1 / 8

Proposed Changes to PTCS Duct Standards

Proposed Changes to PTCS Duct Standards. April 7 th , 2009 Regional Technical Forum. Subcommittee Conference Call. February 24, 2009 Attendees: Mark Johnson David Hales Andres Morrison Bruce Manclark Mark Jerome Brady Peeks Adam Hadley

gordon
Download Presentation

Proposed Changes to PTCS Duct Standards

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Proposed Changes to PTCSDuct Standards April 7th, 2009 Regional Technical Forum

  2. Subcommittee Conference Call • February 24, 2009 • Attendees: • Mark Johnson • David Hales • Andres Morrison • Bruce Manclark • Mark Jerome • Brady Peeks • Adam Hadley • Outcome: Developed recommended changes to the PTCS Duct Standards

  3. PTCS Duct StandardsSubcommittee-Recommended Changes • Put all “duct testing procedures” language in a separate document. • Remove “program standards” language, which required a specific pre-existing leakage rate for manufactured homes (the dry hole test). (Old p.7 #2) • Note: This is not a recommendation to programs to stop pre-screening for payment, simply a recommendation to take the language out of the duct standards document. • Significantly reformat/organize document to make it “spec-like”.

  4. PTCS Duct StandardsSubcommittee-Recommended Changes • Add a requirement to replace insulation. (New 5.2) New Language: Where a large section of duct insulation is removed, the insulation shall be re-installed and securely attached to the duct system. Recommended methods include the use of twine. Mastic will not effectively hold insulation in place.

  5. PTCS Duct StandardsSubcommittee-Recommended Changes • Add the following External Static Pressure “should” to New Homes and Existing Homes/New Ducts section: (New 6.1.2 and 6.2.5) New Language: “If a new air handler is being installed, the total external static pressure acting on the system air handler should be tested with approved instruments and recorded at time of startup. A measured external static pressure of more than 0.8” (200 Pa) should cause installer to consider taking corrective measures with system ductwork.“ Note: This is not a “shall” in the duct specs because it is a “shall” for PTCS heat pumps. In the case of a gas furnace, a “shall” here would hand this responsibility to the duct sealing contractor - something the subcommittee didn’t want to do. Furthermore, the existing contractors are not trained to do this test.

  6. PTCS Duct StandardsSubcommittee-Recommended Changes • Update the supply side only test leakage requirements (Old p.5 section C; New 6.3.4) Old Language: • In extreme cases where return ducts are inaccessible, compliance with either (0.10CFM50 x ft2) or (50% reduction) may be accomplished by testing the supply side only New Language: In cases where return ducts are inaccessible, compliance with (0.10CFM50 x ft2) or (50% reduction) may be accomplished by performing the Duct Leakage to the Exterior test on the supply side only (using the more stringent of the two – whichever is less). Reason for the Change: The subcommittee agreed this is what has been intended all along, and that the previous specification was in error.

  7. PTCS Duct StandardsSubcommittee-Recommended Changes • Modify Manufactured Home language: (Old p.7 #5; New 6.4.4) Old language: If the final tested leakage rate is greater than 75 CFM50, the air handler-to-duct transition connection shall be sealed with proper materials. New language requires: If the final tested leakage rate is greater than 50 CFM50 for single wide homes, plus an additional 30 CFM50 for each additional section, the air-handler transition-to-trunk duct connection shall be sealed.

  8. PTCS Duct StandardsSubcommittee-Recommended Changes • Remove all CAZ testing requirements; modify CO alarm requirement. (Old p.3 #3&4, p.4 #3&4, p.5 #2&3, p.7 #3&4; New 7.1) Old Language: • Based on the protocol for “Combustion Appliance Zone Pressure Testing” forced air system operation shall not de-pressurize a combustion appliance zone by more than 3 Pascals. • When combustion appliances are located within a conditioned space a UL listed carbon monoxide alarm, or equivalent must be installed. New Language: Whenever there is a Combustion Appliance present in the house, garage, or other attached space, a UL listed, C-UL listed, or equivalent carbon monoxide alarm shall be installed in accordance with the carbon monoxide alarm manufacturer’s instructions. Reason for the Change: The CAZ test is not always a reliable test. Test repeatability is questionable. It is also not possible to perform the test in all weather conditions.

More Related