80 likes | 254 Views
Proposed Changes to PTCS Duct Standards. April 7 th , 2009 Regional Technical Forum. Subcommittee Conference Call. February 24, 2009 Attendees: Mark Johnson David Hales Andres Morrison Bruce Manclark Mark Jerome Brady Peeks Adam Hadley
E N D
Proposed Changes to PTCSDuct Standards April 7th, 2009 Regional Technical Forum
Subcommittee Conference Call • February 24, 2009 • Attendees: • Mark Johnson • David Hales • Andres Morrison • Bruce Manclark • Mark Jerome • Brady Peeks • Adam Hadley • Outcome: Developed recommended changes to the PTCS Duct Standards
PTCS Duct StandardsSubcommittee-Recommended Changes • Put all “duct testing procedures” language in a separate document. • Remove “program standards” language, which required a specific pre-existing leakage rate for manufactured homes (the dry hole test). (Old p.7 #2) • Note: This is not a recommendation to programs to stop pre-screening for payment, simply a recommendation to take the language out of the duct standards document. • Significantly reformat/organize document to make it “spec-like”.
PTCS Duct StandardsSubcommittee-Recommended Changes • Add a requirement to replace insulation. (New 5.2) New Language: Where a large section of duct insulation is removed, the insulation shall be re-installed and securely attached to the duct system. Recommended methods include the use of twine. Mastic will not effectively hold insulation in place.
PTCS Duct StandardsSubcommittee-Recommended Changes • Add the following External Static Pressure “should” to New Homes and Existing Homes/New Ducts section: (New 6.1.2 and 6.2.5) New Language: “If a new air handler is being installed, the total external static pressure acting on the system air handler should be tested with approved instruments and recorded at time of startup. A measured external static pressure of more than 0.8” (200 Pa) should cause installer to consider taking corrective measures with system ductwork.“ Note: This is not a “shall” in the duct specs because it is a “shall” for PTCS heat pumps. In the case of a gas furnace, a “shall” here would hand this responsibility to the duct sealing contractor - something the subcommittee didn’t want to do. Furthermore, the existing contractors are not trained to do this test.
PTCS Duct StandardsSubcommittee-Recommended Changes • Update the supply side only test leakage requirements (Old p.5 section C; New 6.3.4) Old Language: • In extreme cases where return ducts are inaccessible, compliance with either (0.10CFM50 x ft2) or (50% reduction) may be accomplished by testing the supply side only New Language: In cases where return ducts are inaccessible, compliance with (0.10CFM50 x ft2) or (50% reduction) may be accomplished by performing the Duct Leakage to the Exterior test on the supply side only (using the more stringent of the two – whichever is less). Reason for the Change: The subcommittee agreed this is what has been intended all along, and that the previous specification was in error.
PTCS Duct StandardsSubcommittee-Recommended Changes • Modify Manufactured Home language: (Old p.7 #5; New 6.4.4) Old language: If the final tested leakage rate is greater than 75 CFM50, the air handler-to-duct transition connection shall be sealed with proper materials. New language requires: If the final tested leakage rate is greater than 50 CFM50 for single wide homes, plus an additional 30 CFM50 for each additional section, the air-handler transition-to-trunk duct connection shall be sealed.
PTCS Duct StandardsSubcommittee-Recommended Changes • Remove all CAZ testing requirements; modify CO alarm requirement. (Old p.3 #3&4, p.4 #3&4, p.5 #2&3, p.7 #3&4; New 7.1) Old Language: • Based on the protocol for “Combustion Appliance Zone Pressure Testing” forced air system operation shall not de-pressurize a combustion appliance zone by more than 3 Pascals. • When combustion appliances are located within a conditioned space a UL listed carbon monoxide alarm, or equivalent must be installed. New Language: Whenever there is a Combustion Appliance present in the house, garage, or other attached space, a UL listed, C-UL listed, or equivalent carbon monoxide alarm shall be installed in accordance with the carbon monoxide alarm manufacturer’s instructions. Reason for the Change: The CAZ test is not always a reliable test. Test repeatability is questionable. It is also not possible to perform the test in all weather conditions.