZI L L DOWN Dupline ENTER PRG WM2-DIN WM2-DIN G 4420 7401 230 G 4420 7401 230 G 4420 7401 230 G 4420 7401 230 G 4420 7401 230 G 4420 7401 230 G 4420 7401 230 POWER ANALYZER POWER ANALYZER 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 UP L R 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 Electricity Electricity Water RS232 Gas Mastergenerator ! ! F PRG G 4420 7401 230 ON LINE BUSY FAULT measures S Energy Monitoring System combined with digital and analog I/O Jens Neigaard

  8. Network with up to 32 Master Generators RS232 Modbus MGEN Master #32 Transmitter Counters Digital I/O Analog I/O MGEN Slave #1 Transmitter Counters Digital I/O Analog I/O RS485 Modbus MGEN Slave #2 Transmitter Counters Digital I/O Analog I/O Jens Neigaard

  9. PLC Gateway #1 Transmitter Counters Digital I/O Analog I/O Gateway #2 Transmitter Counters Digital I/O Analog I/O Profibus-DP LonWorks Ethernet TCP/IP Modbus Gateway #3 Transmitter Counters Digital I/O Analog I/O Network with up to 32 Fieldbus Gateways Jens Neigaard

  10. Interface today • Via Modbus driver • Specview directly • The future • Via OPC server Software Software Options • DDE Server • SCADA software Jens Neigaard

  11. Dupline advantages • Long distance • Free topology • High Noise Immunity • Easy handling • Easy to configure • No need for special cable • No shield and cable terminations required • Counters can be combined with wide Dupline product range, e.g. for machine monitoring and load control • Easy to expand an installation in steps as need appear • Cost-effective Jens Neigaard

  12. Application: Factory Process Monitoring Jens Neigaard

  13. Application: Factory Process Monitoring • Register energy consumption on individual machines, processes or sections of production • - Allocate energy cost to production batches • - Allocate cost to departments • - Overview of energy consumption can be used as input for energy saving strategy • - Document energy savings • Switch loads like lights, ventilation, heating etc • - Keep total energy consumption below allowed levels • - Save energy • - Sequenced start-up of machines Jens Neigaard

  14. Application: Factory Process Monitoring • Register Machine Run Times • - Improved planning of preventive maintenance • - Enables analyses of reasons for machine down- time to be used for improvement of machine efficiency • - Overview of Machine Efficiency can be used in production planning • Immediate central/local reporting of machine alarms • - Reduced machine downtime • Register Machine Alarms • - Enables analyses of machine and operator performance Jens Neigaard

  15. Tourism The situation: a big campsite provide the power supply to different kind of users: campers who rent a bungalow or park their own caravan or tent. The problem: the camping managementneed to collect the single site energy data and read them by means of a PC placed in the reception. The aim is to split the total energy costs, according to the users, avoiding to go on site to read the energy meters whenever a customer leaves. Application: Camping Sites and Yacht Harbours Jens Neigaard

  16. Tourism The solution: EM1-DIN with pulse output is used to monitor the single site energy consumption. All the energy readings in the camping sites is transmitted to a central PC via Dupline, which easily solves the application with its free topology, reliability and capability to transmit signals over distances up to 10 km. The Camp management can also control the access to electricity because a Dupline relay is assigned to each single site Application: Camping Sites and Yacht Harbours Jens Neigaard

  17. Application: Commercial- and Apartment Buildings • Split the energy cost between shops or residents • Split the water- and gas cost between shops or residents Jens Neigaard

  18. SMS Alarms SMS Alarms GSM/ Counter values GSM/ Counter values Apartment owner Building administrator administrate data Server for data collection via GSM modem Internet/ Presentation Of data Jens Neigaard